Key Considerations for Step-Up Transformer Selection in Grid-Connected PV Power Systems

Learn about the key factors for selecting step-up transformers in grid-connected photovoltaic systems including capacity voltage phase winding connection group load and no-load loss considerations.

Edwiin
Field: Power switch
10Year<
China
Add us on Google

In grid-connected photovoltaic (PV) power generation systems, the step-up transformer is a critical component. Optimizing transformer selection to minimize inherent losses and enhance efficiency is essential for improving overall system performance. This article outlines key considerations for proper step-up transformer selection in PV systems.

  • Transformer Capacity Selection
    The required transformer capacity is calculated as: Apparent Power = Active Power / Power Factor. Power factor requirements vary by region&mdash;typically 0.85 for construction and small industrial loads, and 0.9 for large industrial loads. For example, a 550 kW load at 0.85 power factor requires 550 / 0.85 = 647 kVA, so a 630 kVA transformer is suitable. Total load should not exceed 80% of the transformer&rsquo;s rated capacity.

  • Transformer Voltage Selection
    The primary winding voltage should match the source line voltage, while the secondary voltage must align with the connected equipment. For low-voltage three-phase four-wire distribution, appropriate voltage levels (e.g., 10 kV, 35 kV, or 110 kV) should be selected based on primary-side requirements.

  • Transformer Phase Selection
    Choose between single-phase and three-phase configurations according to the power source and load requirements.

  • Transformer Winding Connection Group Selection
    Three-phase windings can be connected in star (Y), delta (D), or zigzag (Z) configurations. The globally preferred connection for distribution transformers is Dyn11, which offers several advantages over Yyn0:

    • Harmonic Suppression: The delta (D) connection effectively suppresses higher-order harmonics.

    • Harmonic Circulation: Third harmonic currents circulate within the delta winding, neutralizing third harmonic flux from the low-voltage side.

    • Harmonic Containment: Third harmonic EMF in the high-voltage winding remains confined within the delta loop, preventing injection into the public grid.

    • Lower Zero-Sequence Impedance: Dyn11 transformers exhibit significantly lower zero-sequence impedance, aiding in the clearance of low-voltage single-phase ground faults.

    • Superior Neutral Current Handling: Capable of handling neutral currents exceeding 75% of phase current, making them ideal for unbalanced loads.

    • Continuity Under Phase Loss: If one high-voltage fuse blows, the remaining two phases can continue operating with Dyn11, unlike with Yyn0.

Therefore, Dyn11-connected transformers are strongly recommended.

Load Loss, No-Load Loss, and Impedance Voltage
Due to the daytime operation pattern of PV systems, transformers incur no-load losses whenever energized, regardless of output. Minimizing load losses is crucial; if nighttime operation occurs, low no-load losses are also important.

This selection strategy ensures efficient transformer operation within PV systems, reducing overall losses and enhancing power generation performance.

Give a tip and encourage the author!
Related Products

Comments

Share your question or perspective
WhatsApp
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login
or continue with
New here?
Register