• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Types & Characteristics of Surge Arresters

Edwiin
Edwiin
Field: Power switch
China

Introduction

Atmospheric lightning strikes on overhead lines, bare conductors, or metallic structures in outdoor substations, as well as overvoltages caused by switching operations of equipment and networks (switching overvoltages), pose significant hazards to electrical equipment. To protect equipment and facilitate insulation coordination, surge arresters (also known as "lightning arresters") must be installed at the incoming/outgoing points of overhead lines and in close proximity to transformers, due to their limited spatial protection zone.

Types and Characteristics of Surge Arresters

The most common surge arresters are non-linear metal oxide (MO) resistor type, housed in porcelain or silicone rubber. These are connected in parallel with the protected equipment and grounded via the earth grid. Another construction type uses silicon carbide (SiC) resistors (valve-type arresters), though these are less prevalent today.

Key Electrical Characteristics:

  • Resealing Voltage: The voltage across the arrester at which the follow current is reliably interrupted after sparkover.

  • Maximum Continuous Operating Voltage (MCOV): The highest power-frequency voltage (50 Hz or 60 Hz) that the arrester can withstand indefinitely.

  • Rated Short-Circuit Current: The maximum short-circuit current the arrester can safely handle.

  • Nominal Discharge Current: Common values include 5 kA, 10 kA, and 20 kA, indicating the arrester’s capacity to dissipate surge energy.

Surge arresters are connected between live conductors and ground. In installations with voltages above 52 kV, they may include discharge operation counters to monitor performance. An example of surge arresters is shown in Figure 1.

Additional Methods

In overhead lines and outdoor substations with voltages above 52 kV, it is common practice to install a lightning protection system comprising "lightning rods," "lightning aerial protection wires," or a combination of both.

LV Overvoltage Protection

Low Voltage (LV, where ) equipment, particularly electronic and informatics systems, is highly susceptible to severe damage from lightning discharges that propagate through cables or building structures.

To mitigate such risks, power surge protectors (SPDs) are typically installed in LV switchboards. These devices feature standard nominal discharge currents of 5 kA, 10 kA, and 20 kA, with some advanced models capable of handling 30–70 kA.

Similar to surge arresters, SPDs are connected between live conductors and ground, as illustrated in Figure 4. This configuration diverts surge currents away from sensitive equipment, ensuring protection against overvoltage events.

Give a tip and encourage the author!
Recommended
Why does a 2-in 4-out 10 kV solid-insulated ring main unit have two incoming feeder cabinets?
Why does a 2-in 4-out 10 kV solid-insulated ring main unit have two incoming feeder cabinets?
A "2-in 4-out 10 kVsolid-insulated ring main unit" refers to a specific type of ring main unit (RMU). The term "2-in 4-out" indicates that this RMU has two incoming feeders and four outgoing feeders.10 kVsolid-insulated ring main unit are equipment used in medium-voltage power distribution systems, primarily installed in substations, distribution stations, and transformer stations to distribute high-voltage power to low-voltage distribution networks. They generally consist of high-voltage incomi
Garca
12/10/2025
Low-Voltage Distribution Lines and Power Distribution Requirements for Construction Sites
Low-Voltage Distribution Lines and Power Distribution Requirements for Construction Sites
Low-voltage distribution lines refer to the circuits that, through a distribution transformer, step down the high voltage of 10 kV to the 380/220 V level—i.e., the low-voltage lines running from the substation to the end-use equipment.Low-voltage distribution lines should be considered during the design phase of substation wiring configurations. In factories, for workshops with relatively high power demand, dedicated workshop substations are often installed, where transformers supply power direc
James
12/09/2025
How to Implement Transformer Gap Protection & Standard Shutdown Steps
How to Implement Transformer Gap Protection & Standard Shutdown Steps
How to Implement Transformer Neutral Grounding Gap Protection Measures?In a certain power grid, when a single-phase ground fault occurs on a power supply line, both the transformer neutral grounding gap protection and the power supply line protection operate simultaneously, causing an outage of an otherwise healthy transformer. The main reason is that during a system single-phase ground fault, the zero-sequence overvoltage causes the transformer neutral grounding gap to break down. The resulting
Noah
12/05/2025
Chinese Protection Relay Earns IEC 61850 Ed2.1 Level-A Certification
Chinese Protection Relay Earns IEC 61850 Ed2.1 Level-A Certification
Recently, the NSR-3611 low-voltage protection and control device and the NSD500M high-voltage measurement and control device—both developed by a Chinese protection and control equipment manufacturer—successfully passed the IEC 61850 Ed2.1 Server Level-A certification test conducted by DNV (Det Norske Veritas). The devices have been awarded the international Level-A certification by the Utilities Communication Architecture International Users Group (UCAIug). This milestone marks the manufacturer
Baker
12/02/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.