Short-Circuit Fault Analysis of 10kV Puffer-Type Load Switch

Felix Spark
Felix Spark
Field: Failure and maintenance
China

1. Fault Overview

In June 2013, a fault occurred in a high - voltage switchgear in operation in a certain urban area, causing a 10kV line to trip. On - site investigation revealed that the faulty switchgear was a pneumatic ring - network high - voltage load switchgear (HXGN2 - 10 type), and the fault characteristic was a three - phase arc short circuit. After isolating the fault and restoring power supply to users, it should be noted that the same type of switchgear in this area, which was put into operation between 1999 and 2000 (with an operation period of more than 12 years, a designed rated current of 630A, and an actual operating current mostly ≤ 300A), has experienced similar faults many times, posing a threat to the reliable operation of the power grid.

2. Working Principle of Pneumatic Load Switches

The pneumatic ring - network cabinet is named for being equipped with a pneumatic load switch. Its movable contact rod also functions as an air cylinder —— the hollow structure contains a sealed “piston”, which is driven by the main shaft to realize the linear movement of closing and opening. When opening, the piston quickly compresses the air in the movable contact rod (air cylinder), and the compressed air is blown towards the arc generated by the separation of the arc - extinguishing contacts through the arc - resistant plastic nozzle at the top, extinguishing the arc by stretching it; the high - speed air flow quickly restores the insulation strength of the medium at the break, preventing the arc from reigniting.

Due to the limited ability of the switch to break fault currents (only applicable to systems below 35kV ), a design scheme of “separating the conductive element from the arc - igniting element” is adopted:

  • Conductive element: Red copper plum - shaped contact fingers + conductive rod, responsible for current transmission;

  • Arc - igniting element: Copper - tungsten alloy arc - igniting rod + arc - igniting ring, specially for arc ignition and extinction.

When opening, the outer surface of the movable contact rod first separates from the static contact fingers, and then the arc - igniting ring separates from the arc - igniting rod. The arc is restricted to burn between the arc - igniting components, avoiding damage to the main contacts; the movable contact rod and the lower terminal are connected by plum - shaped contact fingers to ensure electrical conduction.

3. In - depth Analysis of Fault Causes
(1) Preliminary Investigation (External Factors)

The designed rated current of this type of switch is 630A, but the dispatching data shows that the operating current of the outgoing switch of the substation is 283A, and the theoretical current passing through the switchgear on the way is ≤ 283A. Combined with the on - site environment (sunny weather, no pollution on the cabinet body), external factors such as over - current, over - voltage, and pollution flashover can be directly excluded, and the fault is attributed to the defects of the switchgear itself.

(2) Disassembly and Test Verification

After disassembling the faulty cabinet, it is initially speculated that “poor contact between the movable and static contacts leads to overheating and burning”, but a definite conclusion cannot be drawn due to severe damage to the cabinet. Therefore, sampling detection is carried out on the same type of switchgear in operation:

  • Withstand voltage and loop resistance: The withstand voltage level is qualified, and the loop resistance is 114μΩ (complying with technical regulations );

  • Temperature rise test: The 30 - minute current - rising test data (Table 1 ) shows that the temperature rise reaches 84.2℃ at 400A and as high as 133.1℃ at 630A, far exceeding the national standard for stable judgment of “temperature rise ≤ 1K within 1 hour or ≤ 2K within 3 hours”.

(3) Identification of Root Causes

Comprehensive testing and structural analysis show that the fault originates from the failure of the contact system, specifically manifested as:

  • Insufficient spring force: It cannot effectively contract the plum - shaped contact fingers, resulting in the deterioration of the “surface contact” between the contact fingers and the movable contact rod into “line contact”, and a sharp reduction in the contact area;

  • Defects in processing precision: Insufficient precision in the arc surface/planar processing of the plum - shaped contact fingers aggravates poor contact;

  • Oxidation vicious cycle: The contact fingers and the movable contact rod are exposed to the air, and oxidation leads to an increase in contact resistance → increased heating → further attenuation of spring tension → worse contact effect, eventually causing air ionization arc short circuit and line tripping.

