| Brand | Wone Store |
| Numero ng Modelo | 3-phase Pillar type Magnetically controlled vacuum circuit breaker Tres na phase na uri ng pillar na magneticamente kontroladong vacuum circuit breaker |
| Tensyon na Naka-ugali | 12kV |
| Rated Current | 1250A |
| bilang ng mga pole | 3P |
| Rated short-circuit breaking current | 31.5kA |
| Layong ng mga phase | 210mm |
| Serye | MS4 |
Ang serye ng MS4-12-630/20-XX na mga circuit breaker ay mga indoor switchgear na batay sa semi-hard magnetic material actuator mechanisms. Ginagamit ito sa three-phase AC power systems na may rated voltage na 12KV at frequency na 50-60Hz, bilang isang protective at control device. Ito ay partikular na angkop para sa madalas na operasyon sa rated current o maraming pag-break ng short-circuit currents. Ang serye ng mga circuit breaker na ito ay kasama ang circuit breaker at ang drive module.
Ang struktura ng circuit breaker
Bawat phase ay may isang actuator mechanism, na inilalapat nang perpendicularly at axially sa vacuum interrupter. Ang tatlong excitation coils ay konektado sa parallel. Ang three-phase actuator
mechanisms ay nagpapahiwatig ng synchronous action sa pamamagitan ng synchronous shaft at nagbibigay ng auxiliary switch position signal output nang parehong oras.
Ang vacuum interrupter ay gumagamit ng external bellows, at ang bellows ay gawa sa stainless steel lamination welding process. Ang contact opening distance ay 8mm at ang overtravel ay 2mm. Ang mga contact ay disenyo batay sa prinsipyong longitudinal magnetic field arc extinguishing.
Contact pressure spring sa insulating rod upang tiyakin ang maasintas na kontak sa pagitan ng moving at static contacts ng VI at na ang mga aksyon na ito ay sumasang-ayon sa operational characteristic
requirements.
Ang insulating frame ay gawa ng SMC, na nakakalinya ang upper at lower terminals, operating insulating rods, flexible connections, vacuum interrupters at iba pang mga komponente, na naglalaman ng tungkulin ng insulation at support.
Paggamit
MS4-01/02 Angkop para sa SF6 gas insulated RMU
MS4-03/04 Angkop para sa air insulated switchgear
Teknolohiya parameters
No. |
Item |
Unit |
MS4-01 |
MS4-02 |
MS4-03 |
MS4-04 |
1 |
Rated voltage |
kV |
12 |
12 |
12 |
12 |
2 |
Rated current |
A |
1250 |
1250 |
1250 |
1250 |
3 |
Rated power frequency withstand voltage |
kV |
42 |
42 |
42 |
42 |
4 |
Rated impulse withstand voltage |
kV |
85 |
85 |
85 |
85 |
5 |
Rated short circuit breaking current |
kA |
25 |
31.5 |
25 |
31.5 |
6 |
Rated peak withstand current |
kA |
63 |
80 |
63 |
80 |
7 |
Rated short-circuit withstand current |
kA |
25 |
31.5 |
25 |
31.5 |
8 |
Duration of short circuit |
s |
4 |
4 |
4 |
4 |
9 |
Rated frequency |
Hz |
50 |
50 |
50 |
50 |
10 |
Phase center distance |
mm |
150 |
150 |
210 |
210 |
11 |
Contact distance |
mm |
8±0.5 |
8±0.5 |
8±0.5 |
8±0.5 |
12 |
Over travel |
mm |
2±0.5 |
2±0.5 |
2±0.5 |
2±0.5 |
13 |
Rated operation cycle |
- |
O-0.3s-CO-15s-CO |
|||
14 |
Inherent closing time(don’t include DM time) |
ms |
< 25 |
< 25 |
< 25 |
< 25 |
15 |
Different time of closing operation |
ms |
≤2 |
≤2 |
≤2 |
≤2 |
16 |
Bouncing time |
ms |
≤2 |
≤2 |
≤2 |
≤2 |
17 |
Inherent opening time(don’t include DM time) |
ms |
5±0.5 |
5±0.5 |
5±0.5 |
5±0.5 |
18 |
Different time of opening operation |
ms |
≤2 |
≤2 |
≤2 |
≤2 |
19 |
Mechanical operations (CO-cycles) |
Times |
50000 |
50000 |
50000 |
50000 |
20 |
Rated short-circuit-breaking current time |
Times |
50 |
50 |
50 |
50 |
21 |
Number of auxiliary switches |
pcs |
6NO+6NC |
|||
22 |
Weight |
kg |
34 |
34 |
34 |
34 |
Tala: Kailangan idagdag ang mga aluminum heat sink.
Sukat