IEC61850 model for GIS with Non Conventional Instrument Transformers (NCIT)

Edwiin
Edwiin
Field: Power switch
China

IEC 61850 Standards and NCIT - Related Communication in GIS

The IEC 61850 8 - 1 standard is specifically applicable to station bus communication, providing a framework for data exchange and interoperability within substation automation systems. On the other hand, the IEC 61850 9 - 2 LE standard is directly relevant to the communication of Non - Contact Inductive Transducer (NCIT) sensors.

Ethernet optical communication drivers play a crucial role in this setup. Their significance stems from the utilization of glass core fiber optics as the physical transmission medium. Fiber optics offer advantages such as high - speed data transfer, immunity to electromagnetic interference, and long - distance communication capabilities, making these drivers essential for reliable and efficient communication.

Due to the inherently low - level output signals from an NCIT metering element, the presence of a "Primary Converter" (PC) in close proximity is indispensable. The PC is an electronic device equipped with several key functions. It incorporates signal filtering through a low - pass filter to eliminate unwanted high - frequency noise, digitizes the signal using a Controller Area Network (CAN) interface, and performs necessary signal processing. These operations ensure that the raw signals from the NCIT are in a suitable form for further transmission and analysis.

The computational capabilities of the PC are harnessed to communicate with a device known as the Merging Unit (MU) via a proprietary protocol. The MU serves as a central hub, aggregating inputs from multiple PCs. It is equipped with multiple output ports, which are designed to enable communication with various pieces of equipment, including protection relays, bay controllers, and metering devices. By distributing the processed measurements to these different systems, the MU facilitates seamless integration and coordinated operation within the overall electrical infrastructure.

To achieve optimal metering accuracy, it is imperative to match the sensitivity level of the metering element with the background noise level of the printed circuit board. Minimizing the background noise to the lowest possible level ensures that the metering element can accurately detect and measure electrical quantities without being affected by spurious signals.

Figure [1] illustrates the IEC 61850 communication protocol in conjunction with NCIT sensors for Gas Insulated Substations (GIS). This visual representation provides a comprehensive overview of how the various components interact and communicate, highlighting the integration of standards - based communication and specialized sensor technology to enhance the performance, reliability, and efficiency of GIS - based electrical systems.

Give a tip and encourage the author!
Recommended
Top 5 Critical Process Controls for GIS Installation & Commissioning
Top 5 Critical Process Controls for GIS Installation & Commissioning
This paper briefly outlines the advantages and technical characteristics of GIS (Gas-Insulated Switchgear) equipment, and elaborates on several critical quality control points and process control measures during on-site installation. It emphasizes that on-site withstand voltage tests can only partially reflect the overall quality and installation workmanship of GIS equipment. Only by strengthening comprehensive quality control throughout the entire installation process—especially in key areas su
James
10/29/2025
Home Outlet Grounding Test: 3 Simple Methods
Home Outlet Grounding Test: 3 Simple Methods
Purpose of Grounding System Functional Grounding (Working Grounding):In power systems, grounding is required for normal operation, such as neutral point grounding. This type of grounding is known as working grounding. Protective Grounding:The metal enclosures of electrical equipment may become energized due to insulation failure. To prevent electric shock hazards to personnel, grounding is provided and is referred to as protective grounding. Overvoltage Protection Grounding:Grounding is installe
Oliver Watts
10/29/2025
Complete Guide to Circuit Breaker Selection and Setting Calculation
Complete Guide to Circuit Breaker Selection and Setting Calculation
How to Select and Set Circuit Breakers1. Types of Circuit Breakers1.1 Air Circuit Breaker (ACB)Also known as a molded frame or universal circuit breaker, all components are mounted within an insulated metal frame. It is typically open-type, allowing easy replacement of contacts and parts, and can be equipped with various accessories. ACBs are commonly used as main power supply switches. Overcurrent trip units include electromagnetic, electronic, and intelligent types. They provide four-stage pro
Echo
10/28/2025
Operation and Fault Handling of High and Low Voltage Power Distribution Systems
Operation and Fault Handling of High and Low Voltage Power Distribution Systems
Basic Composition and Function of Circuit Breaker Failure ProtectionCircuit breaker failure protection refers to a protective scheme that operates when the relay protection of a faulty electrical device issues a trip command but the circuit breaker fails to operate. It uses the protection trip signal from the faulty equipment and the current measurement from the failed breaker to determine breaker failure. The protection can then isolate other relevant breakers within the same substation in a sh