• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Why Doesn’t a Standard Breaker Protract Against Ground Faults?

Edwiin
Field: Power switch
China

A broken neutral in a circuit with a standard breaker poses a shock hazard because the breaker does not monitor or protect the neutral wire. The internal mechanism of a standard breaker is not designed to detect ground-fault currents during operation. Standard circuit breakers are engineered to protect against overloads and short circuits, not ground faults.

Standard breakers monitor current in the hot wire and trip if the current exceeds the breaker’s rating—typically due to an overload or short circuit. However, with a broken neutral, fault current may return to the source through the ground wire. This occurs because the ground and neutral terminal bars are bonded in the main panel.

Consequently, a current lower than the breaker’s rated capacity can flow through the circuit in an unintended path. Since no excessive current travels through the hot wire, the breaker does not detect a fault and remains closed. As a result, parts of the circuit stay energized, creating a hidden shock risk that the breaker does not address.

The most common faults in an electric circuit are as follows:
Overloads and Short Circuits

Standard breakers react to excessive current caused by overloads or direct short circuits (high-current faults where current flows directly from hot to neutral or hot to hot). These conditions create a current surge, which the breaker detects and trips to prevent damage.

Ground Faults

A ground fault occurs when current leaks from the hot wire to a grounded surface, bypassing the neutral wire (e.g., due to a broken neutral or a live wire contacting a metal appliance case or wet surface). Ground faults may not generate the high current surges required to trip a standard breaker, especially if only a small amount of current leaks to ground. This leakage can create severe shock hazards without reaching the breaker’s trip threshold.

How Does a Standard Breaker Respond to a Short Circuit or Ground Fault?

Let’s examine how a standard breaker behaves and reacts to short circuits or ground faults in a circuit, as illustrated below.

Consider this example: In a 120V/240V main panel, a lighting circuit is controlled and protected by a 15-amp standard breaker on a 120V supply, and the neutral connection is lost.

As shown in the figure, if the neutral bar in the main panel is unavailable, return current tries to flow back to the neutral bar. Since the neutral bar is bonded to the ground bar, the current’s only path back to the source (typically the transformer) is through the ground wire. This forms a circuit, allowing approximately 2.4 amps of fault current to flow. The light bulb may still emit a dim glow.

This 2.4-amp fault current is well below the breaker’s 15-amp rating, so it does not trip. Consequently, the circuit presents a shock hazard, as all metal components—including equipment enclosures, metal raceways, and the metallic bodies of connected devices—become energized with approximately 72V AC.

Now, consider another scenario where the neutral is lost and the hot wire contacts the metallic body of the device, creating a "double fault." In this case, the light is off due to the absence of load resistance. As shown in the figure, a fault current of approximately 4 amps flows through the ground conductor back to the source.

Again, all metal components in the circuit become energized at 120V AC. This 4-amp fault current remains below the breaker’s 15-amp threshold, so the breaker does not trip. If an operator touches the equipment enclosure, metal raceway, or device’s metallic body, they risk a severe electric shock.

To mitigate these hazards, a GFCI (Ground Fault Circuit Interrupter) breaker is recommended over a standard breaker. GFCI breakers are engineered to detect ground faults and trip in dangerous scenarios—including those caused by a broken neutral—ensuring safer operation.

Give a tip and encourage the author!

Recommended

Rockwill Powers Cambodia’s Battambang Solar-Storage Project
The Battambang Conch PV + Energy Storage Power Station in Cambodia has successfully completed its grid-connected trial operation. The project utilized medium-voltage switchgear supplied by Rockwill Intelligent Electric Co., Ltd. Despite numerous challenges—including an extremely tight delivery schedule—Rockwill Intelligent delivered high-quality products and exceptional service throughout project execution, earning consistent praise from the client.Located in Battambang, Cambodia, the Battambang
12/24/2025
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Application of Auto-Reclosing Residual Current Protective Devices in Lightning Protection for Communication Power Supplies
1. Power Interruption Problems Caused by RCD False Tripping During Lightning StrikesA typical communication power supply circuit is shown in Figure 1. A residual current device (RCD) is installed at the power supply input terminal. The RCD primarily provides protection against electrical equipment leakage currents to ensure personal safety, while surge protective devices (SPDs) are installed on power supply branches to protect against lightning intrusions. When lightning strikes occur, the senso
12/15/2025
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.