• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Comprehensive Guide to Handling Transformer Gas Relay and Protection Actions

Leon
Leon
Field: Fault Diagnosis
China

Handling of Minor Action of Transformer Gas Relay

  • Immediately check and record the protective relay action signals, and report to the dispatcher and station manager.

  • Closely monitor the transformer’s voltage, current, temperature, oil level, oil color, sound, and cooler operation, and assign personnel to conduct an external inspection of the transformer.

  • If significant abnormalities are found during the inspection, report to the dispatcher and take the faulty transformer offline. If no obvious fault signs are observed, escalate to higher authorities for gas sampling, analysis, and inspection of secondary circuits.

Handling of Major Action of Transformer Gas Relay

  • Inspect the relay protection action status, record and reset all signals, and immediately report to the dispatcher and station manager.

  • For a single operating transformer, request the dispatcher to activate the backup transformer immediately. For parallel-operated transformers, ensure the operating unit does not exceed its load capacity.

  • Assign personnel to inspect the transformer for deformation, oil spray, oil level, and oil color. Report inspection results to the dispatcher and relevant departments, and conduct gas analysis and secondary circuit inspections.

Handling of Transformer Differential Protection Action

  • Inspect the transformer body for abnormalities, check porcelain insulators for flashovers or damage, and examine the differential protection zone for short circuits.

  • If no visible faults are found within the differential protection range, inspect the relay protection system and secondary circuits for faults or two-point grounding in the DC circuit. If no anomalies are detected, attempt to restore power after isolating the load; if unsuccessful, do not re-energize.

  • If the action is caused by a relay/secondary circuit fault or DC circuit two-point grounding, disable the differential protection, re-energize the transformer, and then address the fault.

  • If both differential and major gas relay protections are triggered, do not re-energize the transformer without prior internal inspection and testing.

Handling of Transformer Backup Protection Action

  • Use protective action signals, indicators, and instruments to identify the fault location and power outage scope. Check each branch circuit for protective action signals or tripping flags.

  • Disconnect all branch switches on the de-energized bus and confirm they are open.

  • Open line switches with protective actions or tripping flags in the affected circuits.

  • Inspect the tripped bus and transformer switches for abnormalities.

  • Check equipment connected to the de-energized bus for faults.

  • If the fault point is identified, isolate it, restore other unaffected equipment to normal operation, and return the main transformer to service.

  • Report inspection results to the dispatcher and relevant departments, and maintain proper records.

Handling of Transformer Pressure Relief Protection Action

  • Check the protection actions and record all triggered signals.

  • Report the incident to the dispatcher, relevant departments, and leadership.

  • Conduct a thorough external inspection of the transformer, focusing on whether the pressure relief device has sprayed oil or if the top red button has popped up. Report inspection results to the dispatcher and relevant departments.

  • If the pressure relief device has sprayed oil and the red button has popped up, this confirms the validity of the pressure relief protection action.

Give a tip and encourage the author!
Recommended
What Are Combined Transformer Standards? Key Specs & Tests
What Are Combined Transformer Standards? Key Specs & Tests
Combined Instrument Transformers: Technical Requirements and Testing Standards Explained with DataA combined instrument transformer integrates a voltage transformer (VT) and a current transformer (CT) into a single unit. Its design and performance are governed by comprehensive standards covering technical specifications, testing procedures, and operational reliability.1. Technical RequirementsRated Voltage:The primary rated voltages include 3kV, 6kV, 10kV, and 35kV, among others. The secondary v
Edwiin
10/23/2025
What Are the Types of Reactors? Key Roles in Power Systems
What Are the Types of Reactors? Key Roles in Power Systems
Reactor (Inductor): Definition and TypesA reactor, also known as an inductor, generates a magnetic field within the surrounding space when current flows through a conductor. Therefore, any current-carrying conductor inherently possesses inductance. However, the inductance of a straight conductor is small and produces a weak magnetic field. Practical reactors are constructed by winding the conductor into a solenoid shape, known as an air-core reactor. To further increase inductance, a ferromagnet
James
10/23/2025
35kV Distribution Line Single-Phase Ground Fault Handling
35kV Distribution Line Single-Phase Ground Fault Handling
Distribution Lines: A Key Component of Power SystemsDistribution lines are a major component of power systems. On the same voltage-level busbar, multiple distribution lines (for input or output) are connected, each with numerous branches arranged radially and linked to distribution transformers. After being stepped down to low voltage by these transformers, electricity is supplied to a wide range of end users. In such distribution networks, faults such as phase-to-phase short circuits, overcurre
Encyclopedia
10/23/2025
Why Upgrade to Maintenance-Free Transformer Breathers?
Why Upgrade to Maintenance-Free Transformer Breathers?
Maintenance-Free Moisture Absorption Technology for Oil-Immersed TransformersIn traditional oil-filled transformers, the temperature control system causes thermal expansion and contraction of insulating oil, requiring the sealing gel chamber to absorb significant moisture from the air above the oil surface. The frequency of manual silica gel replacement during patrols directly impacts equipment safety—delayed replacement can easily lead to oil degradation. Maintenance-free moisture absorbers rev
Felix Spark
10/23/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.