• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What is Transformation Ratio?

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

What is Transformation Ratio?


Transformer conversion ratio refers to the proportional relationship between the number of turns between the primary and secondary windings of the transformer, which determines the voltage conversion capability of the transformer. The conversion ratio is one of the most basic characteristics of a transformer and is used to describe how the transformer changes the input voltage to the output voltage.


Definition


The conversion ratio of the transformer is defined as the ratio of the number of turns in the primary winding N1 to the number of turns in the secondary winding N2:


bca0efdf41ba69f748906149d8d19117.jpeg


The conversion ratio can also be expressed in terms of voltage, that is, the ratio of primary voltage V1 to secondary voltage V2:


51fb2a315075566a3a0879f1f8694555.jpeg


Type


Booster transformer: when N 1<N 2, the transformation ratio n<1, the primary voltage is lower than the secondary voltage, that is, V1<V2.


Step-down transformer: when N1>N2, the conversion ratio n>1, the primary voltage is higher than the secondary voltage, that is, V1>V2


Isolation transformer: when N1=N2, the transformation ratio n=1, the primary voltage is equal to the secondary voltage, that is V1 is equal to V2.


Working principle


The working principle of transformers is based on the law of electromagnetic induction. When an alternating current passes through the primary winding, it creates an alternating magnetic field around the winding. This magnetic field passes through the secondary winding and induces an electromotive force (EMF) in the secondary winding according to Faraday's law of electromagnetic induction. The size of the induced electromotive force is proportional to the number of turns in the winding, so:


d557d6dfe725e97ca0383325f89c048c.jpeg


Current relation


In addition to voltage changes, transformers also change current. According to the law of electromagnetic induction, the primary current I1 and the secondary current I2


The relationship between them follows the following rules:


42175a8b1964c5f5d0443fd8b074db8f.jpeg


This means that if the transformer is a booster transformer, the secondary current will be reduced; If it is a step-down transformer, the secondary current will increase.


Power relation


Ideally, the input power of the transformer is equal to the output power (ignoring the loss) :


a163359708e103f9d87590c40ecf97cc.jpeg


Application scenario


Transformer conversion ratio has a wide range of application scenarios, including but not limited to:


  •  Power transmission: In the process of power transmission, booster transformers are used to increase voltage to reduce energy loss in the transmission line; Step-down transformers are used to convert high voltage electricity at the end user to low voltage electricity suitable for domestic and industrial use.



  • Power distribution: In a power distribution system, transformers are used to convert the voltage of a high-voltage grid into a voltage suitable for use on the local grid.



  • Industrial applications: In a variety of industrial equipment, transformers are used to convert the grid voltage to the voltage suitable for the operation of a particular equipment.


  • Laboratory and research: In laboratories, transformers are used to generate specific voltages or currents to meet experimental needs.



Design and selection


When designing and selecting a transformer, the following factors need to be considered:


  • Load requirements: Select the appropriate conversion ratio according to the specific requirements of the load to ensure that the output voltage meets the requirements of the load.



  • Voltage level: Select the corresponding transformer according to the voltage level of the power system.



  • Capacity: Select the capacity of the transformer according to the maximum power requirements of the load.



  • Efficiency: Choose an efficient transformer to reduce energy loss.



  • Reliability: Select high-quality transformers to ensure long-term stable operation.


Give a tip and encourage the author!
Recommended
Adjustment and Precautions for H61 Oil Power 26kV Electric Transformer Tap Changers
Adjustment and Precautions for H61 Oil Power 26kV Electric Transformer Tap Changers
Preparatory Work Before Adjusting the Tap Changer of H61 Oil Power 26kV Electric Transformer Apply for and issue a work permit; carefully fill out the operation ticket; conduct a simulation board operation test to ensure the operation is error-free; confirm the personnel who will carry out and supervise the operation; if load reduction is required, notify affected users in advance. Before construction, power must be disconnected to take the transformer out of service, and voltage testing must be
James
12/08/2025
H59/H61 Transformer Failure Analysis and Protection Measures
H59/H61 Transformer Failure Analysis and Protection Measures
1.Causes of Damage to Agricultural H59/H61 Oil-Immersed Distribution Transformers1.1 Insulation DamageRural power supply commonly uses a 380/220V mixed system. Due to the high proportion of single-phase loads, H59/H61 oil-immersed distribution transformers often operate under significant three-phase load imbalance. In many cases, the degree of three-phase load imbalance far exceeds the limits permitted by operational regulations, causing premature aging, deterioration, and eventual failure of th
Felix Spark
12/08/2025
Top 5 Faults Found in H61 Distribution Transformers
Top 5 Faults Found in H61 Distribution Transformers
Five Common Defects of H61 Distribution Transformers1.Lead Wire DefectsInspection Method: The three-phase DC resistance imbalance rate significantly exceeds 4%, or one phase is essentially open-circuited.Remedial Measures: The core should be lifted for inspection to locate the defective area. For poor contacts, re-polish and tighten the connection. Poorly welded joints should be re-welded. If the welding surface area is insufficient, it should be enlarged. If the lead wire cross-section is inade
Felix Spark
12/08/2025
How Voltage Harmonics Affect H59 Distribution Transformer Heating?
How Voltage Harmonics Affect H59 Distribution Transformer Heating?
The Impact of Voltage Harmonics on Temperature Rise in H59 Distribution TransformersH59 distribution transformers are among the most critical equipment in power systems, primarily functioning to convert high-voltage electricity from the power grid into low-voltage electricity required by end users. However, power systems contain numerous nonlinear loads and sources, which introduce voltage harmonics that adversely affect the operation of H59 distribution transformers. This article will discuss i
Echo
12/08/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.