What You Need to Know About Load Switch Malfunctions

Master Electrician
06/30/2025

Hey there, I’m Blue — been working as an electrical engineer for more than 20 years now.
I’ve spent most of my career designing circuit breakers, managing transformers, and helping power companies solve all sorts of electrical system challenges.

WechatIMG3584.png

Today, a friend from Southeast Asia asked me:

"What are the common faults of load switches?"

Great question! So let’s break it down in simple terms — no fancy jargon, just real-world stuff you might actually see on the job or during maintenance.

First, What Exactly Is a Load Switch?

Before we talk about the problems, let’s quickly recap what a load switch is.

A load switch is like a heavy-duty on/off switch used in medium-voltage systems (like 10kV, 20kV grids). It can make and break normal operating currents, but not fault currents — that’s what circuit breakers are for.

So think of it as the "middle guy" between a regular switch and a full-blown circuit breaker. It’s simpler, cheaper, and often used in distribution networks, especially in places where protection coordination isn’t super complex.

Now, Let’s Talk About the Most Common Faults

In my years of fieldwork and troubleshooting, I’ve seen these issues come up again and again. Here’s a list of the most typical ones:

1. Failure to Close or Open Properly

This one’s pretty common, especially in older equipment.

Sometimes the switch won’t close even when you press the button.

Or it closes, but then opens right away.

Could also be stuck in the closed position and refuses to open.

Why does this happen?

Mechanical parts get worn out over time — linkages jammed, springs weak, latches misaligned.

Control circuits might have loose wires or burned relays.

Sometimes the motor operator (if electrically operated) fails.

Real-life example:

I once worked on a site where the load switch wouldn’t close because a small screw had fallen into the mechanism and was jamming the movement. Took us 2 hours to find it!

2. Overheating or Burning Smell

If you smell something burning near a load switch panel, don’t ignore it.

Overheating usually happens at the contacts or terminal connections.

Can lead to insulation damage, melting parts, or even fire if not fixed early.

Causes:

Loose cable connections — high resistance = heat.

Contacts getting old or pitted — bad contact surface.

Excessive current flow beyond rated capacity (overloading).

Tip: Always check the temperature regularly using infrared thermography. If a connection is more than 10–15°C hotter than others, investigate ASAP.

3. Arcing or Flashover During Operation

You hear a loud pop, maybe even see sparks — that’s arcing.

Happens mostly during opening/closing operations.

Dangerous, can damage components or cause injury.

Common reasons:

Main contacts worn out — gaps not maintained properly.

Dust or moisture inside the chamber — lowers insulation level.

Operating under load when it shouldn’t be (e.g., switching off a large motor without a circuit breaker upstream).

Note: Load switches are not meant to interrupt fault currents, only normal load currents. If you’re trying to cut through a short-circuit current, expect trouble.

4. Mechanical Wear and Tear

Load switches are mechanical devices. They move parts, so they wear out eventually.

Bearings, gears, and levers all degrade over time.

Especially true in environments with dust, salt spray, or extreme temperatures.

Prevention tip: Regular preventive maintenance (PM) is key. Lubricate moving parts, inspect linkages, and replace worn-out components before they fail.

5. Control Circuit Failures

The control side is just as important as the main circuit.

Indicator lights stop working.

Remote operation fails.

Local buttons don’t respond.

Typical causes:

Blown fuses in the control circuit.

Corroded terminals or broken wires.

PLC or RTU communication errors (in automated systems).

Quick fix idea: Use a multimeter to trace voltage drop and continuity. Start simple — check fuses first.

6. Moisture and Corrosion Inside the Enclosure

Especially common in coastal areas or humid climates.

Moisture gets into the switchgear cabinet.

Causes rust, corrosion, and reduced insulation levels.

Symptoms:

Tripping for no apparent reason.

Arcing even under light load.

Bad smell or condensation visible inside the box.

Solution: Make sure the enclosure has proper sealing and desiccant packs. In tropical areas, consider adding space heaters or dehumidifiers.

7. Wrong Operation by Personnel

Human error is still one of the biggest causes of failures.

Someone tries to open the switch under heavy load.

Or operates the switch without checking interlocks.

Even worse — someone forgets to lock out/tag out before maintenance.

Lesson learned: Training matters. Clear labeling helps. And always follow safety procedures.

Final Thoughts

Like any electrical equipment, load switches aren’t perfect. But with good design, regular maintenance, and proper operation, most of these faults can be avoided or caught early.

As someone who’s been in the field for over two decades, my advice is:

“Don’t wait for a failure to remind you that maintenance is important.”

If you're dealing with a faulty load switch and want help troubleshooting or choosing replacements, feel free to reach out. Happy to share more stories (and some war scars) from the field.

Stay safe, and keep the lights on!

— Blue


Master Electrician

We aim to gather electrical knowledge and share it with others.

Analysis of the Impact of Immersion on the Performance of Low-Voltage Current Transformers
Analysis of the Impact of Immersion on the Performance of Low-Voltage Current Transformers
1 IntroductionLow - voltage current transformers for metering, with a through - core type epoxy resin structure, are widely used in distribution transformer areas and for small - to - medium - sized industrial and commercial electricity consumption. As a range expander for electric energy metering, their performance directly relates to electricity consumption safety and the accuracy of users' trade calculations. Studying long - term immersion's impact on these transformers is practically signifi
Felix Spark
07/17/2025
What are the common faults that occur when low-voltage current transformers are combined with other power equipment?
What are the common faults that occur when low-voltage current transformers are combined with other power equipment?
Low-voltage current transformers, as indispensable measurement and protection devices in power systems, often encounter various faults when used in combination with other power equipment due to environmental factors, equipment linkage issues, and improper installation and maintenance. These faults not only affect the normal operation of power equipment but may also endanger personal safety. Therefore, it is necessary to gain an in-depth understanding of fault types, judgment methods, and prevent
Felix Spark
07/17/2025
What are the common faults of low-voltage voltage transformers?
What are the common faults of low-voltage voltage transformers?
1. Open - Circuit Fault on the Secondary SideOpen - circuit in the secondary side is a typical fault of low - voltage voltage transformers, showing abnormal voltmeter readings (zero/fluctuation), faulty power meters, buzzing noises, and core overheating. When open - circuited, the secondary voltage spikes (no secondary current to balance the primary EMF), causing core saturation, flux distortion, and potential overheating/damage.Causes include loose terminals, poor contact, or human error. In lo
Oliver Watts
07/16/2025
Fault Analysis of Single - Phase Grounding of Three - Phase 4PT Voltage Transformer
Fault Analysis of Single - Phase Grounding of Three - Phase 4PT Voltage Transformer
In 10 kV and 35 kV ungrounded systems, single - phase grounding faults cause minimal current, so protection rarely trips. Per regulations, operation is limited to 2 hours; prolonged undetected faults may worsen, even damaging switches. While the State Grid promotes small - current grounding line selection devices in 110 kV and 220 kV substations, their accuracy remains low, requiring monitoring/operation staff to analyze remote measurements. For ungrounded systems with three - phase 4PT voltage
Felix Spark
07/15/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!