What is GIS?

10/07/2024

GIS device definition


GIS is the abbreviation of Gas Insulated Switchgear, which is generally translated as a gas insulated fully enclosed combination appliance, usually using SF6 gas as the insulating medium. Includes circuit breaker (CB), isolation switch (DS), ground switch (ES, FES), BUS (BUS), current transformer (CT), voltage transformer (VT), lightning arrester (LA) and other high voltage components. At present, GIS equipment products have covered the voltage range of 72.5 kV ~1200 kV.


53c21faa8c33374d7f652ba8eda068f8.jpeg


Characteristics of GIS equipment


Due to the excellent insulation performance, arc extinguishing performance and stability of SF6 gas, GIS equipment has the advantages of small footprint, strong arc extinguishing ability and high reliability. However, the insulation ability of SF6 gas is greatly affected by the uniformity of electric field, and insulation anomalies are prone to occur when there are tips or foreign objects in GIS.



GIS equipment adopts a completely closed structure, which brings the advantages of internal components free from environmental interference, long overhaul cycle, less maintenance work, low electromagnetic interference, and at the same time, there are also problems such as complex single overhaul work and relatively poor detection means, and when the closed structure is eroded by the external environment, it will further bring a series of problems such as water intake and air leakage.


5436d1ae80a97c066073f10c97a2321f.jpeg


The internal structure of GIS devices


The conductive loop of GIS is composed of several components. According to the working method, it can be generally divided into: fixed contact (electrical contact fastened with fasteners such as screws is called fixed contact, and fixed contact has no relative movement during the working process. Such as the connection between the contact and the basin, etc.), contact contact (the electrical contact that can be separated during the working process is also called separable contact), sliding and rolling contact (during the working process, the contacts can slide or roll each other, but the electrical contact that cannot be separated is called sliding and rolling contact. The middle contact of the switchgear is the use of this electrical contact).


48f61236d3eee77a6c5f7ee32d981ac9.jpeg


Apply


GIS substation


Sulfur hexafluoride closed combination electrical appliances, internationally known as "Gas insulated Switchgear" (Gas lnsulated Switchgear) referred to as GIS, it will be a substation in addition to the transformer in the primary equipment, Including circuit breaker, isolation switch, ground switch, voltage transformer, current transformer, lightning arrester, bus, cable terminal, inlet and outlet line bushing, optimized design organically combined into a whole. In addition to GIS, there is a HGIS, designed for harsher environments, due to the relative GIS less bus, bus pressure change, lightning arrester and other equipment, especially the bus, the use of more flexible.


e215339f242cf555282f5ea797f791b5.jpeg


Advantage


  • Miniaturization: SF6 gas with excellent insulation performance is used as insulation and arc extinguishing medium, which greatly reduces the volume of substation.


  • High reliability: the live parts are all sealed in inert SF6 gas, which improves the reliability of the substation.


  • Good safety: the live part is sealed in the grounded metal housing, so there is no risk of electric shock. SF6 gas is a non-burning gas, so there is no fire hazard.


  • Eliminate adverse effects on the outside: the live part is closed with a metal shell, shielding electromagnetic and static electricity, low noise, strong anti-radio interference ability.


  • Short installation cycle: The realization of miniaturization makes the whole machine assembly and test qualified in the factory, can be shipped to the site in the form of units or intervals, so it can shorten the site installation period, but also improve reliability.



Easy maintenance, short maintenance time: because of its reasonable structure layout and advanced arc extinguishing system, it greatly improves the service life of the product, so the maintenance cycle is long, the maintenance workload is small, and because of miniaturization, low from the ground, it is convenient for daily maintenance.


Sort


GIS can be divided into outdoor type and indoor type according to the installation location.


f8e4cb2968879abc709020ea890e418b.jpeg


GIS can generally be divided into two forms: single-phase single-cylinder and three-phase common cylinder. The 110kV voltage level and the bus bar can be made into a three-phase common cylinder type, and a single-phase single cylinder type is used for 220kV and above.


7814f662-25a9-486d-9ca4-9c3d21cf457b.jpg

Operating principle


  • In normal cases, the circuit breaker and isolation switch of the GIS device are mainly operated in the remote area. The circuit breaker and isolation switch are enabled in the remote/local area to focus on the remote location.


  • The ground switch of a GIS device can be operated only in the local area. When you operate the ground switch, switch the switchblade/ground knife to the remote/local area.


  • In any case, only the program operation can be carried out, the "interlock release switch" on the wire control cabinet must be in the "interlock" position, and its unlock key and the computer anti-misunderstanding lock key are sealed together and used in accordance with the same provisions



Operational requirement


  • Indoor SF6 equipment room frequently entered by operators: ventilation at least once per shift for 15 minutes, the air exchange volume should be greater than 3-5 times the air volume, and the air outlet should be installed in the lower part of the room; Equipment places that are not frequented by operators: ventilate for 15 minutes before entering.


  • For the parts easily touched by operation and maintenance personnel, under normal circumstances, the induced voltage on the shell and frame should not exceed 36V.


  • Temperature rise: the part easily touched by the operator should not exceed 30K; The part easily touched by the operator but not touched during operation should not exceed 40K; Individual parts not easily accessible by the operator should not exceed 65K.


  • SF6 switchgear inspection, at least once a day, unattended substation inspection according to regulations. During the inspection, the main inspection is to check the appearance, whether the equipment is abnormal, and make a record.


The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

What is the difference between a dielectric and an insulator?
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
08/30/2025
Transformer Connection Sections
Transformer Connection Sections
Transformer Connection DesignationsThe transformer connection designation indicates the winding connection method and the phase relationship between the line voltages of the primary and secondary windings. It consists of two parts: letters and a number. The letters on the left denote the connection configurations of the high-voltage and low-voltage windings, while the number on the right is an integer from 0 to 11.This number represents the phase shift of the low-voltage winding's line voltage r
08/15/2025
Automatic Reclosing Scheme in Transmission Systems
Automatic Reclosing Scheme in Transmission Systems
Automatic Reclosing Scheme for Transmission SystemsThe automatic reclosing system is a series-connected network designed to reduce operating costs and enhance network reliability. Extra-high voltage (EHV) transmission lines are used to transmit large amounts of power, on the order of thousands of megawatts (MW), and therefore should not be interrupted at all costs. Although faults on these overhead lines are common, the power transmitted through them should not be interrupted for long periods du
08/07/2025
Transformer operation and maintenance
Transformer operation and maintenance
Transformer Operating TemperatureDuring operation, transformers generate copper losses and iron losses, both of which are converted into heat, causing the transformer’s temperature to rise. Most transformers in China use Class A insulation. Due to heat transfer characteristics, significant temperature differences exist between different components during operation: winding temperature is the highest, followed by the core, and then the temperature of the insulating oil (with upper-layer oil being