What are the accident scenarios in a substation?

Leon
07/30/2025

Handling of Minor Action of Transformer Gas Relay
  • Immediately check and record the protective relay action signals, and report to the dispatcher and station manager.
  • Closely monitor the transformer’s voltage, current, temperature, oil level, oil color, sound, and cooler operation, and assign personnel to conduct an external inspection of the transformer.
  • If significant abnormalities are found during the inspection, report to the dispatcher and take the faulty transformer offline. If no obvious fault signs are observed, escalate to higher authorities for gas sampling, analysis, and inspection of secondary circuits.
Handling of Major Action of Transformer Gas Relay
  • Inspect the relay protection action status, record and reset all signals, and immediately report to the dispatcher and station manager.
  • For a single operating transformer, request the dispatcher to activate the backup transformer immediately. For parallel-operated transformers, ensure the operating unit does not exceed its load capacity.
  • Assign personnel to inspect the transformer for deformation, oil spray, oil level, and oil color. Report inspection results to the dispatcher and relevant departments, and conduct gas analysis and secondary circuit inspections.
Handling of Transformer Differential Protection Action
  • Inspect the transformer body for abnormalities, check porcelain insulators for flashovers or damage, and examine the differential protection zone for short circuits.
  • If no visible faults are found within the differential protection range, inspect the relay protection system and secondary circuits for faults or two-point grounding in the DC circuit. If no anomalies are detected, attempt to restore power after isolating the load; if unsuccessful, do not re-energize.
  • If the action is caused by a relay/secondary circuit fault or DC circuit two-point grounding, disable the differential protection, re-energize the transformer, and then address the fault.
  • If both differential and major gas relay protections are triggered, do not re-energize the transformer without prior internal inspection and testing.
Handling of Transformer Backup Protection Action
  • Use protective action signals, indicators, and instruments to identify the fault location and power outage scope. Check each branch circuit for protective action signals or tripping flags.
  • Disconnect all branch switches on the de-energized bus and confirm they are open.
  • Open line switches with protective actions or tripping flags in the affected circuits.
  • Inspect the tripped bus and transformer switches for abnormalities.
  • Check equipment connected to the de-energized bus for faults.
  • If the fault point is identified, isolate it, restore other unaffected equipment to normal operation, and return the main transformer to service.
  • Report inspection results to the dispatcher and relevant departments, and maintain proper records.
Handling of Transformer Pressure Relief Protection Action
  • Check the protection actions and record all triggered signals.
  • Report the incident to the dispatcher, relevant departments, and leadership.
  • Conduct a thorough external inspection of the transformer, focusing on whether the pressure relief device has sprayed oil or if the top red button has popped up. Report inspection results to the dispatcher and relevant departments.
  • If the pressure relief device has sprayed oil and the red button has popped up, this confirms the validity of the pressure relief protection action.
Leon

Hello! I'm Leon, with 20 years of extensive experience in the power industry. My expertise spans from power distribution equipment to grid operations and maintenance, grounded in robust hands-on and theoretical knowledge. Currently, I focus on sharing insights into electrical equipment fault diagnosis, demystifying complex technical challenges through accessible explanations. I welcome collaboration with industry peers and enthusiasts to collectively explore the intricacies of the power sector.

What are the basic knowledge points about transformer bushings?
What are the basic knowledge points about transformer bushings?
1. Functions of Transformer BushingsThe core function of transformer bushings is to lead the coil leads out to the external environment. They serve both as insulating components between the leads and the oil tank and as fixing devices for the leads.During the operation of a transformer, bushings continuously carry load currents and, in the event of an external short circuit, withstand short-circuit currents. Therefore, transformer bushings must meet the following requirements:Possess specified e
Rockwell
07/31/2025
What are the application scenarios of power transformers with a rating above 10kV?
What are the application scenarios of power transformers with a rating above 10kV?
High - voltage power transformers (above 10 kV) are extensively applied in various sectors, spanning residential and industrial fields. The following is a detailed overview of their main application scenarios and technical characteristics:1. Urban and Civil Applications1.1 Residential Communities and Commercial CentersThe 10 kV - rated combination transformer, favored for its compact size and fully sealed structure, is widely used in new residential complexes, shopping centers, and high - rise b
Vziman
07/31/2025
Power System Voltage Level Classification
Power System Voltage Level Classification
What Is a Voltage Class?Definition of Voltage Class:Voltage classes (or voltage levels) refer to a set of standardized rated voltages used in power systems and electrical equipment. A rated voltage is the nominal voltage at which equipment is designed to operate under normal conditions; essentially, a voltage class defines the intended working voltage range for a system or device.Analogy to Consumer Appliances:Household appliances (e.g., refrigerators, TVs) operate at a nominal voltage—typ
Vziman
07/30/2025
What is the reason for conducting five impulse tests before commissioning a transformer?
What is the reason for conducting five impulse tests before commissioning a transformer?
Verification of Insulation IntegrityWhen a new or overhauled transformer is energized under open-circuit (no-load) conditions, switching surges—caused by operations such as opening or closing the no-load transformer circuit—can generate overvoltages. These reach 4.0–4.5 times the phase voltage if the neutral point is isolated or earthed through a Petersen coil, and up to 3.0 times the phase voltage when the neutral is solidly grounded. The full-voltage, no-load impact test deli
Rockwell
07/30/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!