Why Does the Secondary Insulation of Outdoor Current Transformers Drop?

Felix Spark
Felix Spark
Field: Failure and maintenance
China

I'm Felix, a 15-Year Veteran in the CT Industry, Sharing What You Need to Watch Out For

Hi everyone, I'm Felix, and I've been working with current transformers (CTs) for over 15 years. Today, let’s talk about why the secondary insulation of outdoor CTs sometimes drops, and what you can do to prevent it.

Common Causes:
1. Moisture Ingress — Poor Sealing is the Biggest Problem!

Outdoor CTs are constantly exposed to wind and rain. If the sealing isn't tight enough, moisture can get inside and seriously damage insulation performance.

In coastal areas or humid environments, this problem gets worse — salt mist and dampness can cause mold, corrosion, or even short circuits.

Example: I once found water droplets inside a CT during a site inspection. It turned out the sealing ring had aged and allowed rainwater to slowly seep in.

2. Dust Buildup — Dirt Can Conduct Electricity Too!

Dust, salt particles, and other pollutants can stick to the surface or internal terminals of the CT. When combined with humidity, they form conductive paths that reduce insulation resistance.

Regular cleaning is key — especially in heavily polluted areas. Don’t wait until there’s a problem to wipe things down.

3. Material Aging — Everything Gets Old Eventually

No material lasts forever, especially when exposed to the elements.

UV exposure, extreme temperatures, and chemical corrosion all speed up aging. Over time, materials like silicone rubber or epoxy resin may crack, harden, or lose their insulating properties.

How to check for aging:

  • Look for cracks, discoloration, or brittleness.

  • Monitor if insulation values drop year after year.

  • Track historical test data for sudden changes.

4. Improper Installation — Problems Start Right After Setup

If installation is rushed or done carelessly, problems will follow.

Examples include:

  • Poor grounding;

  • Loose wiring;

  • Installing in places prone to water accumulation;

  • Forgetting or improperly installing waterproof seals.

These issues might not show up immediately, but over time they lead to contact failure, moisture ingress, or partial discharge — all bad news for insulation.

Real-life example: Once, I found unstable insulation readings due to a poorly installed waterproof seal. The technician had just loosely wrapped it instead of pressing it properly — which let rainwater in and caused an insulation breakdown.

5. Lack of Maintenance — Ignoring Care Is Like Slow Self-Damage

Many sites install CTs and forget them until something breaks. But like a car, CTs need regular maintenance.

This includes:

  • Cleaning terminals;

  • Checking seals;

  • Measuring insulation;

  • Replacing worn parts.

Ignoring these basic steps means small issues become big ones — and fixing them later costs more.

How to Detect and Prevent These Issues?

Here are some practical tips:

  • Measure insulation resistance regularly:Use a 2500V megohmmeter to check secondary-to-ground and primary-to-secondary insulation. Most manufacturers recommend values above 1000 MΩ.

  • Check the appearance:Look for cracks, rust, deformation, or signs of moisture. Any of these could signal deeper issues.

  • Improve environmental protection:In high-humidity or salty environments, consider adding space heaters or using CTs with higher IP ratings.

  • Schedule regular maintenance and cleaning:At least once a year, inspect and clean your CTs — replace old seals, tighten connections, and update worn components.

As someone with 15 years of experience in the CT industry, here's my takeaway:

“Insulation problems in outdoor CTs don’t happen suddenly — they build up over time.”

With proper installation, regular checks, and good maintenance habits, most issues can be caught early and avoided altogether.

If you're dealing with insulation drops, unusual data, or unsure how to proceed, feel free to reach out. I’m happy to share more real-world experiences and solutions.

May every CT run safely and reliably, protecting the power grid with precision!

— Felix

Give a tip and encourage the author!
Recommended
10kV RMU Common Faults & Solutions Guide
10kV RMU Common Faults & Solutions Guide
Application Issues and Handling Measures for 10kV Ring Main Units (RMUs)The 10kV ring main unit (RMU) is a common electrical distribution device in urban power distribution networks, primarily used for medium-voltage power supply and distribution. During actual operation, various issues may arise. Below are common problems and corresponding corrective measures.I. Electrical Faults Internal Short Circuit or Poor WiringA short circuit or loose connection inside the RMU can lead to abnormal operati
Echo
10/20/2025
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breakers: Classification and Fault DiagnosisHigh-voltage circuit breakers are critical protective devices in power systems. They rapidly interrupt current when a fault occurs, preventing damage to equipment from overloads or short circuits. However, due to long-term operation and other factors, circuit breakers may develop faults that require timely diagnosis and troubleshooting.I. Classification of High-Voltage Circuit Breakers1. By Installation Location: Indoor-type: Insta
Felix Spark
10/20/2025
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation! Never install the transformer too far away—avoid placing it in remote mountains or wilderness. Excessive distance not only wastes cables and increases line losses, but also makes management and maintenance difficult. Never choose transformer capacity arbitrarily. Selecting the right capacity is essential. If the capacity is too small, the transformer may be overloaded and easily damaged—overloading beyond 30% should not exceed two hours
James
10/20/2025
How to Maintain Dry-Type Transformers Safely?
How to Maintain Dry-Type Transformers Safely?
Maintenance Procedures for Dry-Type Transformers Put the standby transformer into operation, open the low-voltage side circuit breaker of the transformer to be maintained, remove the control power fuse, and hang a "DO NOT CLOSE" sign on the switch handle. Open the high-voltage side circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the high-voltage cabinet, and hang a "DO NOT CLOSE" sign on the switch handle. For dry-type trans
Felix Spark
10/20/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.