RLS type Indoor g3 Load Break Switch
RLS G3 gas load break switch: 12/24/36kV, 630-800A, lightning impulse 75-215kV, 2s short-time 20-31.5kA, making peak 50-80kA. For RMU and cable cabinet control & protection.
RLS G3 gas load break switch: 12/24/36kV, 630-800A, lightning impulse 75-215kV, 2s short-time 20-31.5kA, making peak 50-80kA. For RMU and cable cabinet control & protection.
RLS adopts eco‑friendly g3 gas (GWP<1% of SF₆) and permanent‑magnet arc‑extinguishing principle. Compact footprint with 3‑position mechanical interlock, manual/motor‑driven mechanisms and fuse‑combination option. It complies with IEC 60420, IEC 60265‑1 and supports customized manufacturing.
RLS-12/24kV indoor g3 load switch replaces SF6. Compact, easy install for RMUs and cable branch cabinets. Strong adaptability.
SF6‑free indoor g3 load break switch for 36kV, offering eco‑friendly, reliable, and compact medium‑voltage switching for distribution networks.
g3, eşdeğer elektriksel performansa sahip olup SF₆'ye kıyasla %99'dan fazla daha düşük Küresel Isınma Potansiyeline sahiptir, toksik değildir ve REACH uyumludur. Ürün, IEC 60420, IEC 60265-1 ve ilgili GB standartlarına uygundur.
Giriş besleme ünitesi için manuel K-tipi / motorlu K-tipi; çıkış besleme ve transformatör ünitesi için manuel A-tipi / motorlu A-tipi sunulmaktadır. Motor gerilimi isteğe bağlıdır: DC24/48/110/220 V.
Evet, termik darbe sigortalı sigorta kombinasyonu versiyonu mevcuttur. İsteğe bağlı aksesuarlar: gerilim göstergesi, kapı interlok sistemi, yardımcı kontak, bakır konektör, kablo kelepçesi vb. Özel üretim desteklenmektedir.