D165T_D265T LV Pole Mounted Breaker
Operating Instruction · ROCKWILL

D165T_D265T LV Pole Mounted Breaker

Outdoor LV pole‑mounted circuit‑breaker, rated 440V, max 230A, IP23 protection. 4‑pole (3 protected + neutral) electronic trip unit, for 50‑160kVA pole transformers, ‑25℃~+80℃ wide‑temperature pole‑mount installation.

Add us on Google
Updated2026.10
LanguageEnglish
FilePDF · 263.5 KB
LV Pole Mounted BreakerD265T LV Pole Mounted BreakerD165T LV Pole Mounted Breaker

Document description

This document introduces outdoor LV pole‑mounted circuit‑breaker complying with IEC 60947‑2 international low‑voltage circuit‑breaker standard and French distribution‑network technical specification HN 63‑S‑11. It adopts 4‑pole construction; three phase poles feature electronic trip protection while neutral pole is for conduction only.

IP23‑rated enclosure adapts harsh outdoor pole‑mount environment, providing overload and short‑circuit protection for multiple‑capacity pole‑mount distribution transformers. Complete set includes breaker main‑body, mounting clamp bracket and operating accessories, supporting remote ground‑level linkage operation.

Transformer neutral earthing is achieved when breaker is open. Documentation covers outline dimension, pole‑mount drawing and wiring schematic. It defines installation height, bolt torque, earthing resistance, site commissioning and multi‑level inspection schedule.

Fault‑troubleshooting table and safety rules for live‑line‑isolation & high‑altitude work are documented. Widely deployed for pole‑mount transformer protection in rural and suburban overhead distribution networks.

Related Products

Frequently asked questions

Unauthorised enclosure opening is forbidden per manual requirement. In case of mechanism jamming, isolate and power‑off the unit and contact manufacturer technical support instead of on‑site disassembly.

Secondary control cables shall be routed separately from main‑power cables, not bundled together. Mark all control wires for later maintenance. Complete open‑close signal feedback test after wiring to confirm remote signal transmit‑receive works properly.

Standard delivery includes breaker unit, mounting clamp bracket, fasteners, operating accessories, manual and certificate of conformity. Earthing cable, power cable, insulation sleeves and safety warning signs are site‑consumables to be prepared by customer.

Outline drawing, pole‑mount bracket drawing and electrical wiring schematic are available. Full set of IEC 60947‑2 compliant type‑test reports are supplied. We offer transformer‑capacity‑selection consultation and complete tender‑phase technical documentation.

Inspection cycles cover daily, weekly, monthly and seasonal checks. Daily: visual check and position indicator. Weekly: terminals, earthing and insulation covers. Monthly: voltage‑current measurement, earthing resistance and trip‑parameter verification. Special seasonal inspections before thunder‑storm, high‑temperature and cold seasons.