Shunt Capacitor: What is it? (Compensation & Diagram)

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Is A Shunt Capacitor

What is a Shunt Capacitor?

A capacitor bank is very essential equipment of an electrical power system. The power required to run all the electrical appliances is the load as useful power is active power. The active power is expressed in kW or MW. The maximum load connected to the electrical power system is mainly inductive in nature such as electrical transformer, induction motors, synchronous motor, electric furnaces, fluorescent lighting are all inductive in nature.

In addition to these, inductance of different lines also contributes inductance to the system.
Because of these inductances, the system
current lags behind system voltage. As the lagging angle between voltage and current increases, the power factor of the system decreases. As the electrical power factor decreases, for same active power demand the system draws more current from source. More current causes, more line losses.

Poor electrical power factor causes poor voltage regulation. So to avoid these difficulties, the electrical power factor of the system to be improved. As a capacitor causes current to lead the voltage, capacitive reactance can be used to cancel the inductive reactance of the system.
The capacitor reactance can be used to cancel the inductive reactance of the system.

The capacitor reactance is generally applied to the system by using static capacitor in shut or series with system. Instead of using a single unit of capacitor per phase of the system, it is quite effective to use a bank of capacitor units, in the view of maintenance and erection. This group or bank of capacitor units is known as capacitor bank.

There are mainly two categories of capacitor bank according to their connection arrangements.

  • Shunt capacitor.

  • Series capacitor.

The Shunt capacitor is very commonly used.

How to determine Rating of Required Capacitor Bank

The size of the Capacitor bank can be determined by the following formula :
Where,
Q is required KVAR.
P is active power in KW.
cosθ is
power factor before compensation.
cosθ’ power factor after compensation.

Location of Capacitor Bank

Theoretically it is always desired to commission a capacitor bank nearer to reactive load. This makes transmission of reactive KVARS is removed from a greater part of the network. Moreover if capacitor and load are connected simultaneously, during disconnection of load, capacitor is also disconnected from rest of the circuit. Hence, there is no question of over compensation. But connecting capacitor with each individual load is not practical in the economical point of view. As the size of loads extremely differs for different consumers. So various size of capacitors are not always readily available. Hence proper compensation can not be possible at each loading point. Again each load is not connected with system for 24 × 7 hours. So the capacitor connected to the load also can not be fully utilized.

Hence, capacitor, is not installed at small load but for medium and large loads, capacitor bank can be installed at consumer own premises. Although the inductive loads of medium and large bulk consumers are compensated, but still there would be considerable amount of VAR demand originated from different uncompensated small loads connected to the system. In addition to that, inductance of line and transformer also contribute VAR to the system. On viewing of these difficulties, instead of connecting capacitor to each load, large capacitor bank is installed at main distribution sub-station or secondary grid sub-station.

Connection of Shunt Capacitor Bank

The capacitor bank can be connected to the system either in delta or in star. In star connection, the neutral point may be grounded or not depending upon protection scheme for capacitor bank adopted. In some cases the capacitor bank is formed by double star formation.

Generally large capacitor bank in electrical substation is connected in star.
The grounded star connected bank has some specific advantages, such as,

  • Reduced recovery voltage on circuit breaker for normal repetitive capacitor switching delay.

  • Better surge protection.

  • Comparatively reduced over voltage phenomenon.

  • Lesser cost of installation.

  • In a solidly grounded system the voltage of all 3-phases of a capacitor bank, are fixed and remain unchanged even during 2 phase operation period.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
What Is THD? How It Affects Power Quality & Equipment
What Is THD? How It Affects Power Quality & Equipment
In the field of electrical engineering, the stability and reliability of power systems are of paramount importance. With the advancement of power electronics technology, the widespread use of nonlinear loads has led to an increasingly serious problem of harmonic distortion in power systems.Definition of THDTotal Harmonic Distortion (THD) is defined as the ratio of the root mean square (RMS) value of all harmonic components to the RMS value of the fundamental component in a periodic signal. It is
Encyclopedia
11/01/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.