What is a Residual Current Circuit Breaker?

Encyclopedia
09/09/2024


What is a Residual Current Circuit Breaker?


RCCB Definition


A Residual Current Circuit Breaker (RCCB) is defined as a safety device that detects and interrupts a circuit when there is a leakage current to the ground.


Working Principle


An RCCB operates based on Kirchhoff’s current law, which states that the total current entering a node equals the total current leaving it. In a normal circuit, the currents in the live and neutral wires are balanced. If there is a fault, like damaged insulation or contact with a live wire, some current flows to the ground. This imbalance is detected by the RCCB, causing it to trip and disconnect the circuit within milliseconds.


An RCCB contains a toroidal transformer with three coils: live wire, neutral wire, and sensing coil. When currents are balanced, the live and neutral coils produce equal and opposite magnetic fluxes. An imbalance generates a residual magnetic flux, inducing voltage in the sensing coil. This voltage triggers a relay to open the RCCB contacts and disconnect the circuit.

 

864e406be9e580129b863497afaa3845.jpeg

 

An RCCB includes a test button for users to check its functionality by creating a small leakage current. Pressing the button connects the live wire on the load side to the supply neutral, bypassing the neutral coil. This causes a current imbalance, making the RCCB trip. If it doesn’t trip, the RCCB may be faulty or incorrectly wired and needs repair or replacement.


Types of RCCBs


There are different types of RCCBs based on their sensitivity to different types of leakage currents:


  • Type AC: This type responds to pure alternating currents (AC) only. It is suitable for general applications where there are no electronic devices or variable frequency drives that produce direct or pulsating currents.



  • Type A: This type responds to both AC and pulsating direct currents (DC). It is suitable for applications where there are electronic devices such as computers, TVs, or LED lights that generate rectified or chopped currents.



  • Type B: This type responds to AC, pulsating DC, and smooth DC currents. It is suitable for applications where there are devices such as solar inverters, battery chargers, or electric vehicles that generate smooth DC currents.


  • Type F: This type responds to AC, pulsating DC, smooth DC, and high-frequency AC currents up to 1 kHz. It is suitable for applications where there are devices such as frequency converters, induction cookers, or dimmers that generate high-frequency currents.


The sensitivity of an RCCB is determined by its rated residual operating current (In), the minimum leakage current needed to trip it. Common In values are 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, and 1 A. Lower In values offer higher protection against electric shocks. For example, a 30 mA RCCB can protect against cardiac arrest if a shock lasts more than 0.2 seconds.


Another classification of RCCBs is based on their number of poles:


  • 2-pole: This type has two slots for connecting one live wire and one neutral wire. It is used for single-phase circuits.



  • 4-pole: This type has four slots for connecting three live wires and one neutral wire. It is used for three-phase circuits.


Advantages


  • They provide protection against electric shocks by detecting leakage currents as low as 10 mA.



  • They prevent fires and damage to equipment by interrupting faulty circuits quickly.



  • They are easy to install and operate with simple test and reset buttons.



  • They are compatible with different types of loads and currents (AC, DC, high-frequency).



  • They can act as main disconnecting switches upstream of any derived miniature circuit breakers (MCBs).


Disadvantages


  • They do not provide protection against overcurrents or short circuits, which can cause overheating and melting of wires. Therefore, they must be used in series with an MCB or a fuse that can handle the rated current of the circuit.



  • They may trip unnecessarily due to external factors such as lightning, electromagnetic interference, or capacitive coupling. This can cause inconvenience and loss of productivity.



  • They may fail to trip due to internal factors such as corrosion, wear, or mechanical jamming. This can compromise the safety of the circuit and the users.



  • They are more expensive and bulky than MCBs or fuses.


Choosing RCCBs


To choose the right RCCB for a circuit, the following factors should be considered:


  • The type of load and current: The RCCB should match the type of load (AC, DC, high-frequency) and the type of current (pure, pulsating, smooth) that it will protect. For example, a type B RCCB should be used for a solar inverter that generates a smooth DC current.



