Research on Reliability Enhancement Scheme Implementation for Modular Intelligent Prefabricated Substations

Echo
06/13/2025

1 Implementation Strategies for the Scheme
1.1 Deepen Survey and Research
Before constructing prefabricated cabin - type substations, it is necessary to conduct detailed surveys of local working conditions, clarify the construction scale and objectives, evaluate existing power facilities, plan projects, make up for infrastructure shortcomings, and adjust the construction rhythm. Meanwhile, control costs to avoid project suspension.
1.2 Strengthen Structural Construction
During promotion, multi - dimensional optimization is needed. Design and construction should balance safety and practicality, and incorporate innovative thinking. The cabinets of pre - installed substations adopt an integrated welded structure. The underframe, framework, etc., undergo anti - corrosion treatment for long - term durability; the double - layer structure + heat insulation design controls temperature, and the polyurethane insulation and six - degree anti - corrosion process help improve performance. The anti - corrosion diagram is shown in Figure 1.
The cabinet adopts a high - quality cold - rolled steel steel shell, with sufficient mechanical strength. The minimum top load is 2500N/m²; it can withstand an external mechanical impact energy of 20J, and the corresponding protection level conforms to IK10 specified in GB/T 20138. Meanwhile, it meets the seismic requirements of a horizontal acceleration of 0.3 (g) and a vertical acceleration of 0.15 (g), and has obtained the seismic report issued by the Institute of Engineering Mechanics, China Earthquake Administration.
1.3 Optimization of Internal Control Environment
Modular intelligent prefabricated cabin substations, despite their high flexibility, require critical optimization of the internal control environment. The interior should adopt a concise control model: enhancing response speed of control functions, predicting and eliminating risks, while also adapting to operators' habits for faster system feedback.
For instance, the structure uses "double - layer metal plates + single - layer metal decorative panels", incorporates refrigerator - style insulation technology with polyurethane foam filling, and applies thermal - break insulation to doors/windows (as shown in Figure 2), optimizing the environment at the physical level.
Considering climate and environment, in harsh areas (heavy wind - sand, extreme cold, high pollution), prefabricated cabins use micro - positive pressure dust - prevention tech. Cabin pressure stays at 1.05×external pressure for dust, moisture, and condensation prevention, ensuring equipment stability.
The micro - positive pressure AC integrates micro - positive pressure and air - conditioning systems. It supplies clean air to sealed cabins, keeping internal pressure slightly higher than external; air leaking from door/window gaps flows outward, blocking dust and creating a dust - free environment. The AC also regulates temperature and humidity for constancy. In winter’s low temperatures, as an industrial AC, it starts at - 30 °C, with electric auxiliary heating and the cabin’s good thermal insulation, maintaining a suitable internal operating environment.
1.4 Improving Design Details
Modular intelligent prefabricated cabin substations optimize functions via detail design, use materials complying with regulations, and deliver remarkable benefits.
(1) Lighting System
Explosion - proof LED corridor lights are installed in the inspection corridor, with self - starting emergency lights at both ends for power - off scenarios. Inspection lights are set in unit cabinets, with switches on the operation panel.
(2) Busbars & Cables
For busbars penetrating the cabin top, non - magnetic materials (stainless steel/aluminum) are used for clamps, door panels/frames to avoid eddy currents. Primary and secondary cables are laid independently in sealed channels: The primary channel uses double - layered galvanized sheets + aluminum silicate insulation (Class A fire resistance), matching cable layout. The secondary uses metal trunking, considering anti - interference and shielding.
(3) Settlement Response
Settlement easily damages high - current hard busbars. Thus, fully insulated segmented solid busbars are adopted. Wiring reserves soft - connection nodes and stress - relief bends to compensate for tension and maintain insulation.
1.5 Innovating Maintenance Mechanisms
The operation and maintenance mode should match modular features and cabin functions, ensuring safety, stability, and quick fault removal for upgrades.
1.5.1 Guardrails and Cabin Access Ladders
For multi - level substation construction, protective guardrails are installed around the second - floor cabin. Specifications of the cabin access ladder: The steps are flush with the base of the guardrails; the steps are grid - type (slope > 55°, width < 250mm, height difference between steps > 300mm ), and handrails are equipped on both sides (see Figure 3).
1.5.2 Reserved Test Openings for Cabinet Equipment
Cabinet - type equipment reserves test openings for test tooling installation and voltage - withstand tests. Daily inspection/maintenance uses the internal corridor (width ≥ 1200mm); during repairs, open the opposite inspection door. An emergency escape platform is installed – personnel evacuate to it and slide down in emergencies.
With reserved intervals, cabinet design leaves space for GIS expansion (considering reliability/ease). The top cover splits into 4 modules. For expansion, remove relevant covers, hoist expanded GIS into the cabinet, and assemble.
2 Development Trends
Modular intelligent prefabricated cabin substations need innovative development: The control system integrates intelligent, automation, and big - data technologies to break through the limitations of traditional control, accurately locate and resolve faults; strengthen safety protection, identify external impacts (e.g., lightning protection), and improve drills for extreme disasters.
3 Conclusion
Modular intelligent prefabricated cabin substations can solve problems of traditional construction and support long - term optimization. In the future, the technical system needs to be improved, integrating construction technologies, equipment, and management; during promotion, connect with existing power projects and systems to achieve sustainable development.
Echo

