Search


REC-24 SF6 - Free Ring Main Unit
Brochure · ROCKWILL

REC-24 SF6 - Free Ring Main Unit

24 kV SF6‑free ring‑main‑unit, rated current 630‑1250A, short‑circuit breaking current 20‑25kA, pure‑air / nitrogen insulation, zero‑gauge working‑pressure, ultra‑low leakage rate, compact indoor metal‑enclosed switchgear for distribution‑networks.

Updated2026.09
LanguageEnglish
FilePDF · 1.4 MB
RMUSF6 - Free RMU

Document description

This PDF product manual supports tender comparison, distribution‑substation project selection and pre‑sales technical evaluation. This eco‑friendly gas‑insulated ring‑main‑unit complies with IEC 62271‑1, IEC 62271‑200 and relevant ANSI standards.

It adopts vacuum‑interruption technology with pure‑air or nitrogen zero‑GHG insulating medium and can operate safely under zero gauge pressure; fully‑sealed gas‑tank reaches IP67 and cabinet shell IP4X, type‑tested annual gas‑leakage rate down to 0.01 %, whole‑casing partial‑discharge below 5 pC.

This manual records full dielectric‑withstand values, loop‑resistance ≤140 µΩ, rated gas pressure, multi‑grade mechanical‑life for circuit‑breaker, load‑break‑switch, disconnector and earthing‑switch, complete operating‑sequence, service‑environment of ‑40 ℃ ~ +55 ℃ with allowable installation altitude up to 2500 m.

It features rotating three‑position switch, double visible isolating gaps, five‑protection interlock mechanism, zinc‑inlaid alloy anti‑corrosion surface‑treatment passing 168‑hour salt‑spray test, multiple cabinet variants including upper‑isolation and lower‑isolation layout with compact bay dimensions.

Custom‑manufacturing covering design adjustment, assembly and project‑specific factory‑acceptance‑test is available for diversified distribution‑grid projects. Please contact us for complete dimension drawings and full set of type‑test reports.

Related Products

Frequently asked questions

Double visible gaps provide intuitive isolation confirmation; five‑protection interlock blocks mis‑operation sequences, jointly securing personal safety during overhaul and commissioning work. Please contact us for interlock‑logic guidance.

Rotating three‑position switch integrates closing, opening and earthing functions within single unit, simplifying internal layout and offering visible isolation gap for maintenance safety. Please contact us for structure‑principle description.

It can maintain full insulation performance even at zero gauge pressure, greatly reducing failure risks caused by gas‑leakage and lowering routine gas‑monitoring workload. Please contact us for gas‑system principle introduction.