Parallel Operation of Alternators

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Alternator Definition

An alternator is defined as an AC generator that induces EMF in a stationary wire using a rotating magnetic field, following Faraday’s law of induction.

Conditions for Parallel Operation

  • The phase sequence of the incoming machine’s voltage must match the bus bar’s voltage.

  • The RMS line voltage (terminal voltage) of the bus bar or already running machine and the incoming machine should be the same.

  • The phase angle of the two systems should be equal.

  • The frequency of the two terminal voltages (incoming machine and the bus bar) should be nearly the same. Large power transients will occur when frequencies are not nearly equal.

 Synchronizing Process

Synchronizing involves adjusting terminal voltages and checking phase sequences using a Synchroscope or three-lamp method.

Voltage and Frequency Matching

Ensure terminal voltages and frequencies are nearly identical to avoid power surges and equipment damage.

General Procedure for Paralleling Alternators

The figure below shows an alternator (generator 2) being paralleled with a running power system (generator 1). These two machines are about to synchronize for supplying power to a load. Generator 2 is about to parallel with the help of a switch, S1. This switch should never be closed without satisfying the above conditions.

9ca3324b8f5cd6d7ab25481d285249e8.jpeg

 To equalize terminal voltages, adjust the incoming machine’s terminal voltage by changing its field current. Use voltmeters to match it with the line voltage of the running system.

 There are two methods to check the phase sequence of the machines. They are as follows

  • First one is using a Synchroscope. It is not actually check the phase sequence but it is used to measure the difference in phase angles.

  • Second method is three lamp method (Figure 2). Here we can see three light bulbs are connected to the terminals of the switch, S1. Bulbs become bright if the phase difference is large. Bulbs become dim if the phase difference is small. The bulbs will show dim and bright all together if phase sequence is the same. The bulbs will get bright in progression if the phase sequence is opposite. This phase sequence can be made equal by swapping the connections on any two phases on one of the generators.

c2ba5659db6dd0fb9babf25d41bc95ac.jpeg

Next, check and verify that the frequencies of the incoming and running systems are nearly the same. This can be done by observing the dimming and brightening of the lamps.

When the frequencies are nearly equal, the two voltages (incoming alternator and running system) will alter the phase gradually. These changes can be observed and the switch, S1 can be made closed when the phase angles are equal.

Advantages of Parallel Operation

  • When there is maintenance or an inspection, one machine can be taken out from service and the other alternators can keep up for the continuity of supply.

  • Load supply can be increased.

  • During light loads, more than one alternator can be shut down while the other will operate in nearly full load.

  • High efficiency.

  • The operating cost is reduced.

  • Ensures the protection of supply and enables cost-effective generation.

  • The generation cost is reduced.

  • Breaking down of a generator does not cause any interruption in the supply.

  • Reliability of the whole power system increases.

Give a tip and encourage the author!
Recommended
In-Depth Analysis of Fault Protection Mechanisms for Generator Circuit Breakers
In-Depth Analysis of Fault Protection Mechanisms for Generator Circuit Breakers
1.Introduction1.1 Basic Function and Background of GCBThe Generator Circuit Breaker (GCB), as the critical node connecting the generator to the step-up transformer, is responsible for interrupting current under both normal and fault conditions. Unlike conventional substation circuit breakers, the GCB directly withstands the massive short-circuit current from the generator, with rated short-circuit breaking currents reaching hundreds of kiloamperes. In large generating units, the reliable operati
Felix Spark
11/27/2025
Research and Practice of Intelligent Monitoring System for Generator Circuit Breaker
Research and Practice of Intelligent Monitoring System for Generator Circuit Breaker
The generator circuit breaker is a critical component in power systems, and its reliability directly affects the stable operation of the entire power system. Through research and practical application of intelligent monitoring systems, the real-time operational status of circuit breakers can be monitored, enabling early detection of potential faults and risks, thereby enhancing the overall reliability of the power system.Traditional circuit breaker maintenance primarily relies on periodic inspec
Edwiin
11/27/2025
Why Install GCB at Generator Outlets? 6 Core Benefits for Power Plant Operations
Why Install GCB at Generator Outlets? 6 Core Benefits for Power Plant Operations
1.Protects the GeneratorWhen asymmetric short circuits occur at the generator outlet or the unit bears unbalanced loads, the GCB can quickly isolate the fault to prevent generator damage. During unbalanced load operation, or internal/external asymmetric short circuits, twice the power frequency eddy current is induced on the rotor surface, causing additional heating in the rotor. Meanwhile, the alternating electromagnetic torque at twice the power frequency induces double-frequency vibration in
Echo
11/27/2025
Silent Diesel Generator Installation Guide: Key Steps & Critical Details for Efficiency
Silent Diesel Generator Installation Guide: Key Steps & Critical Details for Efficiency
In industrial production, emergency rescue, commercial buildings, and other scenarios, silent-canopy diesel generator sets serve as the “core backup” for stable power supply. The quality of on-site installation directly determines the unit’s operational efficiency, noise control performance, and service life; even minor oversights may lead to potential faults. Today, based on practical experience, we outline the complete standardized procedures and critical details for on-site installation of si
James
11/27/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.