HECS Series Generator Circuit-breakers

  • HECS Series Generator Circuit-breakers

Key attributes

Brand ROCKWILL
Model NO. HECS Series Generator Circuit-breakers
Rated voltage 25.3kV
Rated normal current 23.5kA
Rated frequency 50/60Hz
Rated short-time withstand current 130kA
Series HECS Series
Description

Overview

The generator circuit-breaker systems are three-phase systems with a SF6 circuit-breaker and a discon-nector in single-phase enclosures, supplied fully assembled on a common frame, with operating mechanisms and control equipment. In addition to the circuit-breaker and disconnector, the generator circuit-breaker systems are available with earthing switch, starting switch, short-circuiting connection, current and voltage transformers, surge capacitor and surge arrester. The single line diagram of a generator circuit-breaker system type HECS is depicted in figure.

Market pioneer

The wide range of ratings with short-circuit currents from 80 to 130 kA makes HECS the most used GCB in the world suitable for power plants with a unit power of up to 800 MW. With small and standardized dimensions HECS is easy to install and highly suitable for replacements and retrofits in existing power plants. HECS has very low lifecycle cost with up to 20,000 close-open (CO) no-load operations or 20 years between main overhauls.

World leader with state-of-art technology

HECS products are type tested according to IEEE C37.013 and in certain aspects even exceed the minimum requirements of IEC/ IEEE 62271-37-013, including switching of fault currents with full phase opposition (180°; out-of-phase). It is also type tested to interrupt generator-source short-circuit current exhibiting delayed current zeros with up to 130% degree of asymmetry.

Digitally integrated with GMS600

HECS is fully integrated with GCB digital monitoring system, GMS600. The GMS600 can perform many functions: data logging, disturbance recording, drive supervi-sion, temperature and SF6 density monitoring. In addition, HECS supports integration of GMS600-A, a breakthrough solution which measures online the contact overlapping time and gives indication of the ablation without the need to go out of operation. Data logged through GMS600 can be connected via the clouds to Digital Enterprise Connect platform.

Compact design

HECS products are fully assembled and factory tested to bring substantial cost and time savings in installation and commissioning at site. Its compact design fits into standard containers for easy transportation, handling and storage.

Technology parameters

Generator clrcult-breakers system type HECS HECS-80 HECS-100 HECS-130
General          
Rated maximum voltage   kV 23.0 25.3 25.3
Rated frequency   Hz 50/60 50/60 50/60
Rated normal current 50 Hz with IPB temperature 90°C/70°C HECS-S A rms up to 8500 - -
  HECS-M A rms up to 10500 up to 10500 -
  HECS-L A rms - up to 13400 up to 13400
  HECS-Lplus A rms - up to 14500 up to 14500
  HECS-XLp A rms - up to 18200 up to 18200
  HECS-XXLp A rms - - up to 23500
Rated normal current 60 Hz with IPB temperature 105°C/80°C HECS-S A rms up to 8000 - -
  HECS-M A rms up to 10000 up to 10000 -
  HECS-L A rms - up to 12000 up to 12000
  HECS-Lplus A rms - up to 13700 up to 13700
  HECS-XLp A rms - up to 17300 up to 17300
  HECS-XXLp A rms - - up to 22200
Rated insulation level          
Rated power frequency withstand voltage to earth and across circuit-breakers contacts   kV rms 60 (80) 60 (80) 60 (80)
across isolating distance of disconnector   kV rms 70 (88) 70 (88) 70 (88)
Rated lightning impulse withstand voltage to earth and across circuit-breakers contacts   kV peak 125 (150) 125 (150) 125 (150)
across isolating distance of disconnector   kV peak 145 (165) 145 (165) 145 (165)
Circuit-breaker          
Rated peak withstand current   kA peak 220 300 360
Rated short-time withstand current   kA, 3s 80 100 130
Rated short-circuit making current   kA peak 220 300 360
Rated short-circuit breaking current   kA peak 80 100 130
Rated operating sequence     CO-30min-CO CO-30min-CO CO-30min-CO
Opening time   ms 34 ± 5 34 ± 5 34 ± 5
Rated interrupting time   ms 68 68 68
Mechanical endurance life   CO 20000 20000 20000
Disconnector          
Rated peak withstand current   kA peak 220 300 360
Rated short-time current   kA, 3s 80 100 130
Operating time   s 2 2 2
Earthing switch          
Rated peak withstand current   kA peak 220 300 360
Rated short-time current   kA, 1s 80 100 130
Operating time   s 2 2 2

 

Know your supplier

Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m² Total staff: 700+ Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: Medium and High Voltage Switchgear/Power and Distribution Transformers/Instrument Transformers and Sensors/Lightning Protection and Electrical Insulation/Substations and E-Houses/Electrical Panel and Controlgear
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login
or continue with
New here?
Register