Air Break Circuit Breaker

Edwiin
Edwiin
Field: Power switch
China

In an air break circuit breaker, the arc is initiated and extinguished in substantially static air as the arc moves. These breakers are used for low voltages, generally up to 15 kV, with rupturing capacities of 500 MVA. As an arc-quenching medium, air circuit breakers offer several advantages over oil, including:

  • Elimination of risks and maintenance associated with oil use.

  • Absence of mechanical stress caused by gas pressure and oil movement.

  • Elimination of costs from regular oil replacement due to oil deterioration from successive breaking operations.

In air break circuit breakers, contact separation and arc extinction occur in air at atmospheric pressure, employing the high-resistance principle. The arc is expanded via arc runners and chutes, while arc resistance is increased through splitting, cooling, and lengthening.

Arc resistance is heightened until the voltage drop across the arc exceeds the system voltage, extinguishing the arc at the current zero point of the AC wave.

Air break circuit breakers are used in DC circuits and AC circuits up to 12,000 V. Typically indoor types, they are installed on vertical panels or indoor draw-out switchgear, widely applied in indoor medium- and low-voltage switchgear for AC systems.

Plain Break Type Air Break Circuit Breaker

The simplest variant features two horn-shaped contacts. Arcing initially occurs across the shortest distance between the horns and is steadily driven upward by convection currents from arc-heated air and the interaction of magnetic and electric fields. As the horns fully separate, the arc extends from tip to tip, achieving lengthening and cooling.

The process’s relative slowness and the risk of arc spreading to adjacent metal components limit its application to approximately 500 V and low-power circuits.

Magnetic Blow-Out Type Air Break Circuit Breaker

Used in circuits with voltages up to 11 kV, arc extinction in some air circuit breakers is achieved via a magnetic field from blowout coils connected in series with the interrupted circuit. These coils move the arc into chutes—they do not extinguish the arc themselves. In the chutes, the arc is lengthened, cooled, and extinguished. Arc shields prevent arc spreading to adjacent networks.

Polarity, Arc Chutes, and Operational Details of Air Break Circuit Breakers
Importance of Coil Polarity

Correct coil polarity is critical to direct the arc upward, leveraging electromagnetic forces to enhance arc movement. This principle becomes more effective with higher fault currents, enabling such breakers to achieve higher rupturing capacities.

Arc Chute Functionality

An arc chute is a key device for arc extinction in air, performing three interrelated roles:

  • Arc Confinement: Restricts the arc to a defined space, preventing uncontrolled spread.

  • Magnetic Control: Guides arc movement via magnetic fields to facilitate extinction within the chute.

  • Rapid Cooling: Deionizes arc gases through intense cooling, ensuring arc quenching.

Air Chute Air Break Circuit Breaker Design

For low- and medium-voltage circuits, this breaker features:

  • Dual Contact Sets:

    • Main Contacts: Copper-based, silver-plated for low resistance, conducting normal current in the closed position.

    • Arcing (Auxiliary) Contacts: Heat-resistant copper alloy, designed to withstand arcing during fault interruption. They close before and open after the main contacts to protect the main contacts from damage.

  • Blowout Mechanism: Steel inserts in the arcing chutes create magnetic fields that accelerate upward arc movement. These plates split the arc into series of short arcs, increasing total voltage drop (anode + cathode drops) across the arcs. If this sum exceeds the system voltage, the arc extinguishes rapidly.

  • Cooling Action: Arc contact with cool steel plates rapidly cools and deionizes the arc, aided by natural or magnetic blowout forces.

Working Principle

  • Fault Occurrence: Main contacts separate first, shifting current to the arcing contacts.

  • Arc Formation: As arcing contacts separate, an arc draws between them.

  • Arc Movement: Electromagnetic and thermal forces drive the arc upward along arc runners.

  • Arc Splitting & Extinction: The arc is split by splitter plates, lengthened, cooled, and deionized, leading to extinction.

Applications

  • Power Station Auxiliaries & Industrial Plants: Suitable for environments requiring fire/explosion hazard mitigation.

  • DC Systems: Employ arc lengthening, runners, and magnetic blowout for breakers up to 15 kV.

Limitation

  • Low-Current Inefficiency: Arc chutes are less effective at low currents due to weaker electromagnetic fields, causing slower arc movement into the chute and potentially delayed interruption.

This design balances simplicity and reliability for medium/low-voltage applications, though its performance varies with current magnitude.

Give a tip and encourage the author!
Recommended
PT Fuse Slow Blow: Causes, Detection & Prevention
PT Fuse Slow Blow: Causes, Detection & Prevention
I. Fuse Structure and Root Cause AnalysisSlow Fuse Blowing:From the design principle of fuses, when a large fault current passes through the fuse element, due to the metal effect (certain refractory metals become fusible under specific alloy conditions), the fuse first melts at the soldered tin ball. The arc then rapidly vaporizes the entire fuse element. The resulting arc is quickly extinguished by quartz sand.However, due to harsh operating environments, the fuse element may age under the comb
Edwiin
10/24/2025
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Common Causes of Fuse BlowingCommon reasons for fuse blowing include voltage fluctuations, short circuits, lightning strikes during storms, and current overloads. These conditions can easily cause the fuse element to melt.A fuse is an electrical device that interrupts the circuit by melting its fusible element due to heat generated when current exceeds a specified value. It operates on the principle that, after an overcurrent persists for a certain period, the heat produced by the current melts
Echo
10/24/2025
Fuse Maintenance & Replacement: Safety and Best Practices
Fuse Maintenance & Replacement: Safety and Best Practices
1. Fuse MaintenanceFuses in service should be regularly inspected. The inspection includes the following items: Load current should be compatible with the rated current of the fuse element. For fuses equipped with a fuse blown indicator, check whether the indicator has actuated. Check the conductors, connection points, and the fuse itself for overheating; ensure connections are tight and making good contact. Inspect the fuse exterior for cracks, contamination, or signs of arcing/discharge. Liste
James
10/24/2025
Maintenance and Repair Items for 10kV High-Voltage Switchgear
Maintenance and Repair Items for 10kV High-Voltage Switchgear
I. Routine Maintenance and Inspection(1) Visual Inspection of Switchgear Enclosure No deformation or physical damage to the enclosure. Protective paint coating shows no severe rust, peeling, or flaking. Cabinet is securely installed, clean on the surface, and free of foreign objects. Nameplates and identification labels are neatly affixed and not falling off.(2) Check of Switchgear Operating Parameters Instruments and meters indicate normal values (comparable to typical operating data, with no s
Edwiin
10/24/2025