Exploring the Design and Application of Photoelectric Current Transformers in GIS

07/07/2025

1.Design and Application Example of Photoelectric Current Transformer in GIS
This article takes a 126kV GIS project as a specific example to deeply explore the design ideas and practical application of photoelectric current transformers in the GIS system. Since this GIS project was officially put into operation, the power system has remained stable, with no major failures occurring, and the operation status is relatively ideal.
1.1 Design and Application Ideas of Photoelectric Current Transformer
In the initial stage of the project, the GIS project team had intense discussions on the layout plan of the photoelectric current transformer. The core controversy focused on: whether to arrange it in the sulfur hexafluoride SF6 gas environment or in the conventional air environment.
Scheme 1: Arranged in the Sulfur Hexafluoride Gas Environment
If this scheme is adopted, the photoelectric current transformer will be in a high - pressure sulfur hexafluoride gas environment, and the electrical connection between it and the control room needs to rely on optical fibers. However, in the high - pressure environment of sulfur hexafluoride, it is rather difficult to introduce optical fibers into the control box. If optical fibers are to be made into terminal ports similar to the form of cables, professional seamless welding technology must be adopted; but the welding process will not only interfere with the transmission of optical signals, but also the conductive path formed by welding may affect the electrical insulation performance of the current transformer, with many unfavorable factors.
Scheme 2: Arranged in the Air Environment
This scheme does not need to consider the impact of high pressure, so there are no concerns related to welding. However, it is necessary to focus on how to ensure the tightness of the current transformer, as well as the impact of eddy currents on the measurement accuracy and other potential impacts that may occur.
After rigorous analysis and comparison, the GIS project team finally selected Scheme 2. This scheme takes the safety, reliability and stability of system operation as the primary consideration, and fully takes into account the operability during the implementation of the scheme.
2. Solution to Scheme Problems
Structural Design and Connection
By comparing and analyzing the design structure of the photoelectric current transformer with that of the traditional electromagnetic current transformer, it is determined to arrange the photoelectric current transformer in the air environment, and carry out the following design work:
Produce an adapted large - scale flange, place the photoelectric current transformer inside the flange, and lead out the optical fiber from the side of the flange. In this way, the connection part between the optical fiber and the photoelectric current transformer is located inside the transformer, and this area is adjacent to the large flanges of other external transformers, and the photoelectric current transformer and the sulfur hexafluoride gas are isolated by metal.
Since eddy currents will be generated during the operation of the current transformer, which will interfere with the measurement accuracy and voltage of the photoelectric current transformer. To solve this problem, electrostatic spraying treatment is adopted on the metal contact surfaces of the two large flanges, so as to block the eddy current loop and ensure the tightness of the sulfur hexafluoride gas.
Electric Field Simulation and Verification
Due to the adoption of the flange structure in the design, the electric field distribution of the photoelectric current transformer will change. To verify the effectiveness of the scheme, it is necessary to use mature simulation calculation tools (such as ANSYS software) to carry out testing and analysis work. Use ANSYS to conduct field strength experiments on the metal rings and conductors of the two flanges. The lightning impulse voltage used in the experiment is 150kV. Through precise analysis by ANSYS software, it is concluded that the field strength at the edge parts of the flange and the shielding cover is the largest, and the maximum value reaches 20kV/mm. This result has passed the test and acceptance after in - depth research and scientific and precise simulation calculations by the project team.
At present, this project has been running stably for a long time, and the effect is good. Currently, certain achievements have been made in the research of photoelectric current transformers in China. However, in the application scenarios of high voltage levels, there are still problems such as reducing the influence of birefringence caused by stress and temperature, ensuring the long - term stable operation of the system, and further improving the measurement accuracy, which need to be solved in the follow - up.
3. Conclusion
Through the discussion of the whole process from scheme selection, implementation to problem solving of the photoelectric current transformer in the GIS system, it can be seen that remarkable results have been achieved in the field of GIS design and application. Compared with the traditional electromagnetic current transformer, the photoelectric current transformer has obvious advantages, and its application range is becoming wider and wider. Many manufacturers and users have already adopted it. It is foreseeable that in the near future, the photoelectric current transformer is expected to completely replace the electromagnetic current transformer, and with the continuous development and maturity of technology, it will make greater contributions to the progress of transformer technology.

Focused on the design of electrical equipment, proficient in electrical principles and relevant specifications, and skilled in using design software. From intelligent substations to various types of electrical equipment, I am adept at optimizing design solutions, integrating new technologies. With practical experience and collaborative management capabilities, I deliver outstanding electrical design achievements.

Key Technologies of Low-Voltage DC Solid-State Circuit Breakers
Key Technologies of Low-Voltage DC Solid-State Circuit Breakers
1 Technical Challenges1.1Stability of Device ParallelingIn practical applications, the current-carrying capacity of a single power electronic device is relatively limited. To meet high-current requirements, multiple devices are often connected in parallel. However, parameter variations between devices—such as slight differences in on-resistance and threshold voltage—can cause uneven current distribution during parallel operation. During switching transients, parasitic inductance and capacitance
09/02/2025
Research on Bridge-Type Fault Current Limiters
Research on Bridge-Type Fault Current Limiters
1 Bridge-Type Superconducting Fault Current Limiter1.1 Structure and Operating Principle of the Bridge-Type SFCLFigure 1 shows the single-phase circuit diagram of the bridge-type SFCL, which consists of four diodes D₁ to D₄, a DC bias voltage source V_b, and a superconducting coil L. A circuit breaker CB is connected in series with the limiter to interrupt the fault current after it has been limited. The bias source V_b provides a bias current i_b to the superconducting coil L. The voltage of V_
08/25/2025
What should be paid attention to in the design of low-voltage pole-mounted circuit breakers?
What should be paid attention to in the design of low-voltage pole-mounted circuit breakers?
Low-voltage pole-mounted circuit breakers are critical protective and control devices in power systems, whose design and operation directly affect system safety and reliability. Their design must comprehensively address environmental adaptability, electrical parameter coordination, and actuator selection to ensure stable operation under diverse conditions. During operation, strict adherence to safety protocols, regular maintenance, and proper handling of exceptional situations are essential to p
08/21/2025
Study on Steep - Wave Breakdown Characteristics of Hybrid Porcelain Insulators
Study on Steep - Wave Breakdown Characteristics of Hybrid Porcelain Insulators
Porcelain and glass insulators exhibit excellent insulation performance and mechanical strength, but are prone to pollution flashover under severe contamination, threatening the stable operation of power grids. To enhance the pollution flashover resistance of external insulation, manufacturers commonly apply room-temperature vulcanized silicone rubber (RTV) coatings with superior hydrophobicity and hydrophobicity transfer properties onto insulator surfaces, thereby reducing flashover risks. Init
08/20/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!