• High - voltage pneumatic load break switch
High - voltage pneumatic load break switch
discuss personally
Model
FKN-12/630
Basic info
Brand ROCKWILL
Model NO. High - voltage pneumatic load break switch
Rated voltage 12kV
Rated normal current 630A
Rated frequency 50/60Hz
Series FKN
Product Detail

Product Overview

The s high - voltage pneumatic load break switches and their combined electrical appliances are indoor high - voltage switchgear for AC 12kV, 50Hz. This load break switch features high specific technical parameters and reliable action. The basic form of the operating mechanism is manual spring - energy - storage type, and it can also be equipped with an electromagnetic spring operating mechanism. Based on the pneumatic arc - extinguishing principle, it can interrupt multiple times without replacing the arc - extinguishing tube.

The high - voltage load break switch can close, carry and open load currents under normal circuit conditions, and has the capability to close short - circuit currents and open short - circuit currents within a specified short time.

The  load break switches can be equipped with earthing switches. The earthing switch has the same short - circuit making capacity as the load break switch, as well as the dynamic and thermal stability capability, and has a strict mechanical interlock with the load break switch, ensuring that misoperation is impossible in terms of structure.

 

Key Features

  • When the FKN12 - 12 load break switch is equipped with a high - voltage current - limiting fuse (with a striker) to form a load break switch - fuse combination, it serves as overload and short - circuit protection for loads (such as power transformers). When one or more phases of the fuse blow, the three phases of the load break switch automatically open.

  • The high - voltage load break switch is suitable for installation in ring - main unit switch cabinets and other types of switch cabinets for receiving and distributing electrical energy.

Technical Parameters

Serial No.

Name

Unit

Value

1

Rated Voltage

KV

12

2

Rated Frequency

Hz

50

3

Rated Current

A

630

4

Maximum Rated Current of Fuse

A

100

5

Rated Active Load Breaking Current, Rated Closed - loop Breaking Current

A

630

6

Rated Short - time Withstand Current (2S)

KA

20

7

Rated Short - circuit Making Current, Rated Peak Withstand Current

KA

50

8

1min Power Frequency Withstand Voltage, Phase - to - phase and to - ground / Break

KV

42/48

9

Lightning Impulse Withstand Voltage (Peak Value), Phase - to - phase and to - ground / Break

KV

75/85

10

Rated Cable Charging Breaking Current

A

10

11

Rated Breaking of No - load Transformer

KVA

1250

12

Mechanical Life

Times

2000

13

Rated Breaking Transfer Current

A

1150

14

Rated Short - circuit Breaking Current of Fuse

KA

31.5

Main Mechanical Characteristics of Load Break Switch

Serial No.

Name

Unit

Value

Remarks

1

Phase - to - phase Center Distance

mm

210 ± 3


2

Total Stroke of Conductive Rod

mm

215 ± 5

3

Distance Between Moving and Static Arc at Opening Position

mm

>160

4

Over - stroke of Electrical Contact of Moving Contact Rod

mm

42 ± 3

5

Just - Closing Speed

m/s

3.8 <sup>+0.7</sup><sub>-0.2</sub>

6

Just - Opening Speed

m/s

>2.7

7

Three - phase Closing Asynchronism

ms

>10

Contact between moving contact rod and contact fingers

8

Three - phase Opening Asynchronism

ms

>5

Separation between moving contact rod and contact fingers

Operating Environmental Conditions

  • Altitude: Not exceeding 1000m.

  • Ambient Temperature: Maximum +40&deg;C, Minimum -10&deg;C.

  • Relative Humidity: Daily average not exceeding 95%, Monthly average not exceeding 90%.

  • Seismic Intensity: Less than 8 degrees.

Know your supplier
ROCKWILL
Rockwill Electric Group Global Manufacturer of High voltage and medium-voltage power equipment and smart grid solutions. Headquartered in Wenzhou, China. Serving 100+ countries with quality, innovation, and trust. What We Offer: • HV-MV switchgear (VCB, SF₆ circuit breakers, RMU, GIS) • Distribution transformers and substations • Smart grid and monitoring systems • Solar, wind, EV charging, and energy storage solutions • EPC turnkey power projects Certified: ISO 9001 / ISO 14001 / ISO 45001
Main Categories
High Voltage Electrical Apparatus
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$150,000,000
Professional Experience
16 years
Workplace
108000m²m²
占位
占位
Related Products
Related Knowledges
Ensuring Reliability: A Deep Dive into Transformer Maintenance
Ensuring Reliability: A Deep Dive into Transformer Maintenance
IntroductionElectric transformers are the backbone of modern power distribution systems, silently enabling the reliable delivery of electricity to homes, businesses, and industries. As these critical assets age and the demand for uninterrupted power grows, the importance of diligent transformer maintenance has never been greater. This essay explores the essential role of transformer maintenance, highlighting the value of proactive care, the impact of advanced diagnostic technologies, and the tra
Vziman
09/03/2025
How does a transformer work?
How does a transformer work?
Transformer Operation PrincipleA transformer is an electrical device that operates on the principle of electromagnetic induction to transfer electrical energy from one circuit to another. It enables the adjustment of voltage levels within an alternating current (AC) system, either stepping up (increasing) or stepping down (decreasing) voltage while maintaining the same frequency.Working Principle:Basic ComponentsA transformer consists of two coils, known as windings—the "primary winding" connect
Rockwell
09/03/2025
Constant testing of high-voltage cable lines
Constant testing of high-voltage cable lines
1. Definition of High-Voltage Cable Line Constant TestingHigh-voltage cable line constant testing refers to the systematic measurement, using specialized instruments, of electrical parameters such as resistance, inductance, capacitance, and conductance before a cable line is commissioned or after major maintenance. The aim is to obtain fundamental data characterizing the electromagnetic properties of the cable, serving as a critical testing phase that provides accurate parameter support for powe
Oliver Watts
09/03/2025
Technical Analysis of 220 kV High-Voltage Cable Construction in Winter
Technical Analysis of 220 kV High-Voltage Cable Construction in Winter
1.Work Environment Requirements and Safeguard MeasuresBased on technical requirements for cable equipment storage, laying, transportation, laying, transposition, testing, and cable terminations, the project owner and construction units have conducted extensive trials and implemented protective measures regarding ambient temperature, humidity, bending radius, traction control, and route optimization. These measures ensure high-voltage cable quality and on-site safety under harsh winter conditions
James
09/03/2025
Withstand voltage test of high-voltage cables
Withstand voltage test of high-voltage cables
Withstand voltage test is an insulation test, but it is a destructive test that can reveal insulation defects difficult to detect in non-destructive testing.The test cycle for high-voltage cables is three years, and it must be conducted after non-destructive tests. In other words, the withstand voltage test is performed only after all non-destructive tests have been passed.Most high-voltage cables used today are cross-linked polyethylene (XLPE) cables, which can have large cross-sections and cov
Oliver Watts
09/03/2025
Analysis of Abnormal Causes of High-Voltage Cable Grounding Circulation and Typical Cases
Analysis of Abnormal Causes of High-Voltage Cable Grounding Circulation and Typical Cases
I. Introduction to Cable Grounding Loop CurrentCables rated 110 kV and above use a single-core structure. The alternating magnetic field generated by the operating current induces a voltage on the metallic sheath. If the sheath forms a closed circuit through the earth, a grounding loop current will flow on the metallic sheath. Excessive grounding loop current (loop current exceeding 50 A, more than 20% of the load current, or a ratio of maximum-to-minimum phase current greater than 3) not only a