Power Plant Fire Protection System

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

WechatIMG1822.jpeg

With the advent of industrialization the demand for power is also on the surge like never before. But augmenting without giving the due consideration for Fire protection and detection system would be detrimental and should not be done.
Thermal Power Plants are classified under the ordinary Hazard Occupancy as per Tariff Advisory Committee (TAC) of India. The design and installation of complete fire protection system shall comply with the regulations of TAC. In the absence of TAC regulations, the National Fire Protection Association (NFPA) standard shall be adopted. The system should be designed in such a manner that it is acceptable to approving statutory body (like TAC) for insurance companies of India and enable an owner to obtain the maximum rebate on its insurance premium.

Thermal Power Plants are characterized by their complex overall system made of a range of different operating modules. In addition to these conditions such as extremely hot surfaces, lubricating oils and coal and coal dust pose huge fire risks. Elements of Fire Protection System is covered in this Portion of Part-I.
This section comprises of following which broadly are the elements of the fire protection system:

Fire Water Reservoir or Fire water Pump House

Water pump house plays an important role in fire protection system, so the complete fire pump arrangement shall be in line with the requirements of TAC. Water storage tank is required for storage of water and water will be drawn as and when required for fire protection. All the fire pumps should work automatically by use of Pressure switches; however stopping of all the fire pumps shall be manual only.
The possible sources of supply of water to storage tank will be from two different sources:

  • From raw water pump discharge header.

  • From CW blow down the system.

The fire water storage tank shall be provided with two equal compartments and both the compartments shall be interconnected through separate isolation valve and each compartment shall be connected to a common suction header of fire water pumps so that any fire pump can be fed by either fire water storage compartment as per TAC regulations.
At least two (2) headers shall be taken out of pump house for making loops around various risks. Each loop shall be interconnected for better reliability of the system. To isolate the system due to damage/repair, suitable nos. of gate valve should be provided.

Pumps Installed in Fire Water Pump House

Dedicated fire water pumps shall be provided for the fire hydrant and spray system. Blind flange with valve connection for future expansion shall be provided in the fire hydrant and spray system network. The installed fire water pump capacity and head shall be designed as per system requirement/TAC recommendations.

Following are the fire water pumps installed in the fire water pump house:

  1. Electric motor driven main fire water pump.

  2. Diesel engine driven pumps

  3. All diesel engine driven pumps shall be provided with 2 × 100% battery chargers and batteries.

  4. Electric motor driven fire water jockey pumps (one working and one stand by).

  5. Air compressor for pressurizing hydro-pneumatic tank.

Fire Water Pumps Data Sheet

For selection of rated capacity, rpm and material construction are:

1.4

TAC approval required

yes

yes

yes

1.5

Used for service like

Hydrant and spray system

Hydrant and spray system

Common for Hydrant and spray system

2.0

Material of construction




2.1

Casing

SS304

SS304

SS304

2.2

Impeller

Stainless steel

Stainless steel

Stainless steel

2.3

Shaft

Stainless steel

Stainless steel

Stainless steel



Control and operating philosophy

Fire water ring main network shall be a pressurized system provided with automatic starting of fire water pumps. The mode of operation of fire water pumping system for following shall be described in Part-II and III.

  • Hydrant and MVWSS

  • Hydrant and HVWSS

  • Fixed Foam system

  • Fire water booster pump

Constructional requirements

  • All hydrant, spray and foam system pipe mains/pipes shall be routed above ground on top of the concrete pedestals at regular intervals.

  • In main plant area and coal stock yard area pipe lines shall be routed in RCC pipe trenches filled with sand and covered with pre-cast RCC removable covers. Pipe trenches crossing through road or rail shall be through Hume pipes.

  • Fire water pipes shall be of carbon steel conforming to IS:1239 (medium grade) and IS:3589.

  • All above ground piping shall be adequately supported by concrete pedestals at regular intervals.

  • All buried pipes shall be double coated and wrapped as per IS:10221 or IS:15337.

  • The entire pipe net work shall be hydraulically designed in such manner that the velocity of water in any section does not exceed 5.0 m/sec.

  • Fire pump pressure has to be decided in such a manner that the requirement of the highest pressure at the remotest and highest hydrant can be meet at the same time in line with the TAC requirements.

  • Hose cabinet shall be provided with 16 SWG thick body and 3 mm glass. The hose shall be provided with key box and pedestal. Fire hose shall be of IS 636 type-A.

Hydrant System

(is covered in part-II)

Spray System

(is covered in part-II)

Fix Foam system

(is covered in part-III)

Potable and mobile extinguisher

(is covered in part-III)

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
What are the safety precautions and guidelines for using AC load banks?
What are the safety precautions and guidelines for using AC load banks?
AC load banks are electrical devices used to simulate real-world loads and are widely applied in power systems, communication systems, automation control systems, and other fields. To ensure personal and equipment safety during use, the following safety precautions and guidelines must be observed:Select an appropriate AC load bank: Choose an AC load bank that meets actual requirements, ensuring its capacity, voltage rating, and other parameters satisfy the intended application. Additionally, sel
Echo
11/06/2025
What should be noted when installing a Type K thermocouple?
What should be noted when installing a Type K thermocouple?
Installation precautions for Type K thermocouples are critical to ensuring measurement accuracy and extending service life. Below is an introduction to the installation guidelines for Type K thermocouples, compiled from highly authoritative sources:1.Selection and Inspection Select the appropriate thermocouple type: Choose the right thermocouple based on the temperature range, medium properties, and required accuracy of the measurement environment. Type K thermocouples are suitable for temperatu
James
11/06/2025
 Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes and Preventive Measures of Fire and Explosion in Oil Circuit Breakers
Causes of Fire and Explosion in Oil Circuit Breakers When the oil level in an oil circuit breaker is too low, the oil layer covering the contacts becomes too thin. Under the effect of the electric arc, the oil decomposes and releases flammable gases. These gases accumulate in the space beneath the top cover, mixing with air to form an explosive mixture, which can ignite or explode under high temperature. If the oil level inside the tank is too high, the released gases have limited space to expan
Felix Spark
11/06/2025
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.