• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Capacitor Bank Protection

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Capacitor Bank Protection Definition


Protecting capacitor banks involves preventing internal and external faults to maintain functionality and safety.


Element Fuses


Manufacturers usually include built-in fuses in each capacitor element. If a fault occurs in an element, it is automatically disconnected from the rest of the unit. The unit can still function, but with reduced output. For smaller capacitor banks, only these built-in protection schemes are used to avoid the cost of additional protective equipment.


Unit Fuse


Unit fuse protection limits the duration of arc in faulty capacitor units. This reduces the risk of major mechanical damage and gas production, protecting neighboring units. If each unit in a capacitor bank has its own fuse, the bank can continue operating without interruption even if one unit fails, until the faulty unit is removed and replaced.


Another major advantage of providing fuse protection to each unit of the bank is that, it indicates the exact location of the faulty unit. But during choosing the size of the fuse for this purpose, it should be taken into consideration that the fuse element must withstand the excessive loading due to harmonics in the system. In the view of that the current rating of the fuse element for this purpose is taken as 65% above the full load current. Whenever the individual unit of capacitor bank is protected by fuse, it is necessary to provide discharge resistance in each of the units.


Bank Protection


While each capacitor unit generally has fuse protection, if a unit fails and its fuse blows, the voltage stress on other units in the same series row increases. Each capacitor unit is designed to withstand up to 110% of its rated voltage. If another unit in the same row fails, the stress on the remaining healthy units increases and can exceed their maximum voltage limit.


Hence it is always desirable to replace damaged capacitor unit from the bank as soon as possible to avoid excess voltage stress on the other healthy units. Hence, there must be some indicating arrangement to identify the exact faulty unit. As soon as the faulty unit is identified in a bank, the bank should be removed from the service for replacing the faulty unit. There are several methods of sensing unbalance voltage caused by failure of capacitor unit.


The figure below is showing the most common arrangement of capacitor bank protection. Here, the capacitor bank is connected in star formation. Primary of a potential transformer is connected across each phase. The secondary of all three potential transformers are connected in series to form an open delta and a voltage sensitive relay is connected across this open delta. 


In exact balanced condition there must not be any voltage appears across the voltage sensitive relay because summation of balanced 3 phase voltages is zero. But when there would be any voltage unbalancing due to failure of capacitor unit, the resultant voltage will appear across the relay and the relay will be actuated for providing an alarm and trip signals.


The voltage-sensitive relay can be adjusted so that at a certain voltage imbalance, only the alarm contacts close. At a higher voltage level, both the trip and alarm contacts close. The potential transformer connected across each phase’s capacitors also helps discharge the bank after it’s switched off.


In another scheme, the capacitors in each phase are divided into two equal parts connected in series. Discharge coil is connected across each of the parts as shown in the figure. In between the secondary of discharge coil and the sensitive voltage that unbalances the relay an auxiliary transformer is connected which serves to regulate the voltage difference between secondary voltages of discharge coil under normal conditions.


Here the capacitor bank is connected in star and the neutral point is connected to the ground through a potential transformer. A voltage sensitive relay is connected across the secondary of the potential transformer. As soon as there is any unbalance between the phases, the resultant voltage will appear across the potential transformer and hence the voltage sensitive relay will be actuated beyond a preset value.

 0cebfeb3c4a2fc78631f022cb7ff9d1f.jpeg

a6686055015578e03ee8f3480d06058e.jpeg

Give a tip and encourage the author!
Recommended
GIS Dual Grounding & Direct Grounding: State Grid 2018 Anti-Accident Measures
GIS Dual Grounding & Direct Grounding: State Grid 2018 Anti-Accident Measures
1. Regarding GIS, how should the requirement in Clause 14.1.1.4 of the State Grid’s "Eighteen Anti-Accident Measures" (2018 Edition) be understood?14.1.1.4: The neutral point of a transformer shall be connected to two different sides of the main mesh of the grounding grid via two grounding down conductors, and each grounding down conductor shall meet the thermal stability verification requirements. Main equipment and equipment structures shall each have two grounding down conductors connected to
Echo
12/05/2025
Three-Phase SPD: Types, Wiring & Maintenance Guide
Three-Phase SPD: Types, Wiring & Maintenance Guide
1. What Is a Three-Phase Power Surge Protective Device (SPD)?A three-phase power surge protective device (SPD), also known as a three-phase lightning arrester, is specifically designed for three-phase AC power systems. Its primary function is to limit transient overvoltages caused by lightning strikes or switching operations in the power grid, thereby protecting downstream electrical equipment from damage. The SPD operates based on energy absorption and dissipation: when an overvoltage event occ
James
12/02/2025
Adjustment Test Operation and Precautions of High-Voltage Power Distribution Cabinets in Power Systems
Adjustment Test Operation and Precautions of High-Voltage Power Distribution Cabinets in Power Systems
1. Key Points for Debugging High-Voltage Power Distribution Cabinets in Power Systems1.1 Voltage ControlDuring the debugging of high-voltage power distribution cabinets, voltage and dielectric loss show an inverse relationship. Insufficient detection accuracy and large voltage errors will lead to increased dielectric loss, higher resistance, and leakage. Therefore, it is necessary to strictly control the resistance under low-voltage conditions, analyze current and resistance values, and avoid ex
Oliver Watts
11/26/2025
Neutral Grounding Methods for Conventional-Speed Railway Power Systems
Neutral Grounding Methods for Conventional-Speed Railway Power Systems
Railway power systems primarily consist of automatic block signaling lines, through-feeder power lines, railway substations and distribution stations, and incoming power supply lines. They provide electricity to critical railway operations—including signaling, communications, rolling stock systems, station passenger handling, and maintenance facilities. As an integral part of the national power grid, railway power systems exhibit distinct characteristics of both electrical power engineering and
Echo
11/26/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.