Puffer interruption in gas HV CB

Edwiin
12/28/2024

Detailed Explanation of the Arc Quenching Process in a Puffer-Type SF6 Circuit Breaker

In a puffer-type SF6 circuit breaker, the arc quenching process is a critical mechanism that ensures the reliable interruption of high currents, especially during short-circuit conditions. The process involves the interaction between the main contacts, arcing contacts, and a PTFE (Polytetrafluoroethylene) nozzle, which guides the flow of compressed SF6 gas to extinguish the arc. Below is a detailed explanation of the arc quenching process, step by step:

  1. Initial State: Main Contacts Open, Current Commutated to Arcing Contacts 
  • Main Contacts: The main contacts, which are larger and designed for carrying normal load current, are placed concentrically outside the arcing contacts. In this initial state, the main contacts have already opened, and the current has been transferred (commutated) to the arcing contacts.
  • Arcing Contacts: The arcing contacts are smaller and specifically designed to handle the high temperatures and pressures generated during arcing. They are about to open, and as they do, an arc will ignite between them.
  1. Arc Ignition: Arcing Contacts Begin to Separate 
  • As the arcing contacts start to separate, the current continues to flow through the small gap between them, forming an arc. At this point, the arc is still relatively stable, and the PTFE nozzle, which is fixed to the moving contact, begins to guide the compressed SF6 gas from the puffer volume toward the arc.
  • The flow of gas is initially limited because the arc cross-section may be large, especially at high short-circuit currents. This phenomenon, where the arc cross-section is larger than the nozzle throat diameter, is known as current clogging. During current clogging, the gas flow is partially blocked by the arc, preventing it from effectively cooling the arc.
  1. Gas Pressure Build-Up and Arc Constriction 
  • Mechanical Movement and Heat Transfer: As the arcing contacts continue to separate, the mechanical movement of the contacts further compresses the SF6 gas in the puffer volume. Additionally, heat from the arc is transferred to the gas, causing its temperature to rise rapidly. This combination of mechanical compression and heat transfer leads to a significant increase in gas pressure within the puffer volume.
  • Approach to Current Zero Crossing: As the arc approaches its natural zero crossing (the point where the alternating current passes through zero), the arc's cross-section begins to decrease. This reduction in arc size allows the compressed SF6 gas to flow more freely through the nozzle.
  • Powerful Gas Blast: Just as the arcing contacts fully separate, the compressed gas in the puffer volume is released through the nozzle, creating a powerful blast that blows directly onto the arc. This high-velocity gas flow cools the arc rapidly, stretches it, and disrupts the ionized plasma, leading to the extinction of the arc.
  1. Arc Extinction and Dielectric Strength Recovery 
  • Arc Extinguishment: Once the arc is extinguished at the current zero crossing, the flow of current ceases, and the arc no longer exists. The absence of the arc means that the heat source is removed, allowing the SF6 gas to cool down.
  • Recombination of Gas Particles: After the arc is extinguished, the decomposed SF6 gas particles (such as SF4, S2F10, etc.) begin to recombine, restoring the original chemical structure of SF6. This recombination process also restores the insulating properties of the gas.
  • Dielectric Strength Recovery: The rapid recombination of gas particles and the cooling of the gas lead to a quick recovery of the dielectric strength between the contacts. This ensures that the arc does not reignite when the voltage across the contacts increases after the current has passed through zero.
  • Contact Movement Stops: With the arc extinguished and the dielectric strength restored, the movement of the contacts stops. The gas pressure inside the circuit breaker (CB) then stabilizes, and the system returns to a normal, non-conductive state.

Key Points to Note:

  • Current Clogging: At high short-circuit currents, the arc cross-section can be larger than the nozzle throat diameter, temporarily blocking the gas flow. This phenomenon is called current clogging. Despite this, the gas pressure continues to build up due to mechanical compression and heat transfer from the arc.
  • Puffer Volume and Nozzle Design: The puffer volume is a crucial component that stores the compressed SF6 gas, which is then released through the PTFE nozzle. The nozzle is designed to direct the gas flow precisely onto the arc, ensuring effective cooling and arc quenching.
  • Rapid Dielectric Strength Recovery: One of the key advantages of SF6 gas is its ability to quickly recover its insulating properties after the arc is extinguished. This ensures that the circuit breaker can safely interrupt high currents without risking arc reignition.

Conclusion

The puffer-type SF6 circuit breaker's arc quenching process is a highly efficient and reliable method for interrupting high currents, especially during short-circuit conditions. The combination of mechanical compression, gas flow, and the unique properties of SF6 gas ensures that the arc is rapidly extinguished, and the dielectric strength between the contacts is quickly restored. This design allows the circuit breaker to handle large fault currents while maintaining the integrity and safety of the electrical system.

Edwiin

Online condition monitoring device (OLM2) on high voltage Circuit Breakers
Online condition monitoring device (OLM2) on high voltage Circuit Breakers
This device is capable of monitoring and detecting various parameters according to the specifications outlined:SF6 Gas Monitoring:Utilizes a specialized sensor for measuring SF6 gas density.Capabilities include measuring gas temperature, monitoring SF6 leak rates, and calculating the optimal date for refilling.Mechanical Operation Analysis:Measures operational times for closing and opening cycles.Evaluates primary contacts separation speed, damping, and contact overtravel.Identifies signs of mec
Edwiin
02/13/2025
Anti pumping function in circuit breakers operating mechanism
Anti pumping function in circuit breakers operating mechanism
The anti - pumping function stands as a crucial characteristic of control circuits. In the absence of this anti - pumping function, assume that a user connects a maintained contact within the closing circuit. When the circuit breaker is closed onto a fault current, the protective relays will promptly trigger a tripping action. However, the maintained contact in the closing circuit will attempt to close the breaker (once again) onto the fault. This repetitive and dangerous process is referred to
Edwiin
02/12/2025
Ageing phenomena of current pass blades in high voltage disconnector switch
Ageing phenomena of current pass blades in high voltage disconnector switch
This failure mode has three primary origins:Electrical Causes: The switching of currents, such as loop currents, can lead to localized wear. At higher currents, an electric arc may burn at a specific spot, increasing the local resistance. As more switching operations occur, the contact surface wears down further, causing an increase in resistance.Mechanical Causes: Vibrations, often due to wind, are the main contributors to mechanical aging. These vibrations cause abrasion over time, leading to
Edwiin
02/11/2025
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Initial Transient Recovery Voltage (ITRV) for high voltage circuit breakers
Transient Recovery Voltage (TRV) stress similar to that encountered during a short-line fault can also occur due to the busbar connections on the supply side of a circuit breaker. This specific TRV stress is known as Initial Transient Recovery Voltage (ITRV). Given the relatively short distances involved, the time to reach the first peak of ITRV is typically less than 1 microsecond. The surge impedance of the busbars within a substation is generally lower compared to that of overhead lines.The f
Edwiin
02/08/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!