Why Doesn’t a Standard Breaker Protract Against Ground Faults?

Edwiin
05/16/2025

A broken neutral in a circuit with a standard breaker poses a shock hazard because the breaker does not monitor or protect the neutral wire. The internal mechanism of a standard breaker is not designed to detect ground-fault currents during operation. Standard circuit breakers are engineered to protect against overloads and short circuits, not ground faults.

Standard breakers monitor current in the hot wire and trip if the current exceeds the breaker’s rating—typically due to an overload or short circuit. However, with a broken neutral, fault current may return to the source through the ground wire. This occurs because the ground and neutral terminal bars are bonded in the main panel.

Consequently, a current lower than the breaker’s rated capacity can flow through the circuit in an unintended path. Since no excessive current travels through the hot wire, the breaker does not detect a fault and remains closed. As a result, parts of the circuit stay energized, creating a hidden shock risk that the breaker does not address.

The most common faults in an electric circuit are as follows:
Overloads and Short Circuits

Standard breakers react to excessive current caused by overloads or direct short circuits (high-current faults where current flows directly from hot to neutral or hot to hot). These conditions create a current surge, which the breaker detects and trips to prevent damage.
Ground Faults
A ground fault occurs when current leaks from the hot wire to a grounded surface, bypassing the neutral wire (e.g., due to a broken neutral or a live wire contacting a metal appliance case or wet surface). Ground faults may not generate the high current surges required to trip a standard breaker, especially if only a small amount of current leaks to ground. This leakage can create severe shock hazards without reaching the breaker’s trip threshold.
How Does a Standard Breaker Respond to a Short Circuit or Ground Fault?
Let’s examine how a standard breaker behaves and reacts to short circuits or ground faults in a circuit, as illustrated below.
Consider this example: In a 120V/240V main panel, a lighting circuit is controlled and protected by a 15-amp standard breaker on a 120V supply, and the neutral connection is lost.
As shown in the figure, if the neutral bar in the main panel is unavailable, return current tries to flow back to the neutral bar. Since the neutral bar is bonded to the ground bar, the current’s only path back to the source (typically the transformer) is through the ground wire. This forms a circuit, allowing approximately 2.4 amps of fault current to flow. The light bulb may still emit a dim glow.
This 2.4-amp fault current is well below the breaker’s 15-amp rating, so it does not trip. Consequently, the circuit presents a shock hazard, as all metal components—including equipment enclosures, metal raceways, and the metallic bodies of connected devices—become energized with approximately 72V AC.
Now, consider another scenario where the neutral is lost and the hot wire contacts the metallic body of the device, creating a "double fault." In this case, the light is off due to the absence of load resistance. As shown in the figure, a fault current of approximately 4 amps flows through the ground conductor back to the source.
Again, all metal components in the circuit become energized at 120V AC. This 4-amp fault current remains below the breaker’s 15-amp threshold, so the breaker does not trip. If an operator touches the equipment enclosure, metal raceway, or device’s metallic body, they risk a severe electric shock.
To mitigate these hazards, a GFCI (Ground Fault Circuit Interrupter) breaker is recommended over a standard breaker. GFCI breakers are engineered to detect ground faults and trip in dangerous scenarios—including those caused by a broken neutral—ensuring safer operation.
Edwiin

Analysis of the Technical Characteristics of Online Monitoring for Medium-Voltage Switchgear Status
Analysis of the Technical Characteristics of Online Monitoring for Medium-Voltage Switchgear Status
With the increasing complexity of power system operation environment and the deepening of power system reform, traditional power grids are accelerating the transformation to smart grids. The goal of equipment condition-based maintenance is achieved through real-time perception of equipment status by new sensors, reliable communication via modern network technology, and effective monitoring by background expert systems.I. Analysis of Condition-based Maintenance StrategyCondition-based Maintenance
Oliver Watts
06/11/2025
What is the current application status and development trend of medium-voltage switchgear?
What is the current application status and development trend of medium-voltage switchgear?
With the accelerated automation of power equipment, various medium-voltage switchgear have emerged in the market. Classified by insulation media, they are mainly divided into air-insulated, SF₆ gas-insulated and solid-insulated types, each with its own advantages and disadvantages: solid insulation offers good performance but poor environmental friendliness, SF₆ features excellent arc extinguishing capability but is a greenhouse gas, and air insulation has high cost-performance but larger volume
Echo
06/11/2025
What components make up the design of medium-voltage ring network distribution switchgear?
What components make up the design of medium-voltage ring network distribution switchgear?
As an expert who has been deeply engaged in the field of power system design for many years, I have always paid attention to the technological evolution and application practice of medium-voltage ring main distribution equipment. As a core electrical device in the secondary distribution link of the power system, the design and performance of such equipment are directly related to the safe and stable operation of the power supply network. The following is a professional analysis of the key design
Dyson
06/11/2025
What aspects should be paid attention to when installing medium-voltage switch cabinets during the initial stage of subway operation?
What aspects should be paid attention to when installing medium-voltage switch cabinets during the initial stage of subway operation?
1. Statistics on Common Faults of Medium-Voltage Switchgear in the Early Operation StageAs project participants, we found during the early operation of a new metro line: 21 sets of power supply equipment were put into use, with a total of 266 accident phenomena in the first year. Among them, 77 faults occurred in medium-voltage switchgear, accounting for 28.9%—significantly higher than faults in other equipment. Statistical analysis shows that major fault types include: protection device s
Felix Spark
06/11/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!