Ⅰ. Muhimman Fungciyonlarin Karkasindan Wuce
1. Recloser: Ingantaccen Kirkiro na Sakamakun
- Mahimmanci: Yadda aiki da tsari, mekanizumin da ingantaccen kontrol ta. Ya taka iya koyar gaban halittu → kirkiro → sakamakun da rike → kwalba.
- Mahimmanci Abubuwa:
- Ayoyi na Iyakokin Aiki: Tana da amfani game da ayoyi masu yawan (misali, "daya da rike + uku da rike" ko "biyu da rike + biyu da rike") don in fada halittukan da kusa da al'amuran. Misali: Aiki da rike na daya ya koyar halittukan da rike; wanda biyo na rike suna da shirin da wasu.
- Ba Da Amfani Game Da Kontrol na Barazan Ba: Tana da transformers da mikroprosasa a cikinsu mafi karfi da zai amfani game da current na line don koyar, ba da amfani game da relay protection panels ba.
2. Outdoor High Voltage Circuit Breaker: Tsarin Kirkiro na Gaba
- Mahimmanci: An yi da ita don kirkiro current na gaban halittu, ya danganta da relays na barazan don logika.
- Abubuwan Da Ba Su Mata Ba:
- Ayoyi masu kwallonsa (misali, "kirkiro → 0.3s → kirkiro → 180s → kirkiro"), ba zai iya haɗa da tsarin al'amuran network mai yawa ba.
- An buƙata da control cabinets da sources na DC, wanda ke hada da system na kwallon karshe da kudin.
II. Mahimmanci Abubuwan na Reclosers
1. Integrasia Masu Yawanci & Ingantaccen
- Kontrol na Jiki: Tana da amfani game da detection na current, logic judgment, da koyar na line don koyar, ya haka yana koyar da dukkan aiki, ya koyar da amfani game da mutane.
- Ingantaccen Algoritomin Protection:
- Inverse-time characteristic curves suka dogara da fuse ampere-second characteristics don samun coordination.
- Zero-sequence CT modules za a iya zama optional don in haɗa da accuracy na ground fault detection.
2. Hira na Reliability na Power Supply
- Mechanism na Sakamakun Da Yawa: 3–4 attempts na sakamakun (misali, "daya da rike + uku da rike") ya sauka 80% na halittukan da rike a first attempt.
- Rapid Fault Isolation: Daga sectionalizers, ya koyar da lokacin da isolating faults ≤30s, ya koyar da kudin outage scope by 70%+.
- Backfeed Prevention: Tie recloser (QR0) delay-closing logic ya koyar da reverse power flow during substation maintenance.
3. Cost Efficiency & Deployment
- 40% Lower TCO:
- An buƙata da relay protection panels, DC screens, da switchroom space.
- Pole-mounted installation (200–300 lbs) vs. breakers requiring 1,800–3,000 lbs + concrete foundations.
- 3× Longer Maintenance Cycles:
- Vacuum/SF₆ types endure 10,000 operations; maintenance every 3–5 years vs. frequent spring-mechanism repairs in breakers.
4. Extreme Environment Adaptability
- Enhanced Weather Resistance:
- Three-phase common tank (SF₆-insulated) tolerates -40°C to 40°C.
- Epoxy-encapsulated split-phase design suits mines/coastal areas.
- Topology Flexibility:
- Single-phase units for rural branches; three-phase assemblies resolve neutral grounding issues.
III. Key Parameter Comparison
|
Characteristic
|
Recloser
|
Outdoor HV Circuit Breaker
|
Advantage
|
|
Rated Current
|
400–1200A (630A mainstream)
|
1200–3000A
|
More economical for light loads
|
|
Short-Circuit Breaking Capacity
|
≤16kA (high-end: 25kA)
|
20–40kA
|
Meets most branch-line needs
|
|
Operation Sequence
|
Programmable (e.g., two fast + two delayed)
|
Fixed standard sequence
|
Adapts to protection strategies
|
|
Control Dependency
|
Self-contained (IED-operated)
|
Requires external relays
|
Simplified system architecture
|
|
Installation
|
Pole-mounted
|
Ground frame structure
|
Space-saving, rapid deployment
|
IV. Typical Applications
- Rural/Mountainous Networks:
- Segments long overhead lines (e.g., 10kV radial feeders), replacing "breaker + protection panel" setups.
- Urban Grid Automation:
- Ring Main Unit (RMU) nodes (QR0 enables automatic load transfer) with FTU for "three-remote" control.
- Special Sites: Oilfields/mines (corrosion-resistant design + anti-theft password function).
V. Limitations & Solutions
- Breaking Capacity Limit: Use circuit breakers for short-circuit currents >16kA.
- Ungrounded Systems: Add zero-sequence CTs to improve single-phase ground fault detection.