Specification for 33kV Vacuum Automatic Recloser by Kenya Power and Lighting Company Limited (KPLC)
Others · ROCKWILL

Specification for 33kV Vacuum Automatic Recloser by Kenya Power and Lighting Company Limited (KPLC)

Kenya 33kV overhead distribution feeders, rural power network upgrade, solar farm outgoing lines, industrial overhead power supply, sectionalizing protection on long medium voltage overhead circuits. Used for automatic fault isolation, transient fault rec

Updated2026.09
LanguageEnglish
FilePDF · 405.1 KB
Specification33kV Vacuum Automatic RecloserKenya Power and Lighting Company Limited (KPLC)

Document description

This document applies to the technical requirements for the design, testing, supply, installation, and related supporting equipment (sensors, controllers, cables, etc.) of automatic reclosing on 33kV columns in Kenya Power and Lighting Company Limited (KPLC) 33kV 50Hz medium voltage distribution network.

ROCKWILL 33kV Vacuum Automatic Recloser is pole-mounted outdoor equipment fully engineered to satisfy KPLC specification for Kenya’s 33kV overhead distribution network. Nominal system voltage 33kV, highest system voltage 36kV, equipment rated voltage 38kV, minimum rated continuous current 630A with optional 1250A. Vacuum interrupter for fault interruption, solid dielectric insulation. Control cabinet IP65 per IEC 60529, supporting up to four auto-reclose operations before lockout. Protection & control unit supports local/remote operation and standard communication protocols for SCADA integration. Type tests shall comply with IEC 62271-100 and KPLC mandatory witness test requirements. Designed for harsh tropical environment, anti-UV, anti-pollution, suitable for Kenya overhead distribution feeders.

Related Products

Frequently asked questions

Specification for 33kV Vacuum Automatic Recloser by Kenya Power and Lighting Company Limited (KPLC) defines the minimum design, material, rating, test and performance requirements for pole-mounted three-phase vacuum reclosers applied on KPLC 33kV overhead distribution network. It mandates rated equipment voltage 38kV, minimum 630A continuous current, IP65 control cabinet and maximum four auto-reclose operations before lockout.

Specification for 33kV Vacuum Automatic Recloser by KPLC requires minimum 70kV rms power frequency withstand voltage for 1 minute and 170kV peak lightning impulse withstand voltage (1.2/50μs). The insulation system shall remain stable under tropical high humidity, dust and UV exposure in Kenyan field conditions.

Specification for 33kV Vacuum Automatic Recloser by KPLC requires the recloser to complete up to four auto-reclose operations and then lock out for permanent faults. The protection sequence is fully programmable, to distinguish transient overhead faults from permanent faults and improve supply restoration for rural feeders.

Specification for 33kV Vacuum Automatic Recloser by KPLC stipulates control cabinet enclosure IP65 per IEC 60529. The cabinet door shall be equipped with padlock provision compatible with KPLC standard safety padlock to prevent unauthorized access to protection and control circuits.

Specification for 33kV Vacuum Automatic Recloser by KPLC requires full IEC 62271 series type tests and KPLC witness test upon request. The vacuum recloser detects and isolates overhead faults automatically, restores power for transient faults quickly, reduces outage duration and reduces manual fault patrol workload on long rural 33kV feeders.