Case study of tank SF₆ circuit breaker failure: African market from a Nigerian perspective

Felix Spark
Felix Spark
Field: Failure and maintenance
China

Introduction

In the context of the African market, especially in Nigeria, the reliable operation of electrical equipment is of utmost importance for the stable development of the power industry. Tank - type SF₆ circuit breakers play a crucial role in power systems due to their excellent arc - extinguishing and insulating properties. However, like any electrical equipment, they are prone to failures. This paper presents a detailed case analysis of a tank - type SF₆ circuit breaker failure in Nigeria, taking into account aspects such as SONCAP certification and its implications for the market.

SONCAP (Standards Organization of Nigeria Conformity Assessment Program) certification is a mandatory requirement for electrical products entering the Nigerian market. It ensures that the products meet Nigerian industrial standards and are safe for use. The certification process involves product testing, factory inspections, and the issuance of a Certificate of Conformity, which is necessary for customs clearance.

 Case Background

In a power substation in Nigeria, a tank - type SF₆ circuit breaker of a certain brand, which had obtained SONCAP certification, experienced a failure. The circuit breaker was part of a key transmission line, and its failure had the potential to disrupt the power supply to a large area, including industrial and residential consumers.

The circuit breaker was installed and commissioned a few years ago, and it had been operating relatively stably until this incident. Regular maintenance and inspections had been carried out in accordance with the manufacturer's recommendations, and all previous tests had shown normal performance.

Failure Incident Description

One day, during normal grid operation, a fault occurred on the line protected by this tank - type SF₆ circuit breaker. The protection system detected the fault and issued a tripping command. However, the circuit breaker failed to open completely as expected. Instead, there was an abnormal arc - burning phenomenon inside the breaker, and partial insulation damage was observed later.

Figure 1 shows a simplified diagram of the power system layout where the circuit breaker was installed. 

The substation operators noticed unusual noises and temperature rises around the circuit breaker. Immediately, they initiated emergency procedures, including isolating the faulty circuit breaker from the grid as much as possible to prevent further damage and potential safety hazards.

Failure Analysis
Electrical Analysis

Through analyzing the fault records and waveform data from the substation's monitoring system, it was found that the fault current waveform was severely distorted during the incident. The current did not drop to zero within the expected time for the circuit breaker to effectively extinguish the arc. This was mainly due to the complex nature of the fault, which caused abnormal current flow patterns.

The SF₆ gas inside the circuit breaker, which is responsible for arc - extinguishing, also showed a decline in performance. Under normal circumstances, SF₆ gas can quickly recombine and restore its dielectric strength when the arc current crosses zero. However, in this case, the continuous non - zero current prevented the proper recovery of the gas's arc - extinguishing ability.

Mechanical Analysis

Upon visual inspection and further mechanical testing, it was discovered that some mechanical components of the circuit breaker showed signs of wear and tear. The moving parts, such as the contact arms and the operating mechanism linkages, had some minor deformations. These deformations might have affected the smooth operation of the circuit breaker during the tripping process, causing a delay in the separation of the contacts and thus prolonging the arcing time.

SONCAP Certification - related Considerations

Although the circuit breaker had SONCAP certification, a review of the certification process and the product's compliance with Nigerian standards was carried out. It was found that the product met all the specified requirements at the time of certification. However, during the operation in the Nigerian environment, factors such as the local power grid characteristics (e.g., higher harmonic content in some areas), temperature, and humidity variations might have influenced the performance of the circuit breaker.

In addition, the maintenance practices in the Nigerian substation were compared with international best practices. It was noted that while the basic maintenance procedures were followed, there might be some room for improvement in terms of more frequent and in - depth inspections, especially considering the harsh operating conditions in some parts of Nigeria.

Solutions and Preventive Measures
Repair and Replacement

The damaged components of the circuit breaker were identified, including some worn - out mechanical parts and the insulation materials that were affected by the arc. These components were replaced with new Upgraded Maintenance Strategies

A more comprehensive maintenance plan was developed for the circuit breaker and other similar equipment in the substation. This included more frequent inspections of mechanical components for wear and tear, regular testing of the SF₆ gas quality, and enhanced monitoring of electrical parameters such as current and voltage waveforms.

Training programs were also organized for the substation operators and maintenance staff. These programs focused on the latest international best practices for maintaining tank - type SF₆ circuit breakers, as well as how to deal with potential failures and emergencies more effectively.

Market - wide Considerations

In view of this failure case, for the African market, especially in Nigeria, it is recommended that more in - depth research be carried out on the adaptability of electrical equipment to local operating conditions. Manufacturers should consider providing customized solutions or additional instructions for products sold in regions with specific environmental and grid characteristics.

For the SONCAP certification process, it could be further improved to take into account the long - term performance of products in the Nigerian market. This might involve more follow - up inspections and performance evaluations after the products have been in operation for a certain period.

Conclusion

The failure of the tank - type SF₆ circuit breaker in the Nigerian power substation is a typical case that highlights the importance of comprehensive equipment management in the African market. While SONCAP certification provides a basic safeguard for product quality, continuous attention to the operation and maintenance of electrical equipment, as well as adaptation to local operating conditions, is essential.

By analyzing the failure from electrical, mechanical, and certification - related aspects, and implementing appropriate solutions and preventive measures, the reliability of power systems in Nigeria and other African countries can be significantly enhanced. This case also serves as a valuable reference for other similar projects in the region, emphasizing the need for a holistic approach to ensure the safe and stable operation of electrical infrastructure in the African market.

Give a tip and encourage the author!
Recommended
10kV RMU Common Faults & Solutions Guide
10kV RMU Common Faults & Solutions Guide
Application Issues and Handling Measures for 10kV Ring Main Units (RMUs)The 10kV ring main unit (RMU) is a common electrical distribution device in urban power distribution networks, primarily used for medium-voltage power supply and distribution. During actual operation, various issues may arise. Below are common problems and corresponding corrective measures.I. Electrical Faults Internal Short Circuit or Poor WiringA short circuit or loose connection inside the RMU can lead to abnormal operati
Echo
10/20/2025
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breaker Types & Fault Guide
High-Voltage Circuit Breakers: Classification and Fault DiagnosisHigh-voltage circuit breakers are critical protective devices in power systems. They rapidly interrupt current when a fault occurs, preventing damage to equipment from overloads or short circuits. However, due to long-term operation and other factors, circuit breakers may develop faults that require timely diagnosis and troubleshooting.I. Classification of High-Voltage Circuit Breakers1. By Installation Location: Indoor-type: Insta
Felix Spark
10/20/2025
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation!
10 Prohibitions for Transformer Installation and Operation! Never install the transformer too far away—avoid placing it in remote mountains or wilderness. Excessive distance not only wastes cables and increases line losses, but also makes management and maintenance difficult. Never choose transformer capacity arbitrarily. Selecting the right capacity is essential. If the capacity is too small, the transformer may be overloaded and easily damaged—overloading beyond 30% should not exceed two hours
James
10/20/2025
How to Maintain Dry-Type Transformers Safely?
How to Maintain Dry-Type Transformers Safely?
Maintenance Procedures for Dry-Type Transformers Put the standby transformer into operation, open the low-voltage side circuit breaker of the transformer to be maintained, remove the control power fuse, and hang a "DO NOT CLOSE" sign on the switch handle. Open the high-voltage side circuit breaker of the transformer under maintenance, close the grounding switch, fully discharge the transformer, lock the high-voltage cabinet, and hang a "DO NOT CLOSE" sign on the switch handle. For dry-type trans
Felix Spark
10/20/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.