• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Technical Features Application and Standards of 500kV Dry-type Shunt Reactors in Brazil

Echo
Echo
Field: Transformer Analysis
China

1 Technical Features and Standard References of 500kV Dry - type Shunt Reactors
1.1 Technical Features

The 500kV dry - type shunt reactor, an oil - free power device for ultra - high - voltage transmission systems, boasts core features like advanced insulation, innovative heat dissipation, optimized electromagnetic design, and modular structure. These advantages, outperforming traditional oil - immersed reactors, also drive new technical standard demands.

  • Advanced Insulation: Using epoxy resin casting and nanocomposites (with nano - SiO₂ particles boosting epoxy breakdown strength by ~40% and partial discharge initial voltage by 25%), it enhances insulation and partial discharge resistance. This breakthrough calls for redefining insulation levels and partial discharge test methods in standards.

  • Innovative Heat Dissipation: A composite structure (multi - channel forced air cooling + phase - change material - assisted heat dissipation) keeps hot - spot temperature rise within 60K (well below IEC limits, verified via finite element analysis and experiments). New temperature - rise test methods/limits are needed in standards.

  • Optimized Electromagnetic Design: Multi - layer staggered winding and gradient insulation optimize electric field distribution, improving short - circuit resistance. Finite element analysis shows ~20% reduction in maximum electric field strength in windings. Standards should add evaluation methods for electric field distribution and short - circuit resistance.

  • Modular Structure: Composed of serially connected identical basic units, easing manufacturing, transportation, and on - site installation. Standards need test requirements for inter - module connection reliability and overall performance consistency.

1.2 Reference and Formulation of Technical Standards

In applying 500kV dry - type shunt reactor tech in Brazil, technical standards played a key role. The research team delved into Brazil’s electrical standard ABNT NBR 5356 - 6 Transformer Part 6: Reactors, and combined international standards like IEC 60076 - 6 Power Transformers - Part 6: Reactors and IEEE Std C57.12.90 - 2021 Standard Test Procedures for Liquid - Immersed Distribution, Power, and Regulating Transformers, to develop a 500kV dry - type shunt reactor technical specification fitting Brazil’s context.

Key focuses during specification formulation:

  • Insulation Level: Tailored to Brazil’s grid, insulation requirements were raised (lightning impulse withstand voltage: 1550kV; operating impulse withstand voltage: 1175kV – higher than Chinese standards but grid - suitable). Per NBR5356 - 6, switching impulse test Tz ≥ 1000 μs and Td ≥ 200 μs.

  • Temperature Rise & Heat Dissipation: For Brazil’s high - temp environment, the average temperature rise limit was tightened from 60K to 50K (via innovative cooling design, boosting safety). Added thermal imaging analysis and long - term temperature monitoring for the composite cooling structure.

  • Loss Requirements & Calculation: Designed per Brazil’s standards with a 0.3% interference loss limit. Using IEEE Std C57.12.90 - 2021 Annex B.2, a 50Hz - 60Hz loss conversion model was built, ensuring accurate and comparable loss calculations across frequencies.

  • Environmental Adaptability: For Brazil’s hot and humid climate, added anti - salt - fog, anti - pollution - flashover, and anti - UV requirements to enhance long - term reliability. Formulated tests like accelerated aging and humid - heat cycle tests.

2 Application Practice of 500kV Dry - type Shunt Reactors in Brazil
2.1 Challenges in Technology Introduction and Standard Adaptation

Applying 500kV dry - type shunt reactor technology in Brazil’s power system poses multiple challenges, requiring solutions to these key issues:

  • Technical Standard Differences: Brazil’s ABNT NBR 5356 - 6 Transformer Part 6: Reactors and China’s GB/T 1094.6 - 2017 Power Transformers - Part 6: Reactors are structurally similar but differ in specific requirements and implementation details. Both reference IEC 60076 - 6 but are localized to national needs, varying in insulation levels, temperature - rise limits, and loss - calculation methods. These differences demand careful handling during technology adaptation.

  • Climate Adaptability: Brazil’s tropical climate (e.g., Silvânia region: annual average temperature >25°C, relative humidity ≥80%) imposes higher heat - dissipation and insulation demands. Such a hot, humid environment severely challenges traditional power equipment’s insulation and service life.

  • Grid - Characteristic Adaptation: Brazil’s 500kV grid has voltage fluctuations ~15% higher than China’s same - level grids, with different harmonic environments. Reactors need stronger voltage adaptability and anti - harmonic performance.

  • Localized Operation & Maintenance (O&M) Needs: To ensure long - term reliable operation, localized O&M capabilities/habits must be considered, covering technical training, spare - parts supply, and localized services.

2.2 Adjustment and Innovation of Technical Standards

To address the above challenges, this research took innovative measures, most crucially adjusting pre - project technical standards and specifications based on the actual use and testing of the new dry - type reactor. This resolved technical adaptation issues and provided a key reference for similar projects.

Key technical standard modifications:

  • Cancel Partial Discharge Test:External corona interference on dry - type reactors far exceeds their internal partial discharges. With no mature testing methods/criteria for interference partial discharge, and considering NBR 5356 - 11 - 2016 only applies to low - voltage dry - type transformers (no external interference) and IEEE C57.21 exempts dry - type shunt reactors from such tests, the partial discharge test for 500kV dry - type reactors is canceled.

  • Optimize Insulation & Test Time:Per Brazilian standards, lightning impulse withstand voltage is 1550kV and operating impulse withstand voltage is 1175kV. Due to reactor impedance, switching impulse test time parameters are adjusted to Td ≥ 120 μs and Tz ≥ 500 μs.

