Commercial Wall-mounted DC EV Charger
Wall-mount DC charger: 20/30/40kW, input ≤36/54/72A. Power-electronic device; no primary switchgear parameters. Short-circuit & lightning protection via external distribution.
Wall-mount DC charger: 20/30/40kW, input ≤36/54/72A. Power-electronic device; no primary switchgear parameters. Short-circuit & lightning protection via external distribution.
Wall‑mount DC charger 20‑40kW, wall‑installation with expansion bolts, bottom‑incoming cables. Requires external residual‑current, short‑circuit and lightning protection. No explicit IEC number in manual, generally complies with IEC 61851‑23, IEC 61851‑1 EV charging standards.
Installazione a parete con M860 bulloni di espansione. Utensili necessari: trapano elettrico, punta da trapano M12, multimetro, cacciavite a croce / a taglio, chiave M13, ecc. La profondità del foro deve essere di 45-50 mm.
Per 20 kW si consiglia un cavo in rame da 6 mm² con interruttore differenziale da 40 A; per 30 kW si consiglia un cavo in rame da 10 mm² con interruttore da 64 A; per 40 kW si consiglia un cavo in rame da 16 mm² con interruttore da 80 A. Il quadro di distribuzione deve essere dotato di protezione contro sovracorrenti, cortocircuiti e scariche atmosferiche.
Verificare l'involucro dell'apparecchiatura per eventuali danni o scrostamenti della vernice; ispezionare l'integrità della guaina del cavo; controllare la pistola di ricarica per eventuali rotture e assicurarsi che non vi siano corpi estranei all'interno della testa della pistola; misurare con il multimetro l'eventuale cortocircuito in ingresso CA; confermare che l'isolamento e la messa a terra soddisfino i requisiti.