4. Equipment Transformation and Optimization Solutions
(1) Process Upgrade: Precise Control of Contact Quality

Aiming at the core problem of “poor contact”, improvements are made from the material and processing ends:

  • Spring selection: Adopt springs with high fatigue resistance to ensure stable spring force within the design life (including the condition of making and breaking the rated current ), avoiding contact problems caused by spring failure;

  • Contact finger processing: Strictly control the processing precision of the arc surface and plane of the plum - shaped contact fingers to ensure complete fitting with the cylindrical arc surface of the movable contact rod, eliminating the hidden dangers of line contact/point contact, and ensuring the current - carrying capacity and temperature rise compliance of the contacts.

(2) Design Optimization: Full - process Condition Monitoring

Integrate the “online monitoring” function into the cabinet structure design to realize visual status:

  • Temperature measurement window and probe: Set up a convenient temperature measurement window, install a temperature probe at the static contact, and display the temperature of the contact part inside the cabinet in real - time through the panel instrument;

  • Data storage and early warning: Configure storage equipment to record operating data. Even if the equipment ages, abnormal situations can be identified in advance through data analysis, triggering the replacement and maintenance process, shifting from passive repair to active operation and maintenance.

(3) Operation and Maintenance Strengthening: Dynamic Defect Treatment

For the equipment in operation, optimize the operation and maintenance methods:

  • Observation window transformation: Change the fixed observation window to a movable one to facilitate temperature monitoring inside the cabinet;

  • Normalization of partial discharge testing: Carry out partial discharge testing of the switchgear during peak load periods to capture insulation defects in advance and avoid the expansion of faults.

5. Application Scenarios and Development Suggestions

With the increase in electricity consumption, the main lines of the distribution network are upgraded to large - cross - section cables of 300 - 400㎡, and the capacity of substations continues to grow. The shortcomings of insufficient breaking capacity and vulnerable contacts of pneumatic switchgear are becoming increasingly prominent. It is recommended that:

  • Scenario adjustment: Withdraw from line ring - network applications and switch to high - voltage power distribution in terminal transformer areas (with a transformer capacity ≤ 630kVA ), utilizing its advantages of “simple structure and low cost”;

  • Technology iteration: For line ring - network scenarios, give priority to selecting switchgear with higher reliability and stronger breaking capacity (such as vacuum load switches ) to meet the requirements of distribution network automation and high reliability;

  • Value continuation: After the transformation of “process upgrade + online monitoring”, the pneumatic load switchgear can continue to serve terminal load scenarios and exert its residual value.

Give a tip and encourage the author!
Recommended
10kV RMU Common Faults & Solutions Guide
10kV RMU Common Faults & Solutions Guide
Application Issues and Handling Measures for 10kV Ring Main Units (RMUs)The 10kV ring main unit (RMU) is a common electrical distribution device in urban power distribution networks, primarily used for medium-voltage power supply and distribution. During actual operation, various issues may arise. Below are common problems and corresponding corrective measures.I. Electrical Faults Internal Short Circuit or Poor WiringA short circuit or loose connection inside the RMU can lead to abnormal operati
Echo
10/20/2025
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breakers: Classification and Fault DiagnosisHigh-voltage circuit breakers are critical protective devices in power systems. They rapidly interrupt current when a fault occurs, preventing damage to equipment from overloads or short circuits. However, due to long-term operation and other factors, circuit breakers may develop faults that require timely diagnosis and troubleshooting.I. Classification of High-Voltage Circuit Breakers1. By Installation Location: Indoor-type: Insta
Felix Spark
10/20/2025
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation! Never install the transformer too far away—avoid placing it in remote mountains or wilderness. Excessive distance not only wastes cables and increases line losses, but also makes management and maintenance difficult. Never choose transformer capacity arbitrarily. Selecting the right capacity is essential. If the capacity is too small, the transformer may be overloaded and easily damaged—overloading beyond 30% should not exceed two hours
James
10/20/2025
How to Maintain Dry-Type Transformers Safely?
How to Maintain Dry-Type Transformers Safely?
Maintenance Procedures for Dry-Type Transformers Put the standby transformer into operation, open the low-voltage side circuit breaker of the transformer to be maintained, remove the control power fuse, and hang a "DO NOT CLOSE" sign on the switch handle. Open the high-voltage side circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the high-voltage cabinet, and hang a "DO NOT CLOSE" sign on the switch handle. For dry-type trans
Felix Spark
10/20/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.