  • Enhance Heat Dissipation:For Brazil’s hot, humid climate, a new composite heat - dissipation structure using Class H (180°C) insulation (boosting heat resistance by 30°C vs traditional designs) is developed. Thermal simulations show hot - spot temperature rise stays within 60K (below design limits).

  • Adjustment of Loss Calculation Method: A reactor’s loss comprises the DC resistance loss of its winding (Pdc) and the winding’s additional loss (Pa). For a given reactor structure, both Pdc and Pa are proportional to the square of the current. Using transposed conductors, and with only a few small conductive metal components (like connectors) at connection points (non - magnetic), the additional loss accounts for a low proportion of the DC loss. Test results show the prototype’s extra loss is ~9%–12%, so the loss calculation formula is as follows:

  • Enhancing Voltage Adaptability: By optimizing the electromagnetic design, the voltage adaptation range of the equipment was expanded to cope with the large voltage fluctuations in the Brazilian power grid. Meanwhile, the equipment’s anti - harmonic performance was improved, and harmonic modes were reduced through a special winding design.

3 Evaluation of Practical Effects and Technical Standards
3.1 Analysis of Practical Effects

Through application at Silvânia Substation, the 500kV dry - type shunt reactor showed excellent performance. Per CEPRI - EETC03 - 2022 - 0880 (E) test report, key indicators:

  • Loss Level: Measured loss: 58.367kW @ 80°C (below 60kW limit), verifying effective loss calculation/control methods.

  • Noise Control: Measured noise: 57dB(A) (well under 80dB(A) requirement), thanks to focused noise - control design.

  • Temperature - Rise Performance: Average temp rise: 22.9K; hot - spot rise: 26.5K (both under design limits), validating new cooling design for Brazil’s climate.

  • Electrical Performance: Performed well in tests (lightning/operating impulse). Used ABNT NBR 5356 - 4/IEC 60076 - 4 parameters (T1, Td, Tz) for operating impulse, accounting for reactor impedance.

These prove the reactor’s applicability/superiority in Brazil’s grid, especially in energy efficiency/environmental protection, supporting sustainable development. Results also verify scientific, forward - looking technical specs.

3.2 Technical Standard Optimization Evaluation

Based on practice/operation, the team proposes optimizations:

  • Loss Limits: Lower 500kV/20Mvar reactor loss limit from 60kW @ 80°C to 58kW @ 80°C; use 75°C for loss - calculation reference.

  • Noise Standards: Refine standards (e.g., 75dB(A) for substations near residences); consider noise under varying voltages (e.g., 600kV).

  • Temperature - Rise Limits: Adjust average temp - rise limit from 60K to 50K; specify Class B insulation (130°C temp index, 60/90°C avg/hot - spot rises).

  • Insulation Coordination: Raise lightning impulse withstand voltage to 1600kV (for Brazil’s frequent lightning); use 140kV power - frequency dry - withstand for neutral - point insulation. Define test freq (≥48Hz, 80% of rated) and duration (≥60s).

  • Environmental Adaptability: Add anti - salt - fog reqs (coastal areas); consider EMF impact, set spacing. Use shields, anti - pollution/UV coatings in design.

These suggestions boost reactor performance/reliability, guide future standards, and help Brazil’s grid develop efficiently, reliably, and sustainably.

Give a tip and encourage the author!
Recommended
3D Wound-Core Transformer: Future of Power Distribution
3D Wound-Core Transformer: Future of Power Distribution
Technical Requirements and Development Trends for Distribution Transformers Low losses, especially low no-load losses; highlighting energy-saving performance. Low noise, particularly during no-load operation, to meet environmental protection standards. Fully sealed designto prevent transformer oil from contacting external air, enabling maintenance-free operation. Integrated protection devices within the tank, achieving miniaturization; reducing transformer size for easier on-site installation. C
Echo
10/20/2025
Reduce Downtime with Digital MV Circuit Breakers
Reduce Downtime with Digital MV Circuit Breakers
Reduce Downtime with Digitized Medium-Voltage Switchgear and Circuit Breakers"Downtime" — it’s a word no facility manager wants to hear, especially when it’s unplanned. Now, thanks to next-generation medium-voltage (MV) circuit breakers and switchgear, you can leverage digital solutions to maximize uptime and system reliability.Modern MV switchgear and circuit breakers are equipped with embedded digital sensors that enable product-level equipment monitoring, providing real-time insights into the
Echo
10/18/2025
One Article to Understand the Contact Separation Stages of a Vacuum Circuit Breaker
One Article to Understand the Contact Separation Stages of a Vacuum Circuit Breaker
Vacuum Circuit Breaker Contact Separation Stages: Arc Initiation, Arc Extinction, and OscillationStage 1: Initial Opening (Arc Initiation Phase, 0–3 mm)Modern theory confirms that the initial contact separation phase (0–3 mm) is critical to the interrupting performance of vacuum circuit breakers. At the beginning of contact separation, the arc current always transitions from a constricted mode to a diffused mode—the faster this transition, the better the interruption performance.Three measures c
Echo
10/16/2025
Advantages & Applications of Low-Voltage Vacuum Circuit Breakers
Advantages & Applications of Low-Voltage Vacuum Circuit Breakers
Low-Voltage Vacuum Circuit Breakers: Advantages, Application, and Technical ChallengesDue to their lower voltage rating, low-voltage vacuum circuit breakers have a smaller contact gap compared to medium-voltage types. Under such small gaps, transverse magnetic field (TMF) technology is superior to axial magnetic field (AMF) for interrupting high short-circuit currents. When interrupting large currents, the vacuum arc tends to concentrate into a constricted arc mode, where localized erosion zones
Echo
10/16/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.