Search


Outdoor Pole‑Mounted SVG Device for Three‑Phase Imbalance Correction

  • Outdoor Pole‑Mounted SVG Device for Three‑Phase Imbalance Correction

Key attributes

Brand Rw Energy
Series RWSVG
Rated voltage 380V
Frequency 50Hz
Efficiency ≥97%
Description

The Problem

Rural distribution lines are long, loads are scattered, and end-of-line voltage is chronically low. With the rise of PV inverters, EV chargers, and other non-linear equipment, three-phase imbalance, harmonic pollution, and reverse reactive power flow are becoming widespread — causing transformer overheating, excessive line losses, and frequent end-user equipment trips.

This device is purpose-built to solve these issues, fully compliant with national low-voltage distribution network governance standards.

Working Principle

Advanced power electronics combined with real-time digital closed-loop control. The IGBT-based inverter module dynamically injects or absorbs reactive current and unbalanced three-phase currents. Intelligent high-speed algorithms continuously monitor phase voltage, current distortion, load imbalance ratio, and harmonic content, delivering millisecond-response, high-precision compensation.

Key Features

Feature Description
Three-Phase Imbalance Correction Real-time dynamic compensation with ultra-fast response
Neutral Current Compensation Up to 3× rated phase current, prevents neutral-point potential drift
Reactive Power Compensation Dynamic active/reactive regulation, accuracy ≥95%, PF up to 0.99, intelligent anti-over-compensation
Harmonic Suppression 2nd to 13th order, suitable for EV chargers, PV inverters, and industrial loads
End-of-Line Voltage Boost Especially effective on long rural low-voltage feeders

 

Technical Specifications

Parameter Specification
Rated Voltage 380 V (±20% allowable fluctuation)
Frequency 50 Hz 
Wiring Three-phase three-wire
Compensation Capacity 30 / 50 / 100 / 150 kvar
Efficiency ≥97%
Power Consumption ≤3% of rated power
Switching Frequency 20 kHz
Response Time 100 μs / 10 ms
Cooling Forced-air cooling
Noise < 65 dB
Protection Rating IP55 with built-in Class II SPD
Operating Temperature &ndash;10&deg;C to +45&deg;C
Storage Temperature &ndash;20&deg;C to +60&deg;C
Humidity < 95% RH (non-condensing)

 

Control Technology

  • Three-level digital vector control algorithm

  • Precise voltage/current waveform distortion detection for active harmonic suppression

Current Transformer

  • External CT input (Class 0.5 or above, &ge;5 VA, secondary recommended: 5 A)

Installation & Enclosure

  • Dimensions: 978(H) &times; 465(W) &times; 485(D) mm (custom sizes available)

  • Material: Stainless steel or hot-dip galvanized steel

  • Side cable entry for easy on-site wiring

  • Front sun-shielded, waterproof, lockable maintenance door

  • Rear ventilation grilles matched to forced-air cooling

  • Designed for pole-mounted deployment in rural distribution networks

Monitoring & Communication

Local: WiFi handheld terminal for full parameter viewing and real-time status monitoring.

Remote (optional): GPRS cloud platform supporting data reporting, remote parameter configuration, multi-level fault alarms, and historical data review.

Protection

Multi-layer protection: over-temperature, over-voltage, under-voltage, over-current, short-circuit, module overload, and grid anomaly detection. Compliant with DL/T 860 and national low-voltage distribution network standards.

  • Adaptive compensation under variable load conditions

  • Anti-resonance design prevents system resonance risks

  • Automatic module isolation during grid anomalies; auto-restart when grid normalizes

  • Switches to protection mode under severe power quality deterioration

Frequently asked questions

Three‑phase imbalance is typically caused by the uneven distribution of single‑phase loads, such as residential appliances, lighting, and increasingly, EV chargers. This imbalance leads to increased energy losses in transformers, neutral line heating, and voltage fluctuations at the end of the line.

Unlike traditional capacitor banks that provide fixed, step‑wise compensation, the RWSVG is an active power electronic device based on IGBT technology. It provides continuous, stepless compensation in both inductive and capacitive ranges. Most importantly, it can redistribute active power between phases to eliminate current imbalance, which passive capacitors cannot do.

Yes. By injecting reactive power dynamically, the RWSVG stabilizes the terminal voltage and raises the voltage level of low‑voltage feeders. This ensures that users at the end of long distribution lines receive stable power, preventing equipment malfunction due to undervoltage.

Know your supplier

Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 30000m² Total staff: 100 Highest Annual Export(usD): 100000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: Medium and High Voltage Switchgear/Low Voltage Electrical Components/Renewable Energy and EV Charging/Electrical Testing and Metering/Lighting and Monitoring Equipment/Power Generation and Backup Systems/Power and Distribution Transformers/Instrument Transformers and Sensors/Transformer and Switchgear Parts/Construction Equipment and Tools/Electrical Manufacturing and Factory Automation/Lightning Protection and Electrical Insulation/Electrical Safety Equipment/Substations and E-Houses/Power Electronic Equipment/Electrical Panel and Controlgear/Power Quality Equipment
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login
or continue with
New here?
Register