Harmonic Mitigation Solution for New Energy Power Stations: Comprehensive Management of High-Frequency Harmonics in Photovoltaic Power Plants

Rockwill
17yrs 700++ staff 108000m²+m² US$150,000,000+ China

Ⅰ. Problem Scenario
High-frequency harmonic injection from PV plant inverter clusters
During operation of large-scale centralized PV power plants, multiple inverters operating in parallel generate wide-band harmonics in the 150-2500Hz range (primarily the 23rd to 49th harmonics), leading to the following grid-side issues:

  • Current Total Harmonic Distortion (THDi) reaching 12.3%, significantly exceeding IEEE 519-2014 standard limits.
  • Causing capacitor bank overload, overheating, and protective device maloperation.
  • Increased Electromagnetic Interference (EMI) affecting nearby sensitive equipment.

II. Core Solution
Adoption of an LC passive filter topology, constructing efficient harmonic absorption circuits using customized reactors + capacitor banks.

  1. Key Equipment Selection

Equipment Type

Model/Specification

Core Function

Dry-Type Iron-Core Series Reactor

CKSC Type (Custom Design)

Provides precise inductive reactance, suppressing high-frequency harmonics.

Filter Capacitor Bank

BSMJ Type (Matched Selection)

Resonates with reactors to absorb specific harmonic bands.

  1. Technical Parameter Design
    Reactor Inductance: 0.5mH ±5% (@50Hz fundamental frequency)
    Quality Factor (Q): >50 (Ensures low-loss high-frequency filtering)
    Insulation Class: Class H (Long-term withstand temperature 180°C)
    Reactance Ratio Configuration: 5.5% (Optimized for 23rd-49th high-frequency band)
    Topology Structure: Delta (Δ) Connection (Enhances high-order harmonic shunting capability)
  2. Filter System Design Key Points
    Resonant Frequency Calculation:
    f_res = 1/(2π√(L·C)) = 2110Hz
    Accurately covers the target frequency band (150-2500Hz), achieving local absorption of high-frequency harmonics.

III. EMC Mitigation Effectiveness Validation

Indicator

Before Mitigation

After Mitigation

Standard Limit

THDi

12.3%

3.8%

≤5% (IEEE 519)

Individual Harmonic Distortion

Up to 8.2%

≤1.5%

Compliant with GB/T 14549

Capacitor Temperature Rise

75K

45K

Compliant with IEC 60831

IV. Engineering Implementation Advantages

  1. High-Efficiency Filtering:
    The 5.5% reactance ratio design specifically suppresses harmonics above the 23rd order, providing a 40% improvement in high-frequency response compared to traditional 7% schemes.
  2. Safety and Reliability:
    The Class H temperature rise insulation system ensures stable equipment operation in outdoor environments ranging from -40°C to +65°C.
  3. Cost Optimization:
    The low-loss design (Q > 50) results in additional system power consumption of < 0.3% of output power.

V. Deployment Recommendations

  1. Installation Location:​ Low-voltage side busbar of the 35kV collection substation.
  2. Configuration:​ Each 2Mvar capacitor bank series-connected with 10 CKSC reactors (Group-based automatic switching).
  3. Monitoring Requirement:​ Install an online harmonic analyzer to track THDi changes in real-time.

Solution Value:​ Effectively resolves high-frequency harmonic pollution in new energy power stations, extends capacitor lifespan by over 37%, and avoids PV output curtailment due to harmonic violation penalties.

07/25/2025
Recommended
Application of New DC Circuit Breakers in Short-Circuit Fault Protection
I. Introduction​With the rapid advancement of modern information technology, intelligence has become a major trend in the development of industrial equipment. In the field of high-voltage switching, intelligent circuit breakers—as critical control components in power systems—form the foundation for automation and intelligence in power systems. This study focuses on an intelligent DC circuit breaker based on single-chip microcomputer (SCM) technology, emphasizing its practical applica
Application Solutions of DC Circuit Breakers in the New Energy Sector
I. Overview​With the rapid development of new energy power generation and electric vehicle (EV) charging facilities, DC systems have imposed higher requirements for safety protection equipment. Traditional AC circuit breakers cannot effectively interrupt DC fault currents, creating an urgent need for specialized DC circuit breaker solutions. This solution provides professional protection configurations for two major application scenarios: photovoltaic (PV) power generation systems and EV chargin
Low-Cost, Low-Loss DC Arc-Free Circuit Breaker Solution for Rail Transit
I. Solution Overview​This solution addresses the protection needs of DC systems (particularly rail transit traction power supply) against short-circuit faults by proposing a DC circuit breaker solution based on optimized mechanical breaker structure. It achieves arc-free interruption through capacitor voltage control, combining low on-state loss and high reliability, making it suitable for frequent operation scenarios.​II. Core Principle​Utilizes a fast mechanical switch topology combined with p
PEBS Circuit Breaker DC Safety Solution
Solution Overview​In modern renewable energy power systems, such as photovoltaic (PV) power generation and energy storage systems, fault protection on the DC side is a core element for ensuring safe, stable, and efficient operation. The Projoy PEBS series DC miniature circuit breakers are specifically designed for such applications, providing a comprehensive and efficient solution integrating arc control, overload protection, and short-circuit protection. This solution aims to deliver the highes
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.