Phase Sequence Indicator

Electrical4u
Field: Basic Electrical
0
China

What Is A Phase Sequence Indicator

We have three phase system and by convention we write three phases as RYB. Phase sequence indicator is the indicator that determines the phase sequence of the three phase supply system.
When we give conventional three phase supply (i.e. RYB) to the
induction motor, we see that the direction of the rotation of the rotor is in clockwise direction.
Now what will happen to direction of rotation of rotor if the phase sequence is reversed, the answer to this question is that the rotor will rotate in the anticlockwise direction. Thus, we see that the direction of rotation of rotor depends on the phase sequence. Let us study how these phase instruments work and on what principle they work.
Now there are two types of phase sequence indicators and they are:

  • Rotating type

  • Static type.

Let us discuss one by one each type.

Rotating Type Phase Sequence Indicators

It works on the principle of induction motors. In this coils are connected in star form and the supply is given from three terminal marked as RYB as shown in the figure. When supply is given the coils produces the rotating magnetic field and these rotating magnetic fields produces eddy emf in the movable aluminium disc as shown in the diagram.
rotating type phase sequence indicator

These eddy emf produces eddy current on the aluminium disc, eddy currents interact with the rotating magnetic field due this a torque is produced which causes the light aluminum disc to move. If the disc moves in the clockwise direction then chosen sequence is RYB and if the direction of rotation is in anticlockwise the sequence is reversed.

Static Type Phase Sequence Indicators

Given below is the arrangement of static type indicator:
static type phase sequence indicator

When the phase sequence is RYB then the lamp B will glow brighter than the lamp A and if the phase sequence is reversed then the lamp A will glow brighter than the lamp B. Now let us see how this happens.
Here we assume that the phase sequence is RYB. Let us mark
voltages as Vry, Vyb and Vbr as per the diagram. We have
Here we have assumed balance operation such that we have Vry=Vbr=Vyb=V. Since algebraic sum of all the phase currents is also equal, therefore we can write
On solving the above equations we have ratio of Ir and Iy equals to 0.27.
It implies that the voltage across the lamp A is only 27 percent of that of lamp B. Hence from this we can conclude that the lamp A will glow dimmer in case of RYB phase sequence while in case of reversed phase sequence we have lamp B is dimmer than lamp A.
There is another kind of phase indicator also that works similar to that of the previous one. However here
inductor is replaced by the capacitor as shown in the diagram given below.
phase sequence indicatorTwo neon lamps are used, along with them two series resistor are also used to limit the current and to protect the neon lamp from breakdown voltage. In this indicator if the supply phase sequence is RYB then lamp A will glow and lamp B will not glow and if the reversed sequence is applied then the lamp A will not glow while lamp B will glow.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!

Recommended

Faults and Handling of Single-phase Grounding in 10kV Distribution Lines
Characteristics and Detection Devices for Single-Phase Ground Faults1. Characteristics of Single-Phase Ground FaultsCentral Alarm Signals:The warning bell rings, and the indicator lamp labeled “Ground Fault on [X] kV Bus Section [Y]” illuminates. In systems with a Petersen coil (arc suppression coil) grounding the neutral point, the “Petersen Coil Operated” indicator also lights up.Insulation Monitoring Voltmeter Indications:The voltage of the faulted phase decreases (in
01/30/2026
Neutral point grounding operation mode for 110kV~220kV power grid transformers
The arrangement of neutral point grounding operation modes for 110kV~220kV power grid transformers shall meet the insulation withstand requirements of transformer neutral points, and shall also strive to keep the zero-sequence impedance of substations basically unchanged, while ensuring that the zero-sequence comprehensive impedance at any short-circuit point in the system does not exceed three times the positive-sequence comprehensive impedance.For 220kV and 110kV transformers in new constructi
01/29/2026
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?
Why Do Substations Use Stones, Gravel, Pebbles, and Crushed Rock?In substations, equipment such as power and distribution transformers, transmission lines, voltage transformers, current transformers, and disconnect switches all require grounding. Beyond grounding, we will now explore in depth why gravel and crushed stone are commonly used in substations. Though they appear ordinary, these stones play a critical safety and functional role.In substation grounding design—especially when multiple gr
01/29/2026
HECI GCB for Generators – Fast SF6 Circuit Breaker
1.Definition and Function1.1 Role of the Generator Circuit BreakerThe Generator Circuit Breaker (GCB) is a controllable disconnect point located between the generator and the step-up transformer, serving as an interface between the generator and the power grid. Its primary functions include isolating generator-side faults and enabling operational control during generator synchronization and grid connection. The operating principle of a GCB is not significantly different from that of a standard c
01/06/2026
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.