RLS G3 gas load break switch: 12/24/36kV, 630-800A, lightning impulse 75-215kV, 2s short-time 20-31.5kA, making peak 50-80kA. For RMU and cable cabinet control & protection.

Terakhir Diperbarui2026.09
BahasaEnglish
BerkasPDF · 2.2 MB
g3 LBSSF6-free LBS

Deskripsi Dokumen

RLS adopts eco‑friendly g3 gas (GWP<1% of SF₆) and permanent‑magnet arc‑extinguishing principle. Compact footprint with 3‑position mechanical interlock, manual/motor‑driven mechanisms and fuse‑combination option. It complies with IEC 60420, IEC 60265‑1 and supports customized manufacturing.

Produk Terkait

Pertanyaan yang Sering Diajukan

g3 memiliki GWP lebih rendah >99% dibandingkan SF₆ dengan kinerja listrik yang setara, tidak beracun, dan mematuhi REACH. Produk ini mematuhi IEC 60420, IEC 60265‑1, dan standar GB yang relevan.

Menyediakan tipe K manual / tipe K bermotor untuk unit umpan masuk; tipe A manual / tipe A bermotor untuk unit umpan keluar & transformator. Tegangan motor opsional: DC24/48/110/220 V.

Ya, versi kombinasi sekering tersedia dengan sekering impactor termal. Aksesori opsional: indikator tegangan, interlock pintu, kontak bantu, konektor tembaga, klem kabel, dll. Manufaktur kustom didukung.