Why do arc furnace transformers and inrush currents cause voltage sags?

Leon
08/06/2025

An electric arc furnace is a device that melts metal using the high temperature generated by an electric arc. It converts electrical energy into thermal energy through a transformer, then transfers the heat via the arc to the furnace charge, causing it to melt. When the arc furnace starts operating, the transformer load increases suddenly, leading to a drop in grid voltage. Additionally, due to the operational characteristics of the arc furnace, the load continues to rise over a period of time, which may result in a significant voltage sag. Conversely, when the arc furnace stops, the sudden reduction in transformer load can cause a rise in grid voltage, resulting in a voltage swell.

During arc furnace operation, as the melting and cooling of the charge generate substantial heat, continuous power supply is required. If faults or operational errors occur during power delivery, sympathetic inrush currents (also known as magnetizing inrush currents) may be triggered, further affecting grid stability.

Statistics show that transformer sympathetic inrush currents impact voltage sags in two main ways: first, they cause a sudden increase in grid current, exacerbating the magnitude of voltage sags; second, they may lead to grid voltage instability, increasing the frequency of voltage sags. To prevent voltage sags caused by sympathetic inrush currents in arc furnace transformers, the following three measures are recommended:

  • Optimize arc furnace operation and adjust transformer parameters: Improve operational procedures and fine-tune transformer settings to effectively reduce the magnitude of voltage sags.
  • Adjust arc furnace operating frequency and transformer load ratio: Properly configure the furnace's operating frequency and load ratio to mitigate the severity of voltage sags.
  • Install voltage sag compensation devices: Monitor grid voltage in real time and automatically activate compensation equipment during voltage sags to restore grid voltage to normal levels.

Understanding that arc furnace transformers and sympathetic inrush currents are key contributors to voltage sags enables targeted measures to reduce their impact, thereby enhancing the efficiency and stability of power system operations.

Time is limited, so this concludes today’s discussion. If you would like to learn more about transformer magnetizing inrush currents and mitigation methods, feel free to leave a comment!

Leon

Hello! I'm Leon, with 20 years of extensive experience in the power industry. My expertise spans from power distribution equipment to grid operations and maintenance, grounded in robust hands-on and theoretical knowledge. Currently, I focus on sharing insights into electrical equipment fault diagnosis, demystifying complex technical challenges through accessible explanations. I welcome collaboration with industry peers and enthusiasts to collectively explore the intricacies of the power sector.

Advantages of SF6 Fully Insulated Ring Main Units in Power Supply Systems
Advantages of SF6 Fully Insulated Ring Main Units in Power Supply Systems
Current Power Supply Method Using SF6 Ring Main UnitsTo enhance grid performance, the design of traditional SF6 ring main units (RMUs) has been further optimized. A key feature of second-generation SF6 RMUs is the use of a grounded, enclosed epoxy resin housing, with SF6 gas as the insulating medium. Two three-position load switches and one three-position arc-rotating circuit breaker are integrated into a single sealed unit, equipped with a pressure relief safety valve. In the event of arc-quenc
Echo
08/09/2025
Working Principle and Introduction of Rectifier Transformers
Working Principle and Introduction of Rectifier Transformers
Working Principle of Rectifier TransformersThe working principle of a rectifier transformer is the same as that of a conventional transformer. A transformer is a device that converts AC voltage based on the principle of electromagnetic induction. Typically, a transformer consists of two electrically isolated windings—the primary and secondary—wound around a common iron core. When the primary winding is connected to an AC power source, the alternating current generates a magnetomotive
Ron
08/07/2025
Common Faults and Diagnostic Technologies of Oil-immersed Distribution Transformers
Common Faults and Diagnostic Technologies of Oil-immersed Distribution Transformers
1.Common Faults and Diagnostic Measures1.1 Transformer Oil Leakage1.1.1 Oil Leakage from Tank Weld SeamsFor oil leakage at flat joints, direct welding is applicable. For leakage at corners or joints reinforced with stiffeners, the exact leakage point is often difficult to locate, and re-leakage may occur after welding due to internal stress. For such cases, repair welding with an added iron plate is recommended: for two-surface joints, the iron plate can be cut into a spindle shape for welding;
Vziman
08/07/2025
Analysis of Interlocking Protection Circuit for Furnace Transformer
Analysis of Interlocking Protection Circuit for Furnace Transformer
Currently, the company operates two electric arc furnace (EAF) transformers. The secondary voltage ranges from 121 V to 260 V, with a rated current of 504 A / 12,213 A. The high-voltage side has a total of eight tap positions, utilizing motor-driven off-circuit voltage regulation. The equipment is equipped with a reactor of corresponding capacity, connected in series to designated taps on the high-voltage side. These transformers have been in operation for over 20 years. Throughout this period,
Dyson
08/07/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!