• LVQB SF6 gas insulated current transformer
  • LVQB SF6 gas insulated current transformer
LVQB SF6 gas insulated current transformer
discuss personally
Model
LVQB-40.5
Basic info
Brand Wone
Model NO. LVQB SF6 gas insulated current transformer
Rated voltage 40.5kV
Series LVQB
Product Detail

Product introduction:
    LVQB series current transformers are SF6 gas insulated, inverted structure to meet the IEC/IEEE standard.The series connected transformer in the line has the functions of electricenergy measurement, metering, relay protec tion and transient protection.
Product features:
●The primary winding is of through type conductive rod structure with good dynamic and thermal stability.
●The maximum thermal stability current is 63kA/3s (when the primary winding is in series). 
●The primary winding passes through the center of the secondary winding without the influence of magnetic flux leakage, and the measurement accuracy reaches 0.1 and 0.2s
●The upper shell is of aluminum alloy welding structure, and the top is equipped with a metal explosion-proof disc. If the internal high-energy discharge occurs, when the gas pressure exceeds 1.0MP a, the explosion-proof disc will break, so as to achieve the purpose of pressure release, improve product safety, and there is no danger of explosion.
●The secondary winding is poured into the aluminum shield housing with organic materials, and the measuring and protection lines at the secondary side will not be subject to electrical attack due to insulation breakdown.
●The optimized electrode shielding structure improves the internal and external electric field distribution of the product, and the insulation performance is excellent. The local discharge test is conducted under the power frequency test voltage.
●The cast aluminum footing is directly cast on the external insulating bushing, and the bottom plate bolt is fixed with the footing from the bottom up to avoid water ingress and ponding from the base fastener. The secondary outlet box is cast with stainless steel or aluminum alloy. The dust-proof, waterproof and breathable sealing structure meets the requirements of IP55. 
●The secondary terminals for users to connect are Phoenix special terminal blocks, which are more convenient and fast to plug, pull and connect.
●The sealing ring is made of ethylene propylene diene monomer (EPDM) and imported fluor silicone rubber. It is suitable for areas with high and low temperature changes and harsh ambient temperatures. The annual air leak age rate is less than 0.5%.
●The product performance remains unchanged after rigorous transportation vibration test.
●The shell, base and junction box are all made of aluminum alloy. The nameplate is made of stainless steel. All exposed parts will never rust. The base is equipped with a density meter, which can display the gas pressure inside the transformer (the displayed value is automatically converted to the internal gas pressure at 20 ℃) and density. When the internal pressure of the transformer drops to the alarm pressure, it will provide a signal and require gas supplement.

LVQB SF6 gas insulated current transformer-2.png

LVQB SF6 gas insulated current transformer-3.png

Remark: Approximate dimensions and weights for special requirements, please consult us.

Know your supplier
Wone
Main Categories
High voltage/Low voltage/Wire cable/Instrument meters/New energy/Tester/Production equipment/Generator/Electrical fittings/Integrated Electrical Equipment
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$50,000,000
Professional Experience
1 years
Workplace
65666m²m²
占位
占位
Related Products
Related Knowledges
What are the common faults of low-voltage voltage transformers?
What are the common faults of low-voltage voltage transformers?
Open - Circuit Fault on the Secondary SideOpen - circuit in the secondary side is a typical fault of low - voltage voltage transformers, showing abnormal voltmeter readings (zero/fluctuation), faulty power meters, buzzing noises, and core overheating. When open - circuited, the secondary voltage spikes (no secondary current to balance the primary EMF), causing core saturation, flux distortion, and potential overheating/damage.Causes include loose terminals, poor contact, or human error. In low
Felix Spark
07/18/2025
Analysis of the Principle of Second - harmonic Restraint for Overcurrent Protection of Distribution Automation Switches
Analysis of the Principle of Second - harmonic Restraint for Overcurrent Protection of Distribution Automation Switches
Substance of Second - harmonic Restraint in Overcurrent ProtectionThe substance of second - harmonic restraint in overcurrent protection is to use the second - harmonic component to judge whether the current is a fault current or an excitation inrush current. When the percentage of the second - harmonic component to the fundamental - wave component is greater than a certain value, it is judged to be caused by the excitation inrush current, and the overcurrent protection is blocked.Therefore, the
Leon
07/18/2025
What are the typical connection methods for 35kV distribution lines?
What are the typical connection methods for 35kV distribution lines?
Typical Wiring Diagram of 35kV Line Radial π ConnectionWhen a 35kV line adopts a radial power grid structure, a single - side power supply or a double - side power supply radial type can be used according to the situation of the power supply points, and a loop - out interval is reserved at the end of the line.Typical Wiring Diagram of 35kV Line Radial T - ConnectionFor double - radial lines, it is advisable to select a double - side power supply. When the power supply points do not meet the r
Leon
07/18/2025
Why are the ground fault point and the accident point not at the same location?
Why are the ground fault point and the accident point not at the same location?
Fault Transfer VoltageIn low - voltage distribution systems, there is a type of personal electric shock accident where the accident occurrence point and the system fault point are not at the same location. This kind of accident occurs because after a ground fault happens elsewhere, the generated fault voltage is conducted to the metal casings of other equipment through the PE wire or PEN wire. When the fault voltage on the metal casing of the equipment is higher than the human - body safe voltag
Leon
07/18/2025
Analysis of Transformer Capacity, Load Rate and Number of Units Selection Issues
Analysis of Transformer Capacity, Load Rate and Number of Units Selection Issues
The safe and economical operation of power transformers is related to the safety, economy, stability, and reliability of the operations of various industries. The limitations of conditions such as the investment economic indicators for its selection, the economic benefits of maintenance and operation, and the adaptability in the new environment (access of distributed power sources, configuration of energy storage, etc.) make it impossible to include comprehensive factors in other aspects.The cap
Leon
07/17/2025
Analysis of the Impact of Immersion on the Performance of Low-Voltage Current Transformers
Analysis of the Impact of Immersion on the Performance of Low-Voltage Current Transformers
1 IntroductionLow - voltage current transformers for metering, with a through - core type epoxy resin structure, are widely used in distribution transformer areas and for small - to - medium - sized industrial and commercial electricity consumption. As a range expander for electric energy metering, their performance directly relates to electricity consumption safety and the accuracy of users' trade calculations. Studying long - term immersion's impact on these transformers is practically signifi
Felix Spark
07/17/2025
×
Inquiry
Download