Rockwill's SF6 Circuit Breaker Solution for 33kV Substations in Nigeria

Rockwill
17yrs 700++ staff 108000m²+m² US$150,000,000+ China

Project Background
Nigeria’s tropical climate, characterized by year-round high temperatures (annual average of 35°C) and humidity (≥80%), poses significant challenges to the sealing integrity, insulation performance, and gas management of electrical equipment. Rockwill was contracted to upgrade a 33kV substation, deploying its proprietary HV-type SF6 circuit breaker to address critical issues:

  1. Sealing Failure Risks: Accelerated aging of seals due to heat and water ingress during monsoon seasons.
  2. SF6 Gas Management: High humidity increases risks of gas liquefaction and moisture(exceeding limits), compromising insulation.
  3. Frequent Operations: Demand for ≥6,000 mechanical cycles to handle grid fluctuations via capacitor bank switching.

Technical Solutions

  1. Standardized Installation
    Compliance: Strict adherence to GBJ147-90 standards and manufacturer guidelines, supplemented with detailed work instructions.
    Hoisting: 16-ton crane for precise positioning, coupled with porcelain insulator withstand tests (power-frequency voltage ≥33kV, lightning impulse voltage ≥170kV).
    Conductor Crimping: Hydraulic crimping tools with ≤5% torque error to minimize contact resistance under high temperatures.
  2. High-Precision Vacuum & Gas Handling
    Pipeline Prep: Pipes cleaned with anhydrous alcohol; sealing grooves coated with 7501 silicone grease to prevent contamination.
    Vacuum Process: Two-stage vacuum pumping to 133Pa, held for 8 hours, followed by 4-hour observation (≤1% fluctuation).
    Gas Quality: SF6 moisture content verified (≤8ppm per cylinder) and post-filling chamber checks (≤150ppm). Leak detection via 1×10⁻⁶ sensitivity detectors.
  3. Climate-Adaptive Design
    Waterproof Seals: Flange grooves coated with waterproof adhesive (-20°C~120°C) and reinforced with shaft retaining rings.
    Anti-Condensation: Built-in humidity-controlled dehumidifiers (threshold: 70%) to prevent gas liquefaction.
    High-Temperature Materials: Silver-plated copper-tungsten alloy contacts withstand arc temperatures ≥2,000°C (contact resistance ≤35μΩ).
  4. Maintenance & Local Support
    Modular Maintenance: Detachable arc chutes enable rapid component replacement, minimizing downtime.
    Local Training: Lagos-based technical center offers hands-on training in gas analysis, mechanical debugging, and more.
    Smart Monitoring: Integrated pressure sensors and wireless modules track SF6 density, temperature, and operations, with auto-alerts for anomalies.

Key Achievements

  1. Reliability: Post-deployment annual failure rate <0.2%, supporting ≥10 daily capacitor switching operations.
  2. Environmental Resilience: Passed 72-hour (45°C, 95% humidity), exceeding IEC 62271-203 sealing standards.
  3. Cost Efficiency: 8-year maintenance cycles (vs. oil circuit breakers) and 30% lower lifecycle costs.

Conclusion
Rockwill’s solution combines rigorous process controls (vacuum protocols, gas QA) and climate-adaptive innovations (waterproof seals, smart dehumidification) to overcome Nigeria’s extreme conditions, setting a replicable benchmark for SF6 breaker applications in Africa. Future plans include SF6/N₂ hybrid gas technology to further reduce carbon emissions and operational costs.

05/13/2025
Recommended
Application of New DC Circuit Breakers in Short-Circuit Fault Protection
I. Introduction​With the rapid advancement of modern information technology, intelligence has become a major trend in the development of industrial equipment. In the field of high-voltage switching, intelligent circuit breakers—as critical control components in power systems—form the foundation for automation and intelligence in power systems. This study focuses on an intelligent DC circuit breaker based on single-chip microcomputer (SCM) technology, emphasizing its practical applica
Application Solutions of DC Circuit Breakers in the New Energy Sector
I. Overview​With the rapid development of new energy power generation and electric vehicle (EV) charging facilities, DC systems have imposed higher requirements for safety protection equipment. Traditional AC circuit breakers cannot effectively interrupt DC fault currents, creating an urgent need for specialized DC circuit breaker solutions. This solution provides professional protection configurations for two major application scenarios: photovoltaic (PV) power generation systems and EV chargin
Low-Cost, Low-Loss DC Arc-Free Circuit Breaker Solution for Rail Transit
I. Solution Overview​This solution addresses the protection needs of DC systems (particularly rail transit traction power supply) against short-circuit faults by proposing a DC circuit breaker solution based on optimized mechanical breaker structure. It achieves arc-free interruption through capacitor voltage control, combining low on-state loss and high reliability, making it suitable for frequent operation scenarios.​II. Core Principle​Utilizes a fast mechanical switch topology combined with p
PEBS Circuit Breaker DC Safety Solution
Solution Overview​In modern renewable energy power systems, such as photovoltaic (PV) power generation and energy storage systems, fault protection on the DC side is a core element for ensuring safe, stable, and efficient operation. The Projoy PEBS series DC miniature circuit breakers are specifically designed for such applications, providing a comprehensive and efficient solution integrating arc control, overload protection, and short-circuit protection. This solution aims to deliver the highes
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.