As an expert in the application and trends of electrical equipment, I have a profound mastery of knowledge in circuits, power electronics, etc. I possess a comprehensive set of abilities including equipment design, fault diagnosis, and project management. I can precisely grasp the industry's pulse and lead the development of the electrical field.

Research on Low - Voltage Anti - DC Current Transformer and Detection Device
Research on Low - Voltage Anti - DC Current Transformer and Detection Device
1. Overview of Components and IssuesTA (low-voltage current transformer) and electric energy meters are key components of low-voltage electric energy metering. The load current of such meters is no less than 60A. Electric energy meters vary in type, model, and anti-DC performance, and are connected in series in the metering device. Due to the lack of anti-DC capability, they suffer from metering errors under DC component loads, usually caused by non-linear loads. With the increasing use of DC or
Dyson
07/16/2025
Anti - Theft Device for Low - Voltage Current Transformers
Anti - Theft Device for Low - Voltage Current Transformers
1. Innovation BackgroundWith the progress of society and economic development, the electricity demand of power users is expanding increasingly. Lawbreakers, aiming to save electricity costs and pursue high profits, gradually use high - tech methods to steal electricity, causing huge economic losses to power supply enterprises. Currently, popular electricity theft methods in the market include illegally opening the wiring cover of low - voltage transformers in electric energy metering boxes, alte
Dyson
07/16/2025
What aspects should be taken into consideration during the design of AIS voltage transformers?
What aspects should be taken into consideration during the design of AIS voltage transformers?
I. Key Elements of Mechanical Structure DesignThe mechanical structure design of AIS voltage transformers ensures long - term stable operation. For 66 kV outdoor AIS voltage transformers (pillar - type structure):Pillar Material: Use epoxy resin casting + metal frame for mechanical strength, pollution/weather resistance. Special design needed for 66 kV (vs 35 kV & below). Dry - type insulation (porcelain/epoxy shell) requires sufficient bending/impact resistance for harsh outdoors.Heat Dissi
Dyson
07/15/2025
Analysis of Gas Concentration in High - Voltage Reactors of Large - Scale Hydroelectric Generator Sets
Analysis of Gas Concentration in High - Voltage Reactors of Large - Scale Hydroelectric Generator Sets
1.Gas Generation and Analysis Principle of High - Voltage ReactorsHigh - voltage reactors use oil and insulating paper for insulation. Normal operation may see local overheating or discharges (e.g., iron core/winding issues, inter - turn short circuits), causing insulation cracking and producing gases like hydrocarbons (methane, etc.), CO, CO2, H2). These gases reflect internal insulation status, enabling real - time monitoring.For closed oil - filled reactors, insulation aging and oil oxidation
Oliver Watts
07/11/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!