  • The rated residual operating current (In): The RCCB should have a low enough In to provide adequate protection against electric shocks, but not too low to cause nuisance tripping. For example, a 30 mA RCCB is recommended for domestic and commercial applications, while a 100 mA RCCB is suitable for industrial applications.



  • The rated current (In): The RCCB should have a high enough In to handle the normal operating current of the circuit, but not too high to exceed the capacity of the MCB or fuse that it is connected with. For example, a 40 A RCCB should be used with a 32 A MCB for a 230 V single-phase circuit.



  • The number of poles: The RCCB should have the same number of poles as the supply voltage. For example, a 2-pole RCCB should be used for a 230 V single-phase circuit, while a 4-pole RCCB should be used for a 400 V three-phase circuit.

 


To install an RCCB, the following steps should be followed:

 


  • Switch off the main power supply and isolate the circuit that needs to be protected by the RCCB.



  • Connect the live wire(s) from the supply side to the input terminal(s) of the RCCB marked as L1, L2, and L3.



  • Connect the neutral wire from the supply side to the input terminal of the RCCB marked as N.



  • Connect the live wire(s) from the load side to the output terminal(s) of the RCCB marked as L1’, L2’, and L3’.



  • Connect the neutral wire from the load side to the output terminal of the RCCB marked as N’.



  • Ensure that all connections are tight and secure and that no wires are loose or exposed.



  • Switch on the main power supply and test the RCCB by pressing the test button. The RCCB should trip and disconnect the circuit. If it does not, check for any wiring errors or faulty components and fix them before using the circuit.



  • Reset the RCCB by pressing the reset button. The RCCB should close and reconnect the circuit. If it does not, check for any wiring errors or faulty components and fix them before using the circuit.

 

Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

Analysis of the Technical Characteristics of Online Monitoring for Medium-Voltage Switchgear Status
Analysis of the Technical Characteristics of Online Monitoring for Medium-Voltage Switchgear Status
With the increasing complexity of power system operation environment and the deepening of power system reform, traditional power grids are accelerating the transformation to smart grids. The goal of equipment condition-based maintenance is achieved through real-time perception of equipment status by new sensors, reliable communication via modern network technology, and effective monitoring by background expert systems.I. Analysis of Condition-based Maintenance StrategyCondition-based Maintenance
Oliver Watts
06/11/2025
What is the current application status and development trend of medium-voltage switchgear?
What is the current application status and development trend of medium-voltage switchgear?
With the accelerated automation of power equipment, various medium-voltage switchgear have emerged in the market. Classified by insulation media, they are mainly divided into air-insulated, SF₆ gas-insulated and solid-insulated types, each with its own advantages and disadvantages: solid insulation offers good performance but poor environmental friendliness, SF₆ features excellent arc extinguishing capability but is a greenhouse gas, and air insulation has high cost-performance but larger volume
Echo
06/11/2025
What components make up the design of medium-voltage ring network distribution switchgear?
What components make up the design of medium-voltage ring network distribution switchgear?
As an expert who has been deeply engaged in the field of power system design for many years, I have always paid attention to the technological evolution and application practice of medium-voltage ring main distribution equipment. As a core electrical device in the secondary distribution link of the power system, the design and performance of such equipment are directly related to the safe and stable operation of the power supply network. The following is a professional analysis of the key design
Dyson
06/11/2025
What aspects should be paid attention to when installing medium-voltage switch cabinets during the initial stage of subway operation?
What aspects should be paid attention to when installing medium-voltage switch cabinets during the initial stage of subway operation?
1. Statistics on Common Faults of Medium-Voltage Switchgear in the Early Operation StageAs project participants, we found during the early operation of a new metro line: 21 sets of power supply equipment were put into use, with a total of 266 accident phenomena in the first year. Among them, 77 faults occurred in medium-voltage switchgear, accounting for 28.9%—significantly higher than faults in other equipment. Statistical analysis shows that major fault types include: protection device s
Felix Spark
06/11/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!