Document description

The globally recognized benchmark standard governing medium-voltage pole-mounted vacuum circuit reclosers and fault interrupters (current Ed.3 2019 edition). Mandates full type-testing of the primary switch body, microprocessor controller, and umbilical control cable as an indivisible integrated system for time-current characteristics (TCC) and duty cycles. Specifies the rated type-test operating sequence as O - 0.3s - CO - 3min - CO, requires Class M2 mechanical endurance (10,000 operations), and enforces strict discrimination between restrikes and non-sustained disruptive discharges (NSDD).