• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Comprehensive Guide to Handling Transformer Gas Relay and Protection Actions

Leon
Field: Fault Diagnosis
China

Handling of Minor Action of Transformer Gas Relay

  • Immediately check and record the protective relay action signals, and report to the dispatcher and station manager.

  • Closely monitor the transformer’s voltage, current, temperature, oil level, oil color, sound, and cooler operation, and assign personnel to conduct an external inspection of the transformer.

  • If significant abnormalities are found during the inspection, report to the dispatcher and take the faulty transformer offline. If no obvious fault signs are observed, escalate to higher authorities for gas sampling, analysis, and inspection of secondary circuits.

Handling of Major Action of Transformer Gas Relay

  • Inspect the relay protection action status, record and reset all signals, and immediately report to the dispatcher and station manager.

  • For a single operating transformer, request the dispatcher to activate the backup transformer immediately. For parallel-operated transformers, ensure the operating unit does not exceed its load capacity.

  • Assign personnel to inspect the transformer for deformation, oil spray, oil level, and oil color. Report inspection results to the dispatcher and relevant departments, and conduct gas analysis and secondary circuit inspections.

Handling of Transformer Differential Protection Action

  • Inspect the transformer body for abnormalities, check porcelain insulators for flashovers or damage, and examine the differential protection zone for short circuits.

  • If no visible faults are found within the differential protection range, inspect the relay protection system and secondary circuits for faults or two-point grounding in the DC circuit. If no anomalies are detected, attempt to restore power after isolating the load; if unsuccessful, do not re-energize.

  • If the action is caused by a relay/secondary circuit fault or DC circuit two-point grounding, disable the differential protection, re-energize the transformer, and then address the fault.

  • If both differential and major gas relay protections are triggered, do not re-energize the transformer without prior internal inspection and testing.

Handling of Transformer Backup Protection Action

  • Use protective action signals, indicators, and instruments to identify the fault location and power outage scope. Check each branch circuit for protective action signals or tripping flags.

  • Disconnect all branch switches on the de-energized bus and confirm they are open.

  • Open line switches with protective actions or tripping flags in the affected circuits.

  • Inspect the tripped bus and transformer switches for abnormalities.

  • Check equipment connected to the de-energized bus for faults.

  • If the fault point is identified, isolate it, restore other unaffected equipment to normal operation, and return the main transformer to service.

  • Report inspection results to the dispatcher and relevant departments, and maintain proper records.

Handling of Transformer Pressure Relief Protection Action

  • Check the protection actions and record all triggered signals.

  • Report the incident to the dispatcher, relevant departments, and leadership.

  • Conduct a thorough external inspection of the transformer, focusing on whether the pressure relief device has sprayed oil or if the top red button has popped up. Report inspection results to the dispatcher and relevant departments.

  • If the pressure relief device has sprayed oil and the red button has popped up, this confirms the validity of the pressure relief protection action.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
Why Must a Transformer Core Be Grounded at Only One Point? Isn't Multi-Point Grounding More Reliable?
Why Does the Transformer Core Need to Be Grounded?During operation, the transformer core, along with the metal structures, parts, and components that fix the core and windings, are all situated in a strong electric field. Under the influence of this electric field, they acquire a relatively high potential with respect to ground. If the core is not grounded, a potential difference will exist between the core and the grounded clamping structures and tank, which may lead to intermittent discharge.I
01/29/2026
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.