Short Circuit Ratio of a Synchronous Machine

06/04/2025

The Short Circuit Ratio (SCR) of a Synchronous Machine
The Short Circuit Ratio (SCR) of a synchronous machine is defined as the ratio of the field current needed to generate rated voltage under open-circuit conditions to the field current required to sustain rated armature current during a short-circuit condition. For a three-phase synchronous machine, the SCR can be derived from its Open-Circuit Characteristic (O.C.C) at rated speed and Short-Circuit Characteristic (S.C.C), as illustrated in the figure below:
From the above figure, the short circuit ratio is given by the equation shown below.
Since the triangles Oab and Ode are similar. Therefore,
Direct Axis Synchronous Reactance (Xd)
The direct axis synchronous reactance Xd is defined as the ratio of the open-circuit voltage corresponding to a specific field current to the armature short-circuit current under the same field current condition.
For a field current of magnitude Oa, the direct axis synchronous reactance (in ohms) is expressed by the following equation:
Relationship Between SCR and Synchronous Reactance
From equation (7), it is evident that the Short Circuit Ratio (SCR) equals the reciprocal of the per-unit direct axis synchronous reactance Xd. In a saturated magnetic circuit, the value of Xd is contingent upon the degree of magnetic saturation.
Significance of the Short Circuit Ratio (SCR)
The SCR is a critical parameter for synchronous machines, influencing their operational characteristics, physical dimensions, and cost. Key implications include:
  • Voltage Regulation Impact
    • Synchronous generators with lower SCR values exhibit more pronounced terminal voltage fluctuations with load changes. Maintaining constant terminal voltage requires wide-ranging adjustments to the field current If).
  • Stability Limitations
    • A smaller SCR corresponds to reduced synchronizing power, which is essential for maintaining synchronism. This results in a lower stability limit, meaning machines with low SCR are less stable when operating in parallel with other generators.
  • Trade-offs in Design
    • High-SCR machines offer superior voltage regulation and enhanced steady-state stability but entail higher armature short-circuit fault currents. Additionally, they influence machine size and cost due to design trade-offs.
The excitation voltage of a synchronous machine is described by the equation:
For the same value of Tph Excitation voltage is directly proportional to the field flux per pole.
The synchronous inductance is given as:
Relationship Between SCR and Air Gap
Thus, the Short Circuit Ratio (SCR) is directly proportional to the air gap reluctance or air gap length. Increasing the air gap length elevates the SCR, though this requires a higher field magnetomotive force (MMF) to maintain the same excitation voltage (). To increase the field MMF, either the field current or the number of field turns must be augmented, necessitating taller field poles and an enlarged machine diameter.
Impact on Machine Design
This leads to a key conclusion: a higher SCR inherently increases the size, weight, and cost of the synchronous machine.
Typical SCR Values by Machine Type
  • Cylindrical Rotor Machines: SCR ranges from 0.5 to 0.9.
  • Salient-Pole Machines: SCR falls between 1.0 and 1.5.
  • Synchronous Compensators: SCR is typically 0.4.
These values reflect the design trade-offs between stability, voltage regulation, and physical dimensions in different synchronous machine configurations.

Wenzhou Rockwell Transformer Co., Ltd. It is a high - tech enterprise integrating R & D, production, sales, and service. It focuses on the manufacturing of power transformers and supporting equipment, and is committed to providing efficient, reliable, and energy - saving power transmission and distribution solutions for global customers. We can offer: •Distribution transformers and substations •Outdoor switchgears and breakers(recloser) •Switchgears and it’s components (GIS, RMU, VCB, SF6 CB) Market and Service: We always take customers as the orientation and provide customized services according to their requirements. Our products are exported to the Middle East, Africa, Northern Europe, South America, and many other countries and regions. Drive the future of electricity with technological innovation and become a leading global supplier of intelligent power equipment.

Fault Analysis and Treatment of Oil-Immersed Transformers
Fault Analysis and Treatment of Oil-Immersed Transformers
Oil Leakage at Welded JointsOil leakage at welded joints primarily stems from poor welding quality, such as incomplete or detached welds, and defects like pinholes and gas pores. Although oil-immersed transformers are initially coated with solder and paint during manufacturing, potentially masking these issues temporarily, the defects tend to surface during operation. Additionally, electromagnetic vibration can cause weld cracks, leading to oil leakage.To resolve such leaks, the first critical s
08/29/2025
What losses occur during operation of the transformer? How to reduce losses?
What losses occur during operation of the transformer? How to reduce losses?
Transformers experience various types of losses during operation, primarily categorized into two main types: copper losses and iron losses.Copper LossesCopper losses, also known as I²R losses, are caused by the electrical resistance of the transformer windings—typically made of copper. As current flows through the windings, energy is dissipated in the form of heat. These losses are proportional to the square of the load current (I²R), meaning they increase significantly with high
Rockwell
08/29/2025
Transformer Detection, Testing, Maintenance and Servicing
Transformer Detection, Testing, Maintenance and Servicing
Transformer testing, inspection, and maintenance are essential tasks to ensure normal operation and extend the service life of transformers. Below are some recommended steps:Visual Inspection: Regularly inspect the transformer's exterior, including the enclosure, cooling system, and oil tank. Ensure the enclosure is intact, free from corrosion, damage, or leakage.Insulation Resistance Testing: Use an insulation resistance tester to check the transformer's insulation system. Verify that the insul
Vziman
08/29/2025
Preventive Detection and Testing of Transformers
Preventive Detection and Testing of Transformers
I. DC Resistance Test of Transformer Primary and Secondary Windings:The DC resistance of transformer primary and secondary windings can be measured using the four-wire (Kelvin) method, which is based on principles related to accurate resistance measurement.In the four-wire method, two test leads are connected to both ends of the winding under test, while the other two leads are connected to adjacent winding terminals. An AC power source is then applied to the two leads connected to the adjacent
Rockwell
08/28/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!