• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Solving the Contradiction in Arc Suppression Coil Grounding: Damping Resistor Applications and Tuning Strategies

Edwiin
Edwiin
Field: Power switch
China

Contradiction Points

In automatic tracking arc suppression coils, the adjustment precision is high, the residual current is small, and the operation is close to the resonance point.

In an automatic tracking arc suppression coil grounding system, two factors must be considered:

  • Under normal operating conditions, the long-term voltage displacement of the neutral point should not exceed 15% of the system's nominal phase voltage;

  • In the case of a ground fault, the grounding residual current should be small to facilitate arc extinction.

As the tuning requirements for an arc suppression coil grounding system, it is necessary to ensure that the neutral point displacement voltage does not exceed 15% of the rated phase voltage during normal operation, while also making the detuning degree as small as possible. This is obviously contradictory.

Solution Points

Currently, a damping resistor is connected to the circuit of the automatic compensation arc suppression coil to resolve this contradiction.

During normal operation of the power grid, due to the presence of the damping resistor, the damping rate d of the resonant circuit increases significantly. Even if the detuning degree is 0 at this time, the neutral point displacement voltage can basically be controlled within the range specified by regulations.

When a ground fault occurs in the power grid, the damping resistor is short-circuited, so that the grounding residual current can be well compensated, basically resolving the contradiction between small grounding residual current and excessive neutral point displacement voltage beyond the specified range.

To prevent series resonance overvoltage, a damping resistor is added to the arc suppression coil grounding circuit to suppress the generation of resonance overvoltage, ensuring that the neutral point displacement voltage does not exceed 15% of the phase voltage during normal operation of the system.

Analysis Points

During normal operation of the power grid, the zero-sequence equivalent circuit of the power grid grounded via an arc suppression coil is a series resonant circuit, as shown in the following figure. In the figure, L and gₗ are the inductance and equivalent conductance of the arc suppression coil; C and g are the per-phase-to-ground capacitance and leakage conductance of the power grid; U₀₀ is the asymmetric voltage.

The neutral point displacement voltage derived from the above figure is:

To meet the requirements of regulations, the method of increasing the detuning degree ν to keep the system away from the resonance point is often adopted. However, as can be seen from the above formula, besides increasing the detuning degree ν, the method of increasing the damping rate d can also be used. Connecting a damping resistor in parallel or in series with the arc suppression coil aims to increase the damping rate of the power grid, thereby reducing the neutral point displacement voltage U0. When a ground fault occurs in the power grid, short-circuiting the damping resistor allows the ground residual current to be well compensated.

Key Points for Attention

To add a damping resistor, the forms of connecting the damping resistor in series with the arc suppression coil circuit or in parallel on the secondary side of the arc suppression coil can be adopted. When a single-phase ground fault occurs in the system, the neutral point voltage rises and the neutral point current increases. When the current exceeds the set value, the damping resistor should be quickly short-circuited to avoid burning it out. When the system returns to normal, the short-circuit point of the damping resistor should be disconnected in a timely manner, so that the damping resistor is normally connected in series to the arc suppression coil circuit again. Otherwise, the system may experience resonance overvoltage due to the loss of the damping resistor.

Give a tip and encourage the author!
Recommended
What Are the Types of Reactors? Key Roles in Power Systems
What Are the Types of Reactors? Key Roles in Power Systems
Reactor (Inductor): Definition and TypesA reactor, also known as an inductor, generates a magnetic field within the surrounding space when current flows through a conductor. Therefore, any current-carrying conductor inherently possesses inductance. However, the inductance of a straight conductor is small and produces a weak magnetic field. Practical reactors are constructed by winding the conductor into a solenoid shape, known as an air-core reactor. To further increase inductance, a ferromagnet
James
10/23/2025
35kV Distribution Line Single-Phase Ground Fault Handling
35kV Distribution Line Single-Phase Ground Fault Handling
Distribution Lines: A Key Component of Power SystemsDistribution lines are a major component of power systems. On the same voltage-level busbar, multiple distribution lines (for input or output) are connected, each with numerous branches arranged radially and linked to distribution transformers. After being stepped down to low voltage by these transformers, electricity is supplied to a wide range of end users. In such distribution networks, faults such as phase-to-phase short circuits, overcurre
Encyclopedia
10/23/2025
On-Line Testing for Surge Arresters Below 110kV: Safe and Efficient
On-Line Testing for Surge Arresters Below 110kV: Safe and Efficient
An On-Line Testing Method for Surge Arresters at 110kV and BelowIn power systems, surge arresters are critical components that protect equipment from lightning overvoltage. For installations at 110kV and below—such as 35kV or 10kV substations—an on-line testing method effectively avoids the economic losses associated with power outages. The core of this method lies in using online monitoring technology to evaluate arrester performance without interrupting system operation.The test principle is b
Oliver Watts
10/23/2025
Why Does MVDC Grounding Cause System Faults?
Why Does MVDC Grounding Cause System Faults?
Analysis and Handling of DC System Grounding Faults in SubstationsWhen a DC system grounding fault occurs, it can be classified as single-point grounding, multi-point grounding, loop grounding, or reduced insulation. Single-point grounding is further divided into positive-pole and negative-pole grounding. Positive-pole grounding may cause misoperation of protection and automatic devices, while negative-pole grounding may lead to failure to operate (e.g., relay protection or tripping devices). On
Felix Spark
10/23/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.