Blocked Rotor Test of an Induction Motor

Edwiin
05/24/2025

The blocked - rotor test of an induction motor is analogous to the short - circuit test of a transformer. In this test, the motor's shaft is immobilized to prevent any rotation, and the rotor winding is short - circuited. For a slip - ring motor, the rotor winding is short - circuited via the slip rings. In the case of cage motors, the rotor bars are inherently short - circuited. This test is also referred to as the Locked Rotor Test. The circuit diagram for the blocked - rotor test is presented below:

A reduced voltage at a reduced frequency is supplied to the stator via a three - phase autotransformer, ensuring that the full - load rated current circulates in the stator. The blocked - rotor test yields the following three measurements:
  • Total power input during short - circuit Psc: This is the algebraic sum of the readings from the two wattmeters. The power input during the blocked - rotor test is equivalent to the combined copper losses of the stator and rotor for all three phases. Since a reduced voltage is applied to the stator, thereby preventing rotor rotation, core and mechanical losses can be disregarded.
  • Ammeter reading

  • Reading of the voltmeter

where cosϕ represents the power factor of the short - circuit. The equivalent resistance of the motor, referred to the stator side, is expressed by the following equation:

The equivalent impedance of the motor referred to the stator side is given by the equation shown below:

The equivalent reactance of the motor referred to the stator side is given by the equation shown below.

The blocked - rotor test is carried out under normal operating conditions, with the rotor current and frequency being in their typical states. Generally, for an induction motor, the slip typically ranges from 2% to 4%. When the stator frequency is 50 hertz under normal conditions, the resulting rotor frequency falls within the range of 1 to 2 hertz.
This test should be executed at a reduced frequency. To achieve accurate results, the blocked - rotor test is performed at a frequency that is 25% or less of the rated frequency. The leakage reactances at the rated frequency are derived based on the principle that reactance is proportional to frequency.
Nevertheless, for motors with a rating of less than 20 kilowatts, the influence of frequency is negligible, and the blocked - rotor test can be directly conducted at the rated frequency.
Edwiin

Generator Protection – Types of Faults & Protection Devices
Generator Protection – Types of Faults & Protection Devices
Common Generator Faults and Protection SystemsClassification of Generator FaultsGenerator faults are primarily categorized into internal and external types:Internal Faults: Arise from issues within generator components.External Faults: Stem from abnormal operating conditions or external network issues.Faults in prime movers (e.g., diesel engines, turbines) are mechanical in nature and defined during equipment design, though they must integrate with generator protections for tripping purposes.Typ
Edwiin
06/05/2025
Short Circuit Ratio of a Synchronous Machine
Short Circuit Ratio of a Synchronous Machine
The Short Circuit Ratio (SCR) of a Synchronous MachineThe Short Circuit Ratio (SCR) of a synchronous machine is defined as the ratio of the field current needed to generate rated voltage under open-circuit conditions to the field current required to sustain rated armature current during a short-circuit condition. For a three-phase synchronous machine, the SCR can be derived from its Open-Circuit Characteristic (O.C.C) at rated speed and Short-Circuit Characteristic (S.C.C), as illustrated in the
Edwiin
06/04/2025
Equivalent Circuit of a Transformer
Equivalent Circuit of a Transformer
The equivalent circuit diagram of any device can be extremely useful for predicting how the device will behave under different operating conditions. It is essentially a circuit - based depiction of the equations that describe the device's performance.The simplified equivalent circuit of a transformer is constructed by representing all of the transformer's parameters on either the secondary side or the primary side. The equivalent circuit diagram of the transformer is presented below:Let the equi
Edwiin
06/03/2025
Transformer On Load Condition
Transformer On Load Condition
Transformer Operation Under Load ConditionsWhen a transformer is under load, its secondary winding connects to a load, which can be resistive, inductive, or capacitive. A current I2 flows through the secondary winding, with its magnitude determined by the terminal voltageV2and load impedance. The phase angle between the secondary current and voltage depends on the load characteristics.Explanation of Transformer Load OperationThe operational behavior of a transformer under load is detailed as fol
Edwiin
06/03/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!