| Chapa | ROCKWILL |
| Namba ya Modeli | 12kV 24kV 36kV Mwili wa Viwanja wa Kufungua na Kutumia (RMU) unaoungatia Nishati ya Ustawi kwa kutumia Hewa Safi au Nitrogeni |
| volts maalum | 12kV |
| Mkato wa viwango | 630A |
| mfumo wa mafano | 50/60Hz |
| Siri | REC |
Maelezo:
ROCKWILL® inaheshimu sana uwiano wa ubora wa bidhaa na teknolojia ya ufanisi, na kusikiliza kila hatua ya ufanisi wa bidhaa kwa uhaba na ujanja. Tumiko la gasi la uzio tu linatumika kutafuta tofauti kamili ya kuwakilisha hewa chafu, nitrogen, karbona dioxi, na hewa safi. Hewa safi iliyoundwa na kiwango cha maji chenye ukosefu na ufanisi mkubwa imechaguliwa kama gazini bora ya uzio ili kukuzima SF6. Kitengo muhimu cha switch ya bidhaa inatumia tabia mpya ya chombo chenye viungo vya kuzuia magonjwa ya vacuum, iliyokumbuka na mtazamo wa switch wa sehemu tatu, na muundo wazi na mfupi; Mfunguo mzima wa gasi unapata hewa safi kutokuwa na SF6, na muundo mzuri wa utambulisho wa umeme, na uzio wa sehemu zote ni chini ya 5pC; Mikakati ya kuchukua maji ya zinc inayotumika kwenye kifaa cha kudhibiti imetoka zaidi ya masaa 168, na muda wa kudumu wa kifaa cha kudhibiti unaweza kuwa hadi 30000 mara.
Sifa:
Ring main unit yenye uzio wa hewa safi / nitrogen
Gasi zenye hekima ya mazingira
Uzio wa karboni ni sifuri, uzio wa takataka ni sifuri
Ufanisi wa kufanya kazi na ujanja, kutafuta ubora zaidi
Inafanikiwa na viwango vya IEC/ANSI
Inatoa ufanisi wa kudhibiti kutegemea
Muhimano wa kutosha wa kupanga, kujenga, kutathmini...
Suluhisho la amani na ulimwengu
Mzunguko wa kutoa mkubwa, biashara rahisi na usakinishaji rahisi
Majina muhimu ya teknolojia (sehemu tatu):
12kV
N |
Item |
Unit |
Data |
1 |
Rated maximum voltage |
kV |
12 |
2 |
Rated maximum current |
A |
630/1250 |
3 |
Rated frequency |
Hz |
50/60 |
4 |
Method of Arc Suppressing |
Vacuum |
|
5 |
Method of Insulation |
Pure air/Nitrogen |
|
6 |
Rated short circuit breaking current |
kA |
20/25 |
7 |
Rated peak value withstand current |
kA |
50/63 |
8 |
Rated 1min power frequency withstand voltage |
kV |
42 |
9 |
Rated lightning impulse voltage |
kV |
75 |
10 |
Operation sequence |
/ |
C-0.3-CO-180-CO |
12 |
Resistance loop |
µΩ |
≤140 |
13 |
Rated gas pressure (20℃ gauge) |
Mpa |
0.02 |
14 |
Minimum operating gas pressure |
Mpa |
0 |
15 |
Mechanical life - Circuit breaker |
N |
10000 |
Mechanical life - Load break switch |
N |
3000/6000 |
|
Mechanical life - Disconnector |
N |
3000/6000 |
|
Mechanical life - Earthing switch |
N |
3000/6000 |
|
16 |
Protection grade - Gas tank |
IP67 |
|
Protection grade - Shell |
IP4X |
||
17 |
Rated annual air leakage rate |
% |
0.01 |
24kV
N |
Item |
Unit |
Data |
1 |
Rated maximum voltage |
kV |
24 |
2 |
Rated maximum current |
A |
630/1250 |
3 |
Rated frequency |
Hz |
50/60 |
4 |
Method of Arc Suppressing |
Vacuum |
|
5 |
Method of Insulation |
Pure air/Nitrogen |
|
6 |
Rated short circuit breaking current |
kA |
20/25 |
7 |
Rated peak value withstand current |
kA |
50/63 |
8 |
Rated 1min power frequency withstand voltage |
kV |
50 |
9 |
Rated lightning impulse voltage |
kV |
125 |
10 |
Operation sequence |
/ |
C-0.3-CO-180-CO |
12 |
Resistance loop |
µΩ |
≤150 |
13 |
Rated gas pressure (20℃ gauge) |
Mpa |
0.04 |
14 |
Minimum operating gas pressure |
Mpa |
0 |
15 |
Mechanical life - Circuit breaker |
N |
10000 |
Mechanical life - Load break switch |
N |
3000/6000 |
|
Mechanical life - Disconnector |
N |
3000/6000 |
|
Mechanical life - Earthing switch |
N |
3000/6000 |
|
16 |
Protection grade - Gas tank |
IP67 |
|
Protection grade - Shell |
IP4X |
||
17 |
Rated annual air leakage rate |
% |
0.01 |
36kV
N |
Item |
Unit |
Data |
1 |
Rated maximum voltage |
kV |
36 |
2 |
Rated maximum current |
A |
630/1250 |
3 |
Rated frequency |
Hz |
50/60 |
4 |
Method of Arc Suppressing |
Vacuum |
|
5 |
Method of Insulation |
Pure air/Nitrogen |
|
6 |
Rated short circuit breaking current |
kA |
20/25 |
7 |
Rated peak value withstand current |
kA |
50/63 |
8 |
Rated 1min power frequency withstand voltage |
kV |
70 |
9 |
Rated lightning impulse voltage |
kV |
170 |
10 |
Operation sequence |
/ |
C-0.3-CO-180-CO |
12 |
Resistance loop |
µΩ |
≤160 |
13 |
Rated gas pressure (20℃ gauge) |
Mpa |
0.04 |
14 |
Minimum operating gas pressure |
Mpa |
0 |
15 |
Mechanical life - Circuit breaker |
N |
10000 |
Mechanical life - Load break switch |
N |
3000/6000 |
|
Mechanical life - Disconnector |
N |
3000/6000 |
|
Mechanical life - Earthing switch |
N |
3000/6000 |
|
16 |
Protection grade - Gas tank |
IP67 |
|
Protection grade - Shell |
IP4X |
||
17 |
Rated annual air leakage rate |
% |
0.01 |
Aina ya chache kwa ujumla ya kifaa cha uzio lenye upamba wa hewa tu au nitrogeni

Aina |
Ukubwa wa mwisho wa panel moja |
Ukubwa wa upande wa panel moja |
Ukubwa wa panel moja wa moduli mdogo |
Panel Circuit Breaker |
390 * 850 * 1950 |
390 * 850 * 1950 |
390 * 850 * 1950 |
Panel Load Break Switch |
390 * 850 * 1950 |
390 * 850 * 1950 |
390 * 850 * 1950 |
Panel PT (na 3phase, 5 mstari) |
600 * 850*1950 |
600 * 850 * 1950 |
600 * 850 * 1950 |
Panel PT (phase moja) |
420 * 850 * 1950 |
420 * 850 * 2000 |
420 * 850 * 1600 |
Bus Riser |
375 * 850 * 1950 |
375 * 850 * 2000 |
375 * 850 * 1600 |
Panel Metering |
750 * 850 * 1950 |
750 * 850 * 2000 |
750 * 850 * 1600 |