Detailed comparison of China's latest power transformer energy efficiency standard GB 20052-2024 and the 2020 version, highlighting scope expansion, tightened loss limits (P0, Pk), and new requirements for renewable energy transformers.
1. Overview
The national standard for "Minimum Allowable Values of Energy Efficiency and the Energy Efficiency Grades for Power Transformers" has undergone a major update. The new version, GB 20052-2024, was issued on April 29, 2024, and is scheduled for official implementation on February 1, 2025, at which time it will fully replace the current GB 20052-2020.
This revision aligns with China's "Dual Carbon" goals, aiming to further enhance the energy efficiency of power equipment, phase out outdated capacity, and incorporate transformers in the renewable energy sector into the management scope for the first time.
2. Key Technical Differences
2.1 Expanded and Adjusted Scope
GB 20052-2024 has made significant adjustments to its scope to adapt to modern power grid structures:
2.2 "Upward Shift" of Energy Efficiency Grade Definitions
The new standard effectively sets the high-efficiency levels of the old standard as the new "entry-level" thresholds.
| Efficiency Grade |
GB 20052-2020 (Old) |
GB 20052-2024 (New) |
Trend |
|---|---|---|---|
| Level 1 (Highest) |
Equivalent to S20 (Oil) / SCB14 (Dry) |
Equivalent to S22+ (NX1) / SCB18 (NX1) |
Significant Increase |
| Level 2 (High) |
Equivalent to S15 / SCB13 |
Equivalent to S20 (NX2) / SCB14 (NX2) |
Old Level 1 becomes New Level 2 |
| Level 3 (Entry) |
Equivalent to S13 / SCB12 |
Equivalent to S13 (NX3) / SCB12 (NX3) |
Entry level remains stable |
Note: Legacy models such as S11 and SCB10/11, which were widely used, now fall below the minimum allowable energy efficiency limit (Level 3) and will be prohibited from production and sale after February 2025.
2.3 Tightening of Loss Limits (P0,Pk)
The 2024 standard focuses on controlling No-load loss (P0), encouraging the use of amorphous alloys and high-permeability silicon steel.
Comparison for a typical 10kV / 1000kVA transformer (approximate values):
| Transformer Type |
Parameter |
2020 Level 1 (S20) |
2024 Level 1 (S22) |
Reduction (Approx) |
|---|---|---|---|---|
| Oil-Immersed
|
No-load loss (P0) |
610 W |
~520 W |
↓ 15% |
| Load loss (Pk) |
8130 W |
~7800 W |
↓ 4% |
|
| Dry-Type
|
No-load loss (P0) |
1140 W |
~980 W |
↓ 14% |
| Load loss (Pk) |
7320 W |
~6950 W |
↓ 5% |
2.4 Changes in Testing and Evaluation Criteria
3. Implementation and Recommendations
4. Conclusion
The release of the GB 20052-2024 standard marks the official entry of China's transformer industry into the "High Energy Efficiency" era. For electrical engineers, it is necessary to focus not only on the efficiency improvements of traditional distribution transformers but also on technical selection for renewable energy supporting transformers, particularly in optimizing core materials and design processes to meet increasingly stringent no-load loss requirements.