• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


How to Safely Operate & Maintain Current Transformers?

Felix Spark
Felix Spark
Field: Failure and maintenance
China

I. Permissible Operating Conditions for Current Transformers

  • Rated Output Capacity: Current transformers (CTs) must operate within the rated output capacity specified on their nameplate. Operation beyond this rating reduces accuracy, increases measurement errors, and causes inaccurate meter readings, similar to voltage transformers.

  • Primary Side Current: The primary current may continuously operate up to 1.1 times the rated current. Prolonged overload operation increases measurement errors and may overheat or damage the windings. The secondary current of a CT is typically 5 A or 1 A (commonly 5 A). Under normal operation, the secondary circuit operates close to a short-circuit condition.

  • The Secondary Circuit Must Never Be Open-Circuited During Operation: An open secondary circuit while the CT is energized will induce dangerously high voltages, endangering equipment and personnel. If the secondary circuit must be interrupted (e.g., for meter removal), the secondary terminals must first be securely short-circuited using a shorting link.

  • The Secondary Winding and Core Must Be Solidly Grounded: This prevents high-voltage transfer from the primary to the secondary side in case of insulation failure between windings.

  • Secondary Load Impedance Must Not Exceed the Rated Value: To ensure measurement accuracy, the connected burden must be within the rated impedance.

  • Observe Terminal Polarity When Wiring: Correct polarity must be maintained during installation and connection.

  • Never Interconnect CT and VT Secondary Circuits: Connecting a CT secondary to a VT secondary may leave the CT effectively open-circuited, creating a hazardous high-voltage condition.

  • Safety During Work: When performing work, a qualified supervisor must be present. Insulated tools must be used, and personnel must stand on an insulating mat.

II. Routine Inspection of Current Transformers in Service

  • Inspect porcelain insulators for cleanliness, absence of damage, cracks, or discharge marks. 

  • Check oil level is normal, oil color is clear and not darkened, with no signs of leakage or seepage. 

  • Listen for abnormal sounds or detect any burnt odor from the CT. 

  • Inspect primary lead connections for firmness, ensuring no loose bolts or signs of overheating. 

  • Verify the secondary winding grounding conductor is intact, securely connected, and free from looseness or breakage. 

  • Check that the terminal box is clean, dry, and free from moisture; ensure secondary terminals have good contact with no open circuits, arcing, or sparking.

Give a tip and encourage the author!
Recommended
Why Can't VT Be Shorted & CT Be Opened? Explained
Why Can't VT Be Shorted & CT Be Opened? Explained
We all know that a voltage transformer (VT) must never operate short-circuited, while a current transformer (CT) must never operate open-circuited. Short-circuiting a VT or opening the circuit of a CT will damage the transformer or create hazardous conditions.From a theoretical standpoint, both VTs and CTs are transformers; the difference lies in the parameters they are designed to measure. So why, despite being fundamentally the same type of device, is one prohibited from short-circuit operatio
Echo
10/22/2025
Why Is Compact Substation Grounding Resistance Usually ≤4Ω?
Why Is Compact Substation Grounding Resistance Usually ≤4Ω?
As a key power distribution equipment, the safe operation of a compact substation relies on reliable grounding measures. People often wonder: Why is the grounding resistance of a compact substation generally required to be no more than 4Ω? Behind this value, there are rigorous technical bases and application scenario restrictions. In fact, the requirement of ≤4Ω is not mandatory in all cases. It mainly applies to scenarios where the high - voltage system adopts "ungrou
Edwiin
07/23/2025
What Are the Common Faults of Low-Voltage Voltage Transformers and Their Solutions?
What Are the Common Faults of Low-Voltage Voltage Transformers and Their Solutions?
Open - Circuit Fault on the Secondary SideOpen - circuit in the secondary side is a typical fault of low - voltage voltage transformers, showing abnormal voltmeter readings (zero/fluctuation), faulty power meters, buzzing noises, and core overheating. When open - circuited, the secondary voltage spikes (no secondary current to balance the primary EMF), causing core saturation, flux distortion, and potential overheating/damage.Causes include loose terminals, poor contact, or human error. In low
Felix Spark
07/18/2025
Impact of Long-Term Immersion on Epoxy-Insulated Low-Voltage Current Transformers
Impact of Long-Term Immersion on Epoxy-Insulated Low-Voltage Current Transformers
1 IntroductionLow - voltage current transformers for metering, with a through - core type epoxy resin structure, are widely used in distribution transformer areas and for small - to - medium - sized industrial and commercial electricity consumption. As a range expander for electric energy metering, their performance directly relates to electricity consumption safety and the accuracy of users' trade calculations. Studying long - term immersion's impact on these transformers is practically signifi
Felix Spark
07/17/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.