What are the common challenges when using a split-core current transformer in industrial environments?

Encyclopedia
Field: Encyclopedia
0
China

Accuracy and calibration


Flux leakage


In open-close current transformer, the opening and closing of the iron core will lead to leakage of magnetic flux. Because the core is not a complete, continuous loop like a solid core transformer, part of the magnetic field line may escape through the gap. This can lead to inaccurate ratios. For example, if the transformer is designed with a ratio of 100:1 (the ratio of primary current to secondary current), magnetic flux leakage may bias the actual ratio, resulting in an error in current measurement.


Calibrating an open-close current transformer to achieve high accuracy can be more difficult than a solid core transformer. Due to the presence of opening and closing sites and possible leakage of magnetic flux, the core and winding parameters need to be adjusted more precisely during calibration.


Accuracy issues related to load


The accuracy of the open-close current transformer is greatly affected by the secondary load. In an industrial environment, the load on the secondary side can vary greatly depending on the measurement or protection equipment connected. If the load impedance is not within the specified range, it will lead to an error in the measured current. For example, if the load impedance is too high, the secondary current may not be precisely proportional to the primary current.


Installation and mechanical stability


Correct closure of the opening and closing core


It is essential to ensure that the opening and closing core is properly closed around the conductor carrying a primary current. In an industrial environment, there may be vibration, mechanical shock, or temperature changes that can cause the opening and closing core to slightly open or misalign. This breaks the magnetic coupling between the primary and secondary windings, resulting in inaccurate current measurement. For example, in a plant with heavy machinery in operation, vibration can gradually loosen the closure of an on-off current transformer.


Mechanical strength and durability


Industrial environments are often harsh, with factors such as dust, moisture and corrosive substances. Open-close current transformers need to be mechanically strong enough to withstand these conditions without being damaged. Materials used in transformer construction, such as core materials and housings, must be resistant to corrosion and mechanical damage. If the core or winding is affected by corrosion or mechanical wear, the electrical performance of the transformer will change and the accuracy will be reduced.


Electromagnetic interference (EMI)


External electromagnetic interference sources


Industrial facilities are full of sources of electromagnetic interference, such as large motors, generators, and power electronics. These sources of electromagnetic interference induce unwanted voltage and current in the on-off current transformer. The induced interference will superimpose on the normal output of the transformer or distort it, making it difficult to measure the primary current accurately. For example, when a nearby high-power motor is started, it generates a strong electromagnetic field, which may be coupled to the current transformer.


Electromagnetic interference shielding


Providing effective electromagnetic interference shielding for open-close current transformers in industrial environments can be challenging. Compared with solid core transformers, the open-close design may make it more difficult to achieve complete shielding. Without proper shielding, the transformer may be more vulnerable to external electromagnetic interference, which can affect its performance and accuracy.


Give a tip and encourage the author!
Recommended
Strange Devices on Transmission Lines: 5 Little-Known Practical Functions
1 Aviation Warning SpheresAviation warning spheres, also known as reflective safety spheres, are used on overhead transmission lines near airports, especially on extra-high-voltage (above 220kV) lines and river-crossing transmission lines. Highly visible aviation marker spheres (aviation warning spheres) must be installed along the lines to provide warning signals.The aviation marker sphere (aviation warning sphere) has a diameter of ф=600mm. The sphere can be manufactured in various bright colo
Leon
09/04/2025
Transmission Line
In transmission lines, a "π" connection involves breaking the original line from Substation A to Substation B and inserting Substation C, forming a "π" configuration. After the "π" connection, the original single line is divided into two independent transmission lines. Following the "π" connection, Substations B and C may both be powered by Substation A (in this case, Substation C receives power via a feeder from Substation B's busbar, or possibly from another voltage point within Substation B);
Encyclopedia
09/04/2025
What are the principles of forced re-energization of transmission lines?
Principles of Forced Re-energization of Transmission LinesRegulations for Forced Re-energization of Transmission Lines Correctly select the forced re-energization end of the line. If necessary, change the connection configuration before forced re-energization, taking into account the reduction of short-circuit capacity and its impact on grid stability. There must be a transformer with its neutral point directly grounded on the busbar at the forced re-energization end. Pay attention to the impact
Edwiin
09/04/2025
Analysis of Accident Handling in Transmission Lines
Analysis of Transmission Line Fault HandlingAs a fundamental component of the power grid, transmission lines are widely distributed and numerous, often exposed to diverse geographical and climatic conditions, making them highly susceptible to faults. Common causes include overvoltage, pollution flashover, insulation damage, tree encroachment, and external damage. Line tripping is one of the most frequent faults in power plant and substation operations, with fault types including single-phase-to-
Leon
09/04/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.