Zero Power Factor Characteristic (ZPFC)

05/10/2025

The Zero Power Factor Characteristic (ZPFC) of a generator represents a curve that illustrates the relationship between the armature terminal voltage and the field current. In this test, the generator operates at synchronous speed with a constant rated armature current and a zero lagging power factor. The Zero Power Factor Characteristic is also known as the Potier Characteristic.

To maintain a very low power factor, the alternator is loaded using reactors or an under - excited synchronous motor. The shape of the ZPFC closely resembles that of the Open Circuit Characteristic (O.C.C.).

The phasor diagram corresponding to a zero power factor lagging condition is presented as follows:

image.png

In the phasor diagram depicted above, the terminal voltage V serves as the reference phasor. Under the condition of zero power factor lagging, the armature current Ia lags behind the terminal voltage V by exactly 90 degrees. The voltage drop Ia Ra (where Ra is the armature resistance) is drawn parallel to the armature current Ia, while Ia XaL (with XaL being the armature leakage reactance) is plotted perpendicular to Ia.

image.png

Eg is the generated voltage per phase.

The phasor diagram at ZPF lagging with the armature resistance Ra neglected is shown below:

image.png

Far represents the armature reaction magnetomotive force (MMF). It is in phase with the armature current Ia, meaning their phase relationship is such that they vary simultaneously.

Ff denotes the MMF of the main field winding, commonly referred to as the field MMF. This is the magnetic - driving force generated by the field winding of the generator.Frstands for the resultant MMF, which is the combined effect of the armature reaction MMF and the field MMF within the machine's magnetic circuit.

The field MMF Ff is calculated by subtracting the armature reaction MMF Far from the resultant MMF Fr. Mathematically, this relationship is expressed as

image.png

As can be observed from the aforementioned phasor diagram, the terminal voltage V, the reactance voltage drop Ia XaL}, and the generated voltage Eg all exhibit the same phase. Consequently, the terminal voltage V is approximately equal to the arithmetic difference between the generated voltage Eg and the reactance voltage drop Ia XaL.

image.png

The three MMF phasor Ff, Fr and Far are in phase. Their magnitudes are related by the equation shown below:

image.png

The two equations mentioned above, namely equation (1) and equation (2), serve as the fundamental building blocks for the Potier triangle.When both sides of equation (2) are divided by Tf - where Tf represents the effective number of turns per pole on the rotor field - the equation can be transformed into its equivalent form in terms of field current. As a result,

image.png

Based on the above - derived equation, the field current can be obtained by summing up the resultant current and the armature reaction current.


Zhejiang Vziman Electric Group Co., Ltd. is a high-tech enterprise specializing in R&D, manufacturing, and service of power electrical equipment. Committed to innovation, quality, and customer satisfaction, it supplies smart solutions for global power sectors, covering grid construction, new energy, and industrial distribution. Core Business • Switchgear (GIS, circuit breakers, Recloser, Load break switch) • Distribution equipment (transformers, RMU, smart terminals) • Power automation systems • Engineering services (installation, maintenance, consulting) Technical Strength • Provincial R&D center, multiple patents • Modern production, ISO/GB/IEC/CE/UL certified • High capacity, large-scale delivery support Market & Vision Serves State Grid, Southern Grid, and global projects (Asia, Africa, Europe, etc.). Aims to lead in smart grids and new energy, promoting sustainable energy development.

Difference Between Short Circuit & Overload
Difference Between Short Circuit & Overload
One of the main differences between a short circuit and an overload is that a short circuit occurs due to a fault between conductors (line-to-line) or between a conductor and earth (line-to-ground), whereas an overload refers to a situation where equipment draws more current than its rated capacity from the power supply.Other key differences between the two are explained in the comparison chart below.The term "overload" typically refers to a condition in a circuit or connected device. A circuit
08/28/2025
Difference Between Leading and Lagging Power Factor
Difference Between Leading and Lagging Power Factor
Leading and lagging power factors are two key concepts related to the power factor in AC electrical systems. The main difference lies in the phase relationship between current and voltage: in a leading power factor, the current leads the voltage, whereas in a lagging power factor, the current lags behind the voltage. This behavior depends on the nature of the load in the circuit.What is Power Factor?Power factor is a crucial, dimensionless parameter in AC electrical systems, applicable to both s
08/26/2025
Difference Between Electromagnet and Permanent Magnet
Difference Between Electromagnet and Permanent Magnet
Electromagnets vs. Permanent Magnets: Understanding the Key DifferencesElectromagnets and permanent magnets are the two primary types of materials that exhibit magnetic properties. While both generate magnetic fields, they differ fundamentally in how these fields are produced.An electromagnet generates a magnetic field only when an electric current flows through it. In contrast, a permanent magnet inherently produces its own persistent magnetic field once it has been magnetized, without requirin
08/26/2025
Interpretation of the “Five Mandatory Surveys” for On - site Investigation in the Operation and Maintenance Specialty
Interpretation of the “Five Mandatory Surveys” for On - site Investigation in the Operation and Maintenance Specialty
The power outage and work scopes must be clearly inspectedCollaborate with the site survey leader to confirm the equipment to be maintained and the work area involved. Consider requirements such as the use of special vehicles and large machinery, and safe distances from adjacent energized equipment. Verify on-site whether the proposed power outage scope is sufficient to meet the operational needs.On-site safety measures must be clearly inspectedCollaborate with the site survey leader to verify s
Vziman
08/14/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!