Development of an Outdoor Integrated Low - Voltage Current Transformer

Dyson
Dyson
Field: Electrical Standards
China

In power grid construction, line losses reflect planning, design, and operation management. They’re key for evaluating power systems. For refined low - voltage transformer area line loss management, accurate line loss counting is critical. So, solidifying basic data, ensuring data accuracy, and proper original data collection matter for analysis. We must also optimize factors affecting collection accuracy, make preventive measures, and boost refined line loss management.

1 Current Status of Refined Line Loss Collection in Low - voltage Transformer Areas

Since 2013, a municipal power company has advanced full - coverage refined line loss work. After over 6 years, current transformers for electricity collection, damaged by nature, see protective shields detach. Exposed to the environment, they crack under sunlight, risking further damage.

Some transformers for refined line loss collection in low - voltage areas are installed on suspended cables. High winds make them swing, and background data shows total meter data is wind - affected. Thus, improving and updating these transformers is needed to remove hazards and enhance management.

Currently, silicone rubber shields are used on local low - voltage transformer area current transformers for UV and rain protection. But different shield fixing methods cause some to detach over time. Also, transformers under fuse boxes on separate supports, though wind - resistant, let water in from the bottom, rusting cores and affecting accuracy.

2 Ideas for Developing Electricity Collection Devices

R & D uses mature, reliable equipment and components, leveraging proven solutions. Key research:

2.1 Special - purpose Current Transformer Design

Design a transformer for outdoor use, live - line installation (open structure), and cable - holding. Its split parts fix to the line pole cross - arm, meeting the local power company’s electrical parameter requirements for distribution transformer electricity collection box upgrades.

2.2 Puncture Power - taking Device Research

Develop a device to take power from the transformer’s bus cable for metering and control. It integrates with the transformer. Insulation between the cable puncture point and the transformer’s secondary winding must be 1.2 times that of general 3 kV (1 - minute power - frequency withstand voltage) low - voltage transformers. Insulation between the puncture point and the transformer’s support must also meet this standard.

The voltage from the puncture needle passes through a switch (integrated with the transformer) before being led out.

2.3 Environmental Adaptability Design

The device must be waterproof, moisture - proof, UV - resistant, work long - term at - 25℃ to 70℃, withstand level 12 typhoons and level 8 earthquakes, and have IP67 protection.

Sample Test Items

Samples undergo tests including:

  • Current transformer tests: accuracy, instrument security coefficient, withstand voltage, rain, and mechanical strength tests.

  • Puncture unit tests: conduction, impact, insulation resistance, DC resistance, temperature rise, and cable tension tests.

  • Overall device tests: mechanical impact, insulating shell heat resistance, and protection level tests.

3 Development of Outdoor Integrated Low - voltage Devices
3.1 Outdoor Integrated Low - voltage Current Transformer Design

As the core of the collection device, the transformer abandons the traditional circular design. Using a square body (fitting cement pole cross - arms), it fixes via screws, reducing wind - and vibration - induced accuracy impacts. Secondary leads use 2.5 mm² RV wires; the open structure allows live - line installation.

The core uses Nippon Steel ZW80 0.23 mm silicon steel sheets (separable, high initial permeability, low loss), meeting class 0.5S accuracy. The body is polycarbonate; the interior is epoxy - cast for stability and insulation.

3.2 Puncture Power - taking Unit Design

The puncture needle and switch are at the transformer’s bottom. The needle, perpendicular to the inner hole (pointing to its center), is telescopic (stroke ≥ 1/2 inner hole diameter, adjusted by screws, torque ≥ 1 N·m). Connected to the transformer’s switch, it leads out via 1.5 mm² RV wire. The switch is cast inside, with a silicone - sealed handle for a tight fit.

3.3 Waterproof, Moisture - proof, and UV - proof Design

The transformer body is epoxy - cast for full insulation and sealing. Grooves with silicone seals on split end faces prevent water/moisture ingress.

The switch is cast inside; the movable handle and lead roots are silicone - sealed/integrally cast, with no exposed live points.

Using polycarbonate and silicone rubber (proven UV - resistant, slow - aging, 30 + year service life).

4 Conclusion

The outdoor integrated low - voltage current transformer has a split open structure, enabling easy installation and live - line work. Its split parts fix to the cross - arm, holding cables tightly with strong tensile/shear resistance.

It integrates current/voltage signals (including power) for pole - mounted transformer area collection. A switch on the voltage lead - out meets personalized needs.

The telescopic puncture needle suits cables of varying thicknesses/insulation. With full insulation/sealing (IP67), it ensures reliability.

Currently split - phase (large volume), future optimization into a three - phase structure will adapt to more scenarios, improving power system refined line loss management.

Give a tip and encourage the author!
Recommended
Minimum Operating Voltage for Vacuum Circuit Breakers
Minimum Operating Voltage for Vacuum Circuit Breakers
Minimum Operating Voltage for Trip and Close Operations in Vacuum Circuit Breakers1. IntroductionWhen you hear the term "vacuum circuit breaker," it might sound unfamiliar. But if we say "circuit breaker" or "power switch," most people will know what it means. In fact, vacuum circuit breakers are key components in modern power systems, responsible for protecting circuits from damage. Today, let's explore an important concept — the minimum operating voltage for trip and close operations.Though it
Dyson
10/18/2025
Efficient Wind-PV Hybrid System Optimization with Storage
Efficient Wind-PV Hybrid System Optimization with Storage
1. Analysis of Wind and Solar Photovoltaic Power Generation CharacteristicsAnalyzing the characteristics of wind and solar photovoltaic (PV) power generation is fundamental to designing a complementary hybrid system. Statistical analysis of annual wind speed and solar irradiance data for a specific region reveals that wind resources exhibit seasonal variation, with higher wind speeds in winter and spring and lower speeds in summer and autumn. Wind power generation is proportional to the cube of
Dyson
10/15/2025
Wind-Solar Hybrid Powered IoT System for Real-Time Water Pipeline Monitoring
Wind-Solar Hybrid Powered IoT System for Real-Time Water Pipeline Monitoring
I. Current Status and Existing ProblemsCurrently, water supply companies have extensive networks of water pipelines laid underground across urban and rural areas. Real-time monitoring of pipeline operation data is essential for effective command and control of water production and distribution. As a result, numerous data monitoring stations must be established along the pipelines. However, stable and reliable power sources near these pipelines are rarely available. Even when power is accessible,
Dyson
10/14/2025
How to Build an AGV-Based Intelligent Warehouse System
How to Build an AGV-Based Intelligent Warehouse System
Intelligent Warehouse Logistics System Based on AGVWith the rapid development of the logistics industry, growing land scarcity, and rising labor costs, warehouses—serving as key logistics hubs—are facing significant challenges. As warehouses become larger, operational frequencies increase, information complexity grows, and order-picking tasks become more demanding, achieving low error rates and reduced labor costs while improving overall storage efficiency has become a primary goal for the wareh
Dyson
10/08/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.