What is Induction Voltage Regulators?

Edwiin
Field: Power switch
China

What is Induction Voltage Regulators?

Definition: An induction voltage regulator is a kind of electrical machine. Its output voltage can be adjusted, ranging from zero up to a specific maximum value. This range depends on the turn ratio between the primary and secondary windings. The primary winding is linked to the circuit that requires voltage regulation, while the secondary winding is connected in series with the same

 

Types of Induction Voltage Regulators

Induction voltage regulators are primarily categorized into two types: the single - phase induction voltage regulator and the three - phase induction voltage regulator.

Single - phase Induction Voltage Regulator

The schematic diagram of a single - phase induction voltage regulator is presented in the figure below. The primary winding is connected across the single - phase power supply, and the secondary winding is connected in series with the outgoing lines.


In this system, an alternating magnetic flux is induced. When the axes of the two windings align, all of the magnetic flux from the primary winding links with the secondary winding. As a result, the maximum voltage is induced in the secondary winding.

 

 

When the rotor is rotated by 90º, no part of the primary flux is linked with the secondary windings; thus, no flux is present in the secondary windings. If the rotor continues to rotate beyond this point, the direction of the induced electromotive force (emf) in the secondary becomes negative. Consequently, the regulator either adds to or subtracts from the circuit voltage, depending on the relative orientation of the two windings within the regulator.


The single - phase voltage regulator does not introduce any phase shift. The primary windings are installed in slots on the surface of the laminated cylindrical core. Since they carry relatively small currents, they have a small conductor cross - sectional area. The rotor of the regulator incorporates compensating windings, also referred to as tertiary windings.


The magnetic axis of the compensating windings is always oriented 90º away from that of the primary windings. This configuration serves to counteract the detrimental series reactance effect of the secondary windings. The secondary windings, which are connected in series with the outgoing line, are located in the stator slots because of their larger conductor area requirements.

Three - Phase Induction Voltage Regulator

Three - phase induction voltage regulators feature three primary windings and three secondary windings, which are spaced 120º apart from one another. The primary windings are placed in the slots of a laminated rotor core and are connected across a three - phase AC power supply. The secondary windings are housed in the slots of a laminated stator core and are connected in series with the load.

The regulator does not necessitate separate primary and compensating windings. This is because each secondary winding of the regulator is magnetically linked to one or more primary windings within the regulator. In this type of regulator, a rotating magnetic field of consistent magnitude is generated. As a result, the voltage induced in the secondary winding also has a constant magnitude. However, the phases of the regulator change in accordance with the variation in the rotor's position relative to the stator.

 

The phasor diagram of the induction regulator is depicted in the figure above. Here, (V1) represents the supply voltage, (Vr) is the voltage induced in the secondary, and (V2) denotes the output voltage per phase. The output voltage is derived as the phasor sum of the supply voltage and the induced voltage for any rotor displacement angle θ.


Consequently, the locus of the resultant is a circle. This circle is drawn with its center located on the tip of the supply voltage vector and has a radius equal to (Vr). The maximum output voltage is achieved when the induced voltage is in - phase with the supply voltage. Conversely, the minimum output voltage is obtained when the induced voltage is in anti - phase with the supply voltage.


The complete phasor diagram for the three - phase case is shown in the figure below. The terminals labeled AB, and C are the input terminals, while ab, and c are the output terminals of the induction regulator. The supply and the output line voltages are in - phase only at the maximum boost and minimum buck positions. For all other positions, there exists a phase displacement between the supply line voltage and the output voltage.

 

 

Give a tip and encourage the author!

Recommended

Main Transformer Accidents and Light Gas Operation Issues
1. Accident Record (March 19, 2019)At 16:13 on March 19, 2019, the monitoring background reported a light gas action of No. 3 main transformer. In accordance with the Code for Operation of Power Transformers (DL/T572-2010), operation and maintenance (O&M) personnel inspected the on-site condition of No. 3 main transformer.On-site confirmation: The WBH non-electrical protection panel of No. 3 main transformer reported a Phase B light gas action of the transformer body, and the reset was ineff
02/05/2026
Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr