Symmetrical & Unsymmetrical Faults

Encyclopedia
04/25/2025

Under normal operating conditions, a power system functions in a balanced state, with electrical parameters such as voltage and current distributed evenly across all phases. However, when insulation fails at any point within the system or live wires come into unintended contact, the system's balance is disrupted, leading to a short - circuit or fault in the line. Faults in power systems can be triggered by a multitude of factors. Natural phenomena like lightning strikes, powerful high - speed winds, and earthquakes can physically damage electrical infrastructure and cause insulation breakdown. Additionally, external events such as trees falling onto power lines, birds creating electrical shorts by bridging conductors, or the degradation of insulation materials over time can also initiate faults.

Faults that occur in transmission lines are typically categorized into two broad types:

Symmetrical Faults

Symmetrical faults involve the simultaneous short - circuiting of all phases within a multi - phase electrical system, often with a connection to the earth as well. What characterizes these faults is their balanced nature; even after the fault occurs, the system maintains its symmetry. In a three - phase setup, for example, the electrical relationships between the phases remain consistent, with the lines effectively displaced by an equal angle of 120°. Despite being relatively rare, symmetrical faults are the most severe type of electrical faults in power systems, as they generate extremely high fault currents. These large - magnitude currents can cause significant damage to equipment and disrupt power supply if not properly managed. Due to their severity and the challenges they pose, engineers perform balanced short - circuit calculations specifically designed to accurately determine the magnitude of these large currents. This information is crucial for designing protective devices, such as circuit breakers, that can safely interrupt the flow of current during a symmetrical fault and safeguard the integrity of the power system.

image.png

Unsymmetrical Faults

Unsymmetrical faults are characterized by their involvement of only one or two phases within a power system, leading to an imbalance among the three - phase lines. These faults typically manifest as connections either between a line and the ground (line - to - ground) or between two lines (line - to - line). An unsymmetrical series fault occurs when there is an abnormal connection between phases or between a phase and the ground, while an unsymmetrical shunt fault is identified by an imbalance in the line impedances.

In a three - phase electrical system, shunt faults can be further classified as follows:

  • Single Line - to - Ground Fault (LG): This fault occurs when one of the conductors makes contact with the ground or the neutral conductor.

  • Line - to - Line Fault (LL): Here, two conductors are short - circuited, disrupting the normal current flow.

  • Double Line - to - Ground Fault (LLG): In this scenario, two conductors come into contact with the ground or the neutral conductor simultaneously.

  • Three - Phase Short - Circuit Fault (LLL): All three phases are short - circuited to each other.

  • Three - Phase - to - Ground Fault (LLLG): All three phases are short - circuited to the ground.

It's important to note that LG, LL, and LLG faults are unsymmetrical, while LLL and LLLG faults fall under the category of symmetrical faults. Given the significant currents generated during symmetrical faults, engineers perform balanced short - circuit calculations to accurately determine these high - magnitude currents, which is essential for designing effective protective measures.

Effect of Faults on Transmission Lines

Faults can have a detrimental impact on power systems in multiple ways. When a fault occurs, it often causes a significant increase in voltages and currents at specific points within the system. These elevated electrical values can damage the insulation of equipment, thereby reducing its lifespan and potentially leading to costly repairs or replacements. Moreover, faults can undermine the stability of the power system, causing three - phase equipment to operate inefficiently or even malfunction. To prevent the spread of damage and ensure the uninterrupted operation of the overall system, it is crucial to promptly isolate the faulty section as soon as a fault is detected. By disconnecting the affected area, the normal operation of the remaining parts of the power system can be maintained, minimizing the impact on power supply and reducing the risk of further failures.

Encyclopedia

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

How to Design and Install a Solar PV System?
How to Design and Install a Solar PV System?
Design and Installation of Solar PV SystemsModern society relies on energy for daily needs like industry, heating, transport, and agriculture, mostly met by non-renewable sources (coal, oil, gas). However, these cause environmental harm, are unevenly distributed, and face price volatility due to limited reserves—driving demand for renewable energy.Solar energy, abundant and capable of meeting global needs, stands out. Standalone PV systems (Fig 1) offer energy independence from utilities.
Edwiin
07/17/2025
Load Frequency Control (LFC) & Turbine Governor Control (TGC) in Power System
Load Frequency Control (LFC) & Turbine Governor Control (TGC) in Power System
Brief Introduction to Thermal Generating UnitsElectricity generation relies on both renewable and non - renewable energy resources. Thermal generating units represent a conventional approach to power production. In these units, fuels such as coal, nuclear energy, natural gas, biofuel, and biogas are combusted within a boiler.The boiler of a generating unit is an extremely complex system. In its simplest conception, it can be visualized as a chamber whose walls are lined with pipes, through which
Edwiin
06/06/2025
Why 3-Phase Power? Why Not 6, 12 or More for Power Transmission?
Why 3-Phase Power? Why Not 6, 12 or More for Power Transmission?
It is well-known that single-phase and three-phase systems are the most prevalent configurations for power transmission, distribution, and end-use applications. While both serve as fundamental power supply frameworks, three-phase systems offer distinct advantages over their single-phase counterparts.Notably, multi-phase systems (such as 6-phase, 12-phase, etc.) find specific applications in power electronics—particularly in rectifier circuits and variable frequency drives (VFDs)—wher
Edwiin
06/05/2025
How Many Poles and Towers are Situated Within a 1-km Span?
How Many Poles and Towers are Situated Within a 1-km Span?
The number of distribution poles and transmission towers within a 1-kilometer stretch of overhead lines varies significantly based on multiple factors, including voltage level, power line type, supporting structure, geographical location, local regulations, and specific grid requirements.In urban areas, distribution utility poles are typically positioned at closer intervals, while in rural regions, they are spaced farther apart. Additionally, the use of taller structures for higher-voltage trans
Edwiin
06/05/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!