| Brand | ROCKWILL |
| Series | RMR,RGIS,REC |
A ring main unit built on air insulation: no sealed gas tank, no SF6, no pressure monitoring. Compartmented air-insulated switchgear with load break switches, vacuum interrupters and earthing, designed for ring distribution from 12kV to 36kV.

A ring main unit (RMU) is a compact assembly of two or more ring circuits plus a transformer feeder, used to connect a distribution substation into a ring network. In an air insulated version, the busbars, switches and cable interfaces sit in air at atmospheric pressure inside compartmented enclosures, instead of a sealed SF6 or gas tank.
The switching duty is split the same way as in a gas unit: load break switches (or a three-position switch) make and break normal load current and provide the earthing position, while a vacuum interrupter or vacuum circuit breaker handles fault current where protection is required. The difference is that the dielectric is the air inside the cubicle, so the design lives or dies by creepage distance, compartment barriers and moisture control rather than by gas pressure.
That makes the format straightforward to build, easy to inspect and cheap to service — and it makes it sensitive to the site. Air insulated RMUs are at their best in a dry, ventilated indoor switch room, in a kiosk with heaters and ventilation, or under an enclosure that keeps rain, dust and condensation away from the insulation surfaces.
Two, three or four ring ways, with the transformer feeder as a separate way and clear mechanical interlocking between them.
Busbar sections can be added on site, so a two-way unit can grow into a three- or four-way ring without replacing the assembly.
Switch-fuse for small transformer feeders, or a vacuum circuit breaker with relay protection where reclosing and remote control are required.

Typical air insulated RMU capability, class by class. Values are the design ratings for the class; a project can be taken higher on request.
Swipe the table sideways to see all columns →
| Class | Rated current | Short-time | Peak | PF withstand | LI impulse | Typical use |
|---|---|---|---|---|---|---|
| 12kV | 630A (1250A on request) | 20kA / 3s (25kA) | 50kA | 42kV | 75kV | Secondary substations, industrial rings |
| 24kV | 630A (1250A on request) | 20kA / 3s (25kA) | 50kA | 50kV | 125kV | Primary distribution rooms, expandable rings |
| 36kV | 630A | 20kA / 3s | 50kA | 70kV | 170kV | Regional distribution, larger substations |
Busbar rating refers to the ring and feeder ways; the transformer way is limited by the switch-fuse or breaker fitted. Higher fault levels need a metalclad panel rather than an RMU envelope.

| Property | Air insulated switchgear RMU |
|---|---|
| Insulation | Atmospheric air; phase barriers, shrouded conductors and adequate creepage set the dielectric |
| Interruption | Vacuum interrupter or vacuum circuit breaker; load break switch for ring ways |
| Earthing | Three-position switch or dedicated earthing switch, mechanically interlocked with the cable compartment |
| Cable connection | Inner-cone bushings with screened separable elbows; the cable compartment is earthed before access |
| Compartments | Busbar, switch, cable and (where fitted) breaker compartment separated by metal barriers |
| Operation | Manual with a removable handle, or motorised for remote switching |
| Protection | Overcurrent and earth fault relay, over/under voltage, auto-reclose on breaker-equipped units |
| Communication | IEC 61850, DNP3, Modbus, IEC 60870-5-101/104 via RTU / FTU / DTU |
| Enclosure | IP4X standard, IP54 with an outdoor kiosk; anti-condensation heaters in humid locations |
| Ambient | -15°C to +40°C indoor standard; wider range with a conditioned kiosk |
| Maintenance | Periodic inspection and contact wear checks; no gas handling, no pressure monitoring |
| Life | Mechanical endurance of the switch and mechanism defines service life; the insulation does not degrade with age if the enclosure stays dry |
Three formats do the same ring duty; the choice is about space, environment and how much maintenance access the operator wants.
Swipe the table sideways to see all columns →
| Air insulated RMU | Sealed gas / dry air RMU | Metalclad AIS panel | |
|---|---|---|---|
| Insulation | Atmospheric air in compartments | Sealed tank, SF6 or dry air | Atmospheric air, withdrawable breaker |
| Footprint | Medium — needs a switch room | Smallest | Largest, one bay per circuit |
| Environment | Dry, ventilated, indoor or kiosk | Any — immune to humidity and pollution | Indoor, ventilated room |
| Service access | Direct — compartments open, parts visible | Limited — sealed for life | Best — breaker withdrawable |
| Current / fault level | 630A, 20–25kA | 630–1250A, 20–31.5kA | up to 4000A, up to 40kA |
| Cost per ring | Lowest | Higher | Highest |
| Best for | Standard dry substations, budget projects | Coastal, humid, polluted, cold sites | High current, frequent switching, easy service |
| If the project is… | Specify |
|---|---|
| A dry indoor 12kV substation with a normal ring | Two-way air insulated RMU with switch-fuse transformer way |
| An expandable ring that will grow in phases | Extensible air insulated RMU with spare busbar sections |
| Remote-controlled distribution automation | Motorised RMU with relay and IEC 61850 RTU |
| A coastal or very humid site | Sealed dry-air or gas RMU instead of an air insulated unit |
| High fault level or 2000A+ feeders | Metalclad air insulated switchgear panel line-up |
Common requirements in IEC 62271-1, switches and earthing in -102 / -103, metal-enclosed assemblies in -200, IP ratings in IEC 60529.
Dielectric withstand, temperature rise, short-time and peak withstand, mechanical endurance, IP verification and internal arc where specified.
Power-frequency withstand on each unit, wiring and interlock checks, operation test of every switch and breaker before dispatch.

Send the voltage class, ring arrangement and transformer rating. We will confirm the configuration, the protection scheme and the delivery schedule.
Ring Main Unit — a compact assembly of ring circuits plus a transformer feeder that ties a distribution substation into a ring network. "RUM" is a common misspelling of the same term.
No. An RMU is a compact ring unit with load break switches and a transformer way; a metalclad panel is a full switchboard bay with a withdrawable breaker, used where current or fault level is higher.
Yes, extensible designs allow additional busbar sections and ways to be added on site, so a two-way ring can become three- or four-way without replacing the enclosure.
A dry, ventilated space. Humidity and condensation are the main risks to air insulation, so anti-condensation heaters and a sealed kiosk are used on outdoor or humid installations.
12kV, 24kV and 36kV classes at 630A busbar current, 20kA for three seconds (25kA on request), with 1250A available on request at 12kV and 24kV.