• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Comprehensive Guide to Handling Transformer Gas Relay and Protection Actions

Leon
Leon
Field: Fault Diagnosis
China

Handling of Minor Action of Transformer Gas Relay

  • Immediately check and record the protective relay action signals, and report to the dispatcher and station manager.

  • Closely monitor the transformer’s voltage, current, temperature, oil level, oil color, sound, and cooler operation, and assign personnel to conduct an external inspection of the transformer.

  • If significant abnormalities are found during the inspection, report to the dispatcher and take the faulty transformer offline. If no obvious fault signs are observed, escalate to higher authorities for gas sampling, analysis, and inspection of secondary circuits.

Handling of Major Action of Transformer Gas Relay

  • Inspect the relay protection action status, record and reset all signals, and immediately report to the dispatcher and station manager.

  • For a single operating transformer, request the dispatcher to activate the backup transformer immediately. For parallel-operated transformers, ensure the operating unit does not exceed its load capacity.

  • Assign personnel to inspect the transformer for deformation, oil spray, oil level, and oil color. Report inspection results to the dispatcher and relevant departments, and conduct gas analysis and secondary circuit inspections.

Handling of Transformer Differential Protection Action

  • Inspect the transformer body for abnormalities, check porcelain insulators for flashovers or damage, and examine the differential protection zone for short circuits.

  • If no visible faults are found within the differential protection range, inspect the relay protection system and secondary circuits for faults or two-point grounding in the DC circuit. If no anomalies are detected, attempt to restore power after isolating the load; if unsuccessful, do not re-energize.

  • If the action is caused by a relay/secondary circuit fault or DC circuit two-point grounding, disable the differential protection, re-energize the transformer, and then address the fault.

  • If both differential and major gas relay protections are triggered, do not re-energize the transformer without prior internal inspection and testing.

Handling of Transformer Backup Protection Action

  • Use protective action signals, indicators, and instruments to identify the fault location and power outage scope. Check each branch circuit for protective action signals or tripping flags.

  • Disconnect all branch switches on the de-energized bus and confirm they are open.

  • Open line switches with protective actions or tripping flags in the affected circuits.

  • Inspect the tripped bus and transformer switches for abnormalities.

  • Check equipment connected to the de-energized bus for faults.

  • If the fault point is identified, isolate it, restore other unaffected equipment to normal operation, and return the main transformer to service.

  • Report inspection results to the dispatcher and relevant departments, and maintain proper records.

Handling of Transformer Pressure Relief Protection Action

  • Check the protection actions and record all triggered signals.

  • Report the incident to the dispatcher, relevant departments, and leadership.

  • Conduct a thorough external inspection of the transformer, focusing on whether the pressure relief device has sprayed oil or if the top red button has popped up. Report inspection results to the dispatcher and relevant departments.

  • If the pressure relief device has sprayed oil and the red button has popped up, this confirms the validity of the pressure relief protection action.

Give a tip and encourage the author!
Recommended
Adjustment and Precautions for H61 Oil Power 26kV Electric Transformer Tap Changers
Adjustment and Precautions for H61 Oil Power 26kV Electric Transformer Tap Changers
Preparatory Work Before Adjusting the Tap Changer of H61 Oil Power 26kV Electric Transformer Apply for and issue a work permit; carefully fill out the operation ticket; conduct a simulation board operation test to ensure the operation is error-free; confirm the personnel who will carry out and supervise the operation; if load reduction is required, notify affected users in advance. Before construction, power must be disconnected to take the transformer out of service, and voltage testing must be
James
12/08/2025
H59/H61 Transformer Failure Analysis and Protection Measures
H59/H61 Transformer Failure Analysis and Protection Measures
1.Causes of Damage to Agricultural H59/H61 Oil-Immersed Distribution Transformers1.1 Insulation DamageRural power supply commonly uses a 380/220V mixed system. Due to the high proportion of single-phase loads, H59/H61 oil-immersed distribution transformers often operate under significant three-phase load imbalance. In many cases, the degree of three-phase load imbalance far exceeds the limits permitted by operational regulations, causing premature aging, deterioration, and eventual failure of th
Felix Spark
12/08/2025
Top 5 Faults Found in H61 Distribution Transformers
Top 5 Faults Found in H61 Distribution Transformers
Five Common Defects of H61 Distribution Transformers1.Lead Wire DefectsInspection Method: The three-phase DC resistance imbalance rate significantly exceeds 4%, or one phase is essentially open-circuited.Remedial Measures: The core should be lifted for inspection to locate the defective area. For poor contacts, re-polish and tighten the connection. Poorly welded joints should be re-welded. If the welding surface area is insufficient, it should be enlarged. If the lead wire cross-section is inade
Felix Spark
12/08/2025
How Voltage Harmonics Affect H59 Distribution Transformer Heating?
How Voltage Harmonics Affect H59 Distribution Transformer Heating?
The Impact of Voltage Harmonics on Temperature Rise in H59 Distribution TransformersH59 distribution transformers are among the most critical equipment in power systems, primarily functioning to convert high-voltage electricity from the power grid into low-voltage electricity required by end users. However, power systems contain numerous nonlinear loads and sources, which introduce voltage harmonics that adversely affect the operation of H59 distribution transformers. This article will discuss i
Echo
12/